PDU2-MIB DEFINITIONS ::= BEGIN

IMPORTS
    MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE                         FROM SNMPv2-SMI
    enterprises, Integer32, Unsigned32, IpAddress                           FROM SNMPv2-SMI
    MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUP FROM SNMPv2-CONF
    TEXTUAL-CONVENTION, DisplayString, MacAddress, TruthValue, RowPointer   FROM SNMPv2-TC
    InetAddressType, InetAddress, InetPortNumber FROM INET-ADDRESS-MIB
    sysContact, sysName, sysLocation FROM RFC1213-MIB;


raritan MODULE-IDENTITY
    LAST-UPDATED "201406040000Z"      -- June 04, 2014
    ORGANIZATION "Raritan"
    CONTACT-INFO "
                  Author:       Raritan Americas, Inc.
                  postal:       Raritan Americas, Inc.
                                400 Cottontail Lane
                                Somerset, NJ 08873
                  email:        tech@raritan.com
                  phone:        +1 732 764 8886
                 "
    DESCRIPTION  "This MIB describes the SNMP functions of the Dominion PX G2
                  Power Distribution Unit by Raritan Computer."


    REVISION     "201406040000Z"      -- June 04, 2014

    DESCRIPTION "PX2 release 3.0.0:
                  - Support for signed sensor readings
                  - Support for unit-level power and energy sensors
                  - Send trap on peripheral device firmware update
                  - Allow peripheral device auto management to be disabled
                  - Allow front panel outlet switching to be enabled or disabled
                  - Support DX-PIR occupancy sensor

                 1) Changed the SYNTAX from Integer32 to Unsigned32:
                      measurementsUnitSensorValue
                 2) Added signed value, range and threshold columns to:
                      unitSensorConfigurationTable
                      unitSensorMeasurementsTable
                      pduSensorStateChange
                      inletSensorConfigurationTable
                      inletSensorMeasurementsTable
                      inletSensorLogTable
                      inletSensorStateChange
                      inletPoleSensorConfigurationTable
                      inletPoleSensorMeasurementsTable
                      inletPoleSensorLogTable
                      inletPoleSensorStateChange
                      overCurrentProtectorSensorConfigurationTable
                      overCurrentProtectorSensorMeasurementsTable
                      overCurrentProtectorSensorLogTable
                      overCurrentProtectorSensorStateChange
                      outletSensorConfigurationTable
                      outletSensorMeasurementsTable
                      outletSensorLogTable
                      outletSensorStateChange
                      outletPoleSensorConfigurationTable
                      outletPoleSensorMeasurementsTable
                      outletPoleSensorLogTable
                      outletPoleSensorStateChange
                 3) Added unsigned value, range and threshold columns to:
                      unitSensorLogTable
                      transferSwitchSensorConfigurationTable
                      transferSwitchSensorMeasurementsTable
                      transferSwitchSensorLogTable
                      transferSwitchSensorStateChange
                 4) Added UnitSensorControlTable
                 5) Added unitSensorReset and unitSensorStateChange traps
                 6) Deprecated pduSensorStateChange trap
                 7) Added to unitConfigurationTable:
                      peripheralDevicesAutoManagement
                      frontPanelOutletSwitching
                      frontPanelRCMSelfTest
                      frontPanelActuatorControl
                 8) Added to externalSensorConfigurationTable:
                      externalSensorAlarmedToNormalDelay
                 9) Deprecated:
                      wireCount in unitConfiguraionTable
                      tables for wireSensors
                      traps for wireSensors
                 10) SensorStateEnumeration: Added
                      fail(14)
                 11) ProductTypeEnumeration: Renamed
                      rackSts(2) to transferSwitch
                 12) Added:
                      PeripheralDeviceFirmwareUpdateStateEnumeration
                      peripheralDeviceFirmwareUpdateState
                      peripheralDeviceFirmwareUpdate trap
                 13) Added userName to the following traps:
                      bulkConfigurationSaved
                      bulkConfigurationCopied
                      lhxSupportChanged
                      deviceSettingsSaved
                      deviceSettingsRestored
                 "


    REVISION     "201401090000Z"      -- January 9, 2014

    DESCRIPTION "PX2 release 2.6.0:
                  - Support for PX3TS transfer switches

                 1) SensorTypeEnumeration:
                    Removed:
                      scrOpenStatus
                      scrShortStatus
                    Added:
                      i1SmpsStatus(46)
                      i2SmpsStatus(47)
                      switchStatus(48)
                 2) SensorStateEnumeration:
                    Removed:
                      marginal
                      fail
                    Added:
                      i1OpenFault(22)
                      i1ShortFault(23)
                      i2OpenFault(24)
                      i2ShortFault(25)
                      fault(26)
                      warning(27)
                      critical(28)
                 3) unitDeviceCapabilities: Added
                      i1SmpsStatus(45)
                      i2SmpsStatus(46)
                 4) transferSwitchCapabilities: Added
                      switchStatus(47)
                 5) Added transferSwitchConfiguration table
                 6) unitSensorLogTable:
                    Removed:
                      logUnitSensorAvgValue
                      logUnitSensorMaxValue
                      logUnitSensorMinValue
                    Added:
                      logUnitSensorSignedAvgValue
                      logUnitSensorSignedMaxValue
                      logUnitSensorSignedMinValue
                 "


    REVISION     "201401070000Z"      -- January 7, 2014

    DESCRIPTION  "PX2 release 2.5.30:
                   - Accumulating sensors (energy counters) can be reset
                   - Sensor accuray and tolerance variables are deprecated

                   1) Added peripheralDevicePackagePosition and peripheralDevicePackageState
                   2) Added radiusError trap
                   3) Added serverReachabilityError trap
                   4) Deprecated the following:
                           unitSensorConfigurationTable/unitSensorAccuracy
                           unitSensorConfigurationTable/unitSensorTolerance
                           inletSensorConfigurationTable/inletSensorAccuracy
                           inletSensorConfigurationTable/inletSensorTolerance
                           inletPoleSensorConfigurationTable/inletPoleSensorAccuracy
                           inletPoleSensorConfigurationTable/inletPoleSensorTolerance
                           outletSensorConfigurationTable/outetSensorAccuracy
                           outletSensorConfigurationTable/outletSensorTolerance
                           outletPoleSensorConfigurationTable/outetPoleSensorAccuracy
                           outletPoleSensorConfigurationTable/outletPoleSensorTolerance
                           overCurrentProtectorSensorConfigurationTable/overCurrentProtectorSensorAccuracy
                           overCurrentProtectorSensorConfigurationTable/overCurrentProtectorSensorTolerance
                           externalSensorConfigurationTable/externalSensorAccuracy
                           externalSensorConfigurationTable/externalSensorTolerance
                           wireSensorConfigurationTable/wireSensorAccuracy
                           wireSensorConfigurationTable/wireSensorTolerance
                           transferSwitchSensorConfigurationTable/transferSwitchSensorAccuracy
                           transferSwitchSensorConfigurationTable/transferSwitchSensorTolerance
                   5) Added inletSensorReset and outletSensorReset traps
                   6) Added inletSensorControl and inletSensorControlTable
                   7) Added outletSensorControl and outletSensorControlTable
		   8) Added unknownPeripheralDeviceAttached trap
                 "


    REVISION     "201311210000Z"      -- November 21, 2013

    DESCRIPTION  "PX2 release 2.5.20:
                   - Support for residual current monitors
                   - Support for USB cascading with one IP address
                   - Support for line-neutral voltage sensors

                   1) SensorTypeEnumeration: Added
                        rmsVoltageLN(25)
                        residualCurrent(26)
                        rcmState(27)
                   2) SensorStateEnumeration: Added
                        warning(27)
                        critical(28)
                        selfTest(29)
                   3) inletDeviceCapabilities: Added
                        residualCurrent(26)
                        rcmState(27)
                   4) Added rmsVoltageLN(24) to inletPoleCapabilities
                   5) Added inletRCMResidualOperatingCurrent to inletConfigurationTable
                   6) Added rcmControl under control
                   7) Added rcmSelfTestTable under rcmControl
                   8) Added DeviceCascadeTypeEnumeration
                   9) Added deviceCascadeType, deviceCascadePosition to unitConfigurationTable
                  10) Added agentInetPortNumber under trapInformation
                  11) Added agentInetPortNumber as a varbind to all traps
                  12) Added peripheralDevicePackageTable containing information on peripheral
                            device packages
                 "


    REVISION     "201309180000Z"      -- September 18, 2013

    DESCRIPTION  "
                  1) Added serverConnectivityUnrecoverable trap
             
                 "


    REVISION     "201308010000Z"      -- August 1, 2013

    DESCRIPTION  "
                  1) Add RCBO OCP types
             
                 "

    REVISION     "201307100000Z"      -- July 10, 2013

    DESCRIPTION  "
                  1) Added externalSensorTypeDefaultThresholdsTable 
             
                 "


    REVISION     "201307020000Z"      -- July 2, 2013

    DESCRIPTION  "
                  1) Added relayBehaviorOnPowerLoss to unitConfigurationTable
                 "


    REVISION     "201305210000Z"      -- May 21, 2013

    DESCRIPTION  "
                  1) Added inletEnableState to inletConfigurationTable
                  2) Added traps: inletEnabled and inletDisabled
                 "


    REVISION     "201304260000Z"      -- April 26, 2013

    DESCRIPTION  " 
                  1) Added traps: webcamInserted and webcamRemoved 
                  2) Added trapInformation parameters: webcamModel,webcamConnectionPort
            
                 "


    REVISION     "201303270000Z"      -- March 27, 2013

    DESCRIPTION  " 
                  1) Changed outletSource to outletPowerSource in outletConfigurationTable
                  2) Changed transferSwitchSource1 and transferSwitchSource2 to 
                             transferSwitchPowerSource1 and transferSwitchPowerSource2  in  transferSwitchConfigurationTable
                  3) Changed overCurrentProtectorSource to overCurrentProtectorPowerSource in overCurrentProtectorConfigurationTable
                  4) Changed wireSource to wirePowerSource in wireConfigurationTable
                  
                 "

    REVISION     "201303251000Z"      -- March 25, 2013

    DESCRIPTION  " 
                  1) Added comments showing the possible states for each sensor type.          
                 "


    REVISION     "201303250000Z"      -- March 25, 2013

    DESCRIPTION  " 
                  1) Added outletSource to outletConfigurationTable
                  2) Added transferSwitchSource1 and transferSwitchSource2 to transferSwitchConfigurationTable
                  3) Added overCurrentProtectorSource to overCurrentProtectorConfigurationTable
                  4) Added wireSource to wireConfigurationTable
                  
                 "


    REVISION     "201303180000Z"      -- March 18, 2013

    DESCRIPTION  " 1) Added meteringControllerCount to the unitConfigurationTable 
                   2) Added meteringController to BoardTypeEnumeration
                 "


    REVISION     "201302250000Z"      -- February 25, 2013

    DESCRIPTION  " 
                  1) Added ProductTypeEnumeration
                  2) Added productType to unitConfigurationTable
                 "


    REVISION     "201302040000Z"      -- February 04, 2013

    DESCRIPTION  " 1) Added TransferSwitchTransferReasonEnumeration
                   2) Added transferSwitchLastTransferReason to transferSwitchControlTable
                   3) Added transferSwitchLastTransferReason to transferSwitchSensorStateChange trap
                 "


    REVISION     "201301240000Z"      -- January 24, 2013
 
    DESCRIPTION  "Added required sensor types and units
                 "

    REVISION     "201211200000Z"      -- November 20, 2012

    DESCRIPTION  "1) Added  externalSensorIsActuator and externalSensorPosition to the externalSensorConfigurationTable
                  2) Added actuatorControlTable
                 "


    REVISION     "201211150000Z"      -- November 15, 2012

    DESCRIPTION  "1) Removed transferSwitchOutputCapabilities from transferSwitchConfigurationTable
                  2) Removed the following tables:
                       transferSwitchOutputSensorConfigurationTable
                       transferSwitchOutputSensorLogTable
                       transferSwitchOutputSensorMeasurementsTable
                  3) Removed transferSwitchOutputSensorStateChange trap
                  4) Added transferSwitchControlTable
                  5) Removed the following entries from SensorTypeEnumeration:
                       overTemperatureFault
                       fans
                       internalFault
                       inletPhaseDeviationFault
                       overloadFault
                  6) Added the following entries to SensorTypeEnumeration:
                       overloadStatus
                       overheatStatus
                       scrOpenStatus
                       scrShortStatus
                       fanStatus
                       inletPhaseSyncAngle
                       inletPhaseSync
                  7) Added the following entries to SensorStateEnumeration:
                       inSync,
                       outOfSync
                  8) Renamed transferSwitchNoTransferIfPhaseDeviationFault to
                     transferSwitchAutoReTransferRequiresPhaseSync
                 "


    REVISION     "201210050000Z"      -- October 5, 2012

    DESCRIPTION  "1) Modified the DESCRIPTION of the following.
                          outletSwitchControlTable
                          transferSwitchOutputSensorMeasurementsEntry 
                          overCurrentProtectorSensorMeasurementsEntry
                          outletPoleSensorMeasurementsEntry
                          transferSwitchOutputSensorLogEntry
                          transferSwitchOutputSensorLogTable
                          wireSensorLogEntry
                          externalSensorNumber
                          controllerConfigurationEntry
                          SensorUnitsEnumeration 
                          measurementsGroup
                          logGroup
                 "



    REVISION     "201210040000Z"      -- October 4, 2012

    DESCRIPTION  "1) In the transferSwitchConfigurationTable,
                       replaced  transferSwitchFrequencyDeviation with
                                 transferSwitchLowerMarginalFrequency and transferSwitchUpperMarginalFrequency
                 "


    REVISION     "201209280000Z"      -- September 28, 2012

    DESCRIPTION  "1) Modified the DESCRIPTION of the following.
                          bulkConfigurationCopied, userModified, userSessionTimeout
                 "

 
    REVISION     "201209210000Z"      -- September 21, 2012

    DESCRIPTION  "1) Added the following traps:
                          deviceSettingsSaved,  deviceSettingsRestored
                 "


    REVISION     "201209200000Z"      -- September 20, 2012

    DESCRIPTION  "1) Added the following objects to the transferSwitchConfigurationTable:
                          transferSwitchInternalFaultType 
                  2) Added transferSwitchInternalFaultType to transferSwitchSensorStateChange trap
                  3) Added marginal to SensorStateEnumeration
                 "


    REVISION     "201209170000Z"      -- September 17, 2012

    DESCRIPTION  "Deprecated the following objects from the unitConfigurationTable
                          pxInetAddressType, 
                          pxInetIPAddress,                  
                          pxInetNetmask,                    
                          pxInetGateway  
                 
                 "

    REVISION     "201209040000Z"      -- September 4, 2012

    DESCRIPTION  "Support for transfer Switch objects and sensors.
                  1. Added transferSwitchCount to unitConfigurationTable
                  2. Added the following tables:
                       transferSwitchConfigurationTable,
                       transferSwitchSensorConfigurationTable,
                       transferSwitchSensorLogTable,
                       transferSwitchSensorMeasurementsTable
                       transferSwitchOutputSensorConfigurationTable,
                       transferSwitchOutputSensorLogTable,
                       transferSwitchOutputSensorMeasurementsTable
                 3. Added 
                       transferSwitchSensorStateChange trap
                       transferSwitchOutputSensorStateChange trap
                 
                 "
    
    REVISION     "201206220000Z"      -- June 22, 2012

    DESCRIPTION  "
                  1. Added surgeProtectorStatus to SensorTypeEnumeration
                  2. Added surgeProtectorStatus to inletDeviceCapabilities
                 "


    REVISION     "201206180000Z"      -- June 18, 2012

    DESCRIPTION  "Added a comment before the section listing the traps.
                   The comment notes that the pxInetIPAddressType and  
                  pxInetIPAddress fields are not used for IPv6 traps
                 "





    REVISION     "201206060000Z"      -- June 6, 2012

    DESCRIPTION  "Support for wire objects and sensors.
                  1. Added wireCount to unitConfigurationTable
                  2. Added the following tables:
                       wireConfigurationTable,
                       wireSensorConfigurationTable,
                       wireSensorLogTable,
                       wireSensorMeasurementsTable
                 3. Added wireSensorStateChange trap
                 "


    REVISION	 "201205250000Z"      -- May 25, 2012

    
    DESCRIPTION  "added userAccepted/DeclinedRestrictedServiceAgreement traps"
    
    REVISION     "201205150000Z"      -- May 15, 2012
    
    DESCRIPTION  "
                  1. Added support for NTP servers.
                     Added the following objects under info
                       synchronizeWithNTPServer, useDHCPProvidedNTPServer,
                       firstNTPServerAddressType, firstNTPServerAddress,
                       secondNTPServerAddressType, secondNTPServerAddress
                 
                 "
   

    REVISION     "201203260000Z"      -- March 26, 2012
    
    DESCRIPTION  "added lhxSupportChanged trap."
    

    REVISION     "201112130000Z"      -- December 13, 2011
    
    DESCRIPTION  "
                  1. Added usbSlaveConnected, usbSlaveDisonnected traps
                 
                 "




    REVISION     "201111290000Z"      -- November 29, 2011
    
    DESCRIPTION  "
                  1. Added cascadedDeviceConnected to UnitConfigurationEntryStruct
                 
                 "


    REVISION     "201110250000Z"      -- October 25, 2011
    
    DESCRIPTION  "
                  1. Added DeviceIdentificationParameterEnumeration
                  2. Added deviceIdentificationChanged Trap
                  3. Added sysContact, sysName, sysLocation to all traps
                 
                 "


    REVISION     "201106160000Z"      -- June 16, 2011
    
    DESCRIPTION  "
                  1. Changed DESCRIPTION of outletSequencingDelay
                 
                 "


    REVISION     "201103220000Z"      -- March 22, 2011
    
    DESCRIPTION  "
                  1. Added rfCodeTagConnected, rfCodeTagDisconnected traps 
                  2. Changed MAX-ACCESS for externalOnOffSensorSubtype to read-write
                 "


    REVISION     "201102210000Z"      -- February 21, 2011
    
    DESCRIPTION  "
                  1. Added rpm(19) to SensorUnitsEnumeration
                  "


    REVISION     "201102140000Z"      -- February 14, 2011
    
    DESCRIPTION  "
                  1. Changed 5WIRE IEC60309 enumerations from 250V to 208V
                  "

    REVISION     "201102080000Z"      -- February 8, 2011
    
    DESCRIPTION  "
                  1. Removed OnOffSensorSubtypeEnumeration
                  2. Changed SYNTAX of externalOnOffSensorSubtype to SensorTypeEnumeration
                  3. Added binary, contact, fanspeed, none to SensorTypeEnumeration
                  4. Changed outletPoleCapabilities to be the same as inletPoleCapabilities
                  "

    REVISION     "201102030000Z"      -- February 3, 2011
    
    DESCRIPTION  "
                  1. Added externalSensorSerialNumber,externalOnOffSensorSubtype, externalSensorChannelNumber
                     to the externalSensorStateChange trap."

    REVISION     "201101310000Z"      -- January 31, 2011
    
    DESCRIPTION  "
                  1. Modifed the DESCRIPTION of the powerControl trap
                 "


    REVISION     "201012150000Z"      -- December 15, 2010
    
    DESCRIPTION  "
                  1. Added dataLoggingEnableForAllSensors to logConfigurationTable
                 "


    REVISION     "201012131131Z"      -- December 13, 2010
    
    DESCRIPTION  "
                  1. Added inrushGuardDelay to unitConfigurationTable
                  2. Added outletSequenceDelay to outletConfigurationTable
                  3. Deprecated outletSequencingDelay
                 "


    REVISION     "201012130000Z"      -- December 13, 2010
    
    DESCRIPTION  "1. Added externalOnOffSensorSubtype to ExternalSensorConfigurationEntryStruct
                  2. Added OnOffSensorSubtypeEnumeration
                  3. Added alarmed to SensorStateEnumeration
                  4. Removed firmwareFileDiscarded trap
                  5. Removed securityViolation trap
                 "


    REVISION     "201012070000Z"      -- December 7, 2010

    DESCRIPTION  "1. changed  DESCRIPTION  of measurementPeriod to say that the value is fixed at 1 second.
                  "

    REVISION     "201010070000Z"      -- October 7, 2010

    DESCRIPTION  "1. added ocpFUSEPAIR(5) to OverCurrentProtectorTypeEnumeration
                  2. changed  ocpFUSE1POLE(4) to ocpFUSE(4) in OverCurrentProtectorTypeEnumeration
                  "

    REVISION     "201010040000Z"      -- October 4, 2010

    DESCRIPTION  "1. added ocpFUSE2POLE(5) to OverCurrentProtectorTypeEnumeration
                  2. changed ocpFUSE(4) to ocpFUSE1POLE(4) in OverCurrentProtectorTypeEnumeration
                  "

    REVISION     "201009010000Z"      -- September 1, 2010
    
    DESCRIPTION  "1. Removed userName from serverNotReachable and serverReachable traps
                  "

    REVISION     "201008050000Z"      -- August 5, 2010
    
    DESCRIPTION  "1. Added reliabilityDataTableSequenceNumber
                  2. Changed SYNTAX of reliabilityErrorLogIndex to Integer32(1..2147483647)"

    REVISION     "201007230000Z"      -- July 23, 2010
    
    DESCRIPTION  "1. Moved serverCount to unitConfigurationTable "


    REVISION     "201007220000Z"      -- July 22, 2010
    
    DESCRIPTION  "1. Added support for the Reliability Tables
                  2. Added new group reliabilityGroup
                  3. Defined nodes reliability,reliabilityData,reliabilityErrorLog                        
                  4. Added reliabilityDataTable & reliabilityErrorLogTable"



    REVISION     "201007210000Z"      -- July 21, 2010
    
    DESCRIPTION  "1. Added plug56PA320 to PlugTypeEnumeration
                  2. Added plug56P320F to PlugTypeEnumeration"

    REVISION     "201007140000Z"      -- July 14, 2010
    
    DESCRIPTION  "1. Added the following traps:
                    pingServerEnabled, pingServerDisabled, serverNotReachable, serverReachable
                  2. Added the serverReachabilityTable  
                 "


    REVISION     "201007060000Z"      -- July 6, 2010
    
    DESCRIPTION  "1. Added externalSensorChannelNumber to externalSensorConfigurationTable
                  "
                                    

    
    REVISION     "201007010000Z"      -- July 1, 2010
    
    DESCRIPTION  "1. added outletSwitchingState to outletSwitchControlTable
                  2. added outletSwitchingTimeStamp to outletSwitchControlTable"
                                    
   

    REVISION     "201006300000Z"      -- June 30, 2010
    
    DESCRIPTION  "1. added switchingOperation to the powerControl trap
                  "


    REVISION     "201006210000Z"      -- June 21, 2010
    
    DESCRIPTION  "1. added support for Load shedding
                  2. added loadShedding to the unitConfigurationTable.
                  3. added nonCritical to the outletConfigurationTable
                  4. added loadSheddingModeEntered & loadSheddingModeExited traps
                  5. modified description of inletPlug in inletConfigurationTable"

    REVISION     "201006030000Z"      -- June 3, 2010
    
    DESCRIPTION  "1. added plugOTHER to PlugTypeEnumeration
                  2. added receptacleOTHER to ReceptacleTypeEnumeration
                  3. added inletPlugDescriptor to inletConfigurationTable
                  4. added outletReceptacleDescriptor to outletConfigurationTable
                  "

    REVISION     "201005270000Z"      -- May 27, 2010
    
    DESCRIPTION  "1. added INetAddressType and INetAddress to represent IP addresses
                  2. unitConfigurationTable: deprecated pxIpAddress
                  3. unitConfigurationTable: added pxInetAddressType,pxInetIPAddress,pxInetNetmask,pxInetGateway
                  2: added pxInetAddressType,pxInetIPAddress to all traps
                  3: defined new trap deviceUpdateFailed"

    REVISION     "201005240000Z"      -- May 24, 2010
    
    DESCRIPTION  "Added typeOfSensor to externalSensorStateChange trap"

    REVISION     "201004190000Z"      -- April 19, 2010
    
    DESCRIPTION  "modified the DESCRIPTION of the deviceUpdateCompleted trap"

    REVISION     "201004150000Z"      -- April 15, 2010
    
    DESCRIPTION  "modified the DESCRIPTION of all SensorStateChangeDelay parameters"


    REVISION     "201004080000Z"      -- April 8, 2010
    
    DESCRIPTION  "modified the DESCRIPTION of sensor parameters that do not apply to discrete sensors"

    REVISION     "201003290000Z"      -- March 29, 2010
    
    DESCRIPTION  "added trap ldapError"


    REVISION     "201003250000Z"      -- March 25, 2010
    
    DESCRIPTION  "changed the SYNTAX of the following objects from Integer32 to Unsigned32:
                       logInletSensorMaxValue,
                       logInletSensorMinValue,
                       logInletSensorAvgValue,
                       logInletPoleSensorMaxValue,
                       logInletPoleSensorMinValue,
                       logInletPoleSensorAvgValue,
                       logOutletSensorMaxValue,
                       logOutletSensorMinValue,
                       logOutletSensorAvgValue,
                       logOutletPoleSensorMaxValue,
                       logOutlePoletSensorMinValue,
                       logOutletPoleSensorAvgValue,
                       logOverCurrentProtectorSensorMaxValue,
                       logOverCurrentProtectorSensorMinValue,
                       logOverCurrentProtectorSensorAvgValue,
                       measurementsInletSensorValue,
                       measurementsInletPoleSensorValue,
                       measurementsOutletSensorValue,
                       measurementsOutletPoleSensorValue,
                       measurementsOverCurrentProtectorSensorValue"

    REVISION     "201003160000Z"      -- March 16, 2010
    
    DESCRIPTION  "added trap smtpMessageTransmissionFailure"

    REVISION     "201003010000Z"      -- March 1, 2010
    
    DESCRIPTION  "changed externalSensorsZCoordinateUnits to an Enumeration"

    REVISION     "201001290000Z"      -- January 29, 2010
    
    DESCRIPTION  "The first version of the MIB."

    
    
       
		::= { enterprises 13742 }

pdu2		OBJECT IDENTIFIER ::= { raritan 6 }

traps                        OBJECT IDENTIFIER ::= { pdu2 0 }
trapInformation              OBJECT IDENTIFIER ::= { traps 0 }
board                        OBJECT IDENTIFIER ::= { pdu2 1 }
environmental                OBJECT IDENTIFIER ::= { pdu2 2 }
configuration                OBJECT IDENTIFIER ::= { pdu2 3 }
control                      OBJECT IDENTIFIER ::= { pdu2 4 }
measurements                 OBJECT IDENTIFIER ::= { pdu2 5 }
log                          OBJECT IDENTIFIER ::= { pdu2 6 }
conformance                  OBJECT IDENTIFIER ::= { pdu2 9 }
reliability                  OBJECT IDENTIFIER ::= { pdu2 10 }

unit                         OBJECT IDENTIFIER ::= { configuration 2 }
inlets                       OBJECT IDENTIFIER ::= { configuration 3 }
overCurrentProtector         OBJECT IDENTIFIER ::= { configuration 4 }
outlets                      OBJECT IDENTIFIER ::= { configuration 5 }
externalSensors              OBJECT IDENTIFIER ::= { configuration 6 }
serverReachability           OBJECT IDENTIFIER ::= { configuration 7 }
wires                        OBJECT IDENTIFIER ::= { configuration 8 }
transferSwitch               OBJECT IDENTIFIER ::= { configuration 9 }



outletControl                OBJECT IDENTIFIER ::= { control 1 }
externalSensorControl        OBJECT IDENTIFIER ::= { control 2 }
transferSwitchControl        OBJECT IDENTIFIER ::= { control 3 }
actuatorControl              OBJECT IDENTIFIER ::= { control 4 }
rcmControl                   OBJECT IDENTIFIER ::= { control 5 }
inletSensorControl           OBJECT IDENTIFIER ::= { control 6 }
outletSensorControl          OBJECT IDENTIFIER ::= { control 7 }
unitSensorControl            OBJECT IDENTIFIER ::= { control 8 }


measurementsUnit                  OBJECT IDENTIFIER ::= { measurements 1 }
measurementsInlet                 OBJECT IDENTIFIER ::= { measurements 2 }
measurementsOverCurrentProtector  OBJECT IDENTIFIER ::= { measurements 3 }
measurementsOutlet                OBJECT IDENTIFIER ::= { measurements 4 }
measurementsExternalSensor        OBJECT IDENTIFIER ::= { measurements 5 }
measurementsWire                  OBJECT IDENTIFIER ::= { measurements 6 }
measurementsTransferSwitch        OBJECT IDENTIFIER ::= { measurements 7 }

logUnit                  OBJECT IDENTIFIER ::= { log 1 }
logInlet                 OBJECT IDENTIFIER ::= { log 2 }
logOverCurrentProtector  OBJECT IDENTIFIER ::= { log 3 }
logOutlet                OBJECT IDENTIFIER ::= { log 4 }
logExternalSensor        OBJECT IDENTIFIER ::= { log 5 }
logWire                  OBJECT IDENTIFIER ::= { log 6 }
logTransferSwitch        OBJECT IDENTIFIER ::= { log 7 }

reliabilityData                           OBJECT IDENTIFIER ::= { reliability 1 }
reliabilityErrorLog                       OBJECT IDENTIFIER ::= { reliability 2 }








compliances     OBJECT IDENTIFIER ::= { conformance 1 }
groups          OBJECT IDENTIFIER ::= { conformance 2 }

-- Conformance Information
-- compliance statements

complianceRev2      MODULE-COMPLIANCE
                STATUS current
                DESCRIPTION
                    "The requirements for conformance to the PDU2-MIB."
                MODULE -- this module

                GROUP configGroup
                DESCRIPTION
                    "The configuration group."

                GROUP logGroup
                DESCRIPTION
                    "The log group."

                GROUP measurementsGroup
                DESCRIPTION
                    "The measurements group."

                GROUP controlGroup
                DESCRIPTION
                    "The control group."

                GROUP trapInformationGroup
                DESCRIPTION
                    "The information group."

                GROUP trapsGroup
                DESCRIPTION
                    "The information group."

                GROUP reliabilityGroup
                DESCRIPTION
                    "The reliability group."

                ::= { compliances 2 }

complianceRev1      MODULE-COMPLIANCE
                STATUS deprecated
                DESCRIPTION
                    "The requirements for conformance to the PDU2-MIB."
                MODULE -- this module

                GROUP ipAddressGroup
                DESCRIPTION
                    "The ipAddress group."

                GROUP oldConfigGroup
                DESCRIPTION
                    "old (deprecated) configuration data"

                GROUP oldLogGroup
                DESCRIPTION
                    "old (deprecated) logging data"

                GROUP oldMeasurementsGroup
                DESCRIPTION
                    "old (deprecated) measurement data"

                GROUP oldTrapsGroup
                DESCRIPTION
                    "old (deprecated) traps"

                ::= { compliances 1 }




-- units of conformance

configGroup       OBJECT-GROUP
                OBJECTS { pduCount,
                          pduManufacturer,             
                          pduModel,                   
                          pduSerialNumber,            
                          pduRatedVoltage,           
                          pduRatedCurrent,            
                          pduRatedFrequency,         
                          pduRatedVA,
                          pduImage, 
                          inletCount,
                          transferSwitchCount,
                          productType,
                          overCurrentProtectorCount,
                          outletCount,                
                          inletControllerCount,       
                          outletControllerCount, 
                          meteringControllerCount,      
                          externalSensorCount,                              
                          pxMACAddress,                 
                          utcOffset,
                          pduName,                      
                          boardVersion,                      
                          boardFirmwareVersion,                           
                          boardFirmwareTimeStamp,  
                          unitSensorLogAvailable,
                          unitSensorUnits,
                          unitSensorDecimalDigits,
                          unitSensorResolution,
                          unitSensorMaximum,
                          unitSensorMinimum,                
                          unitSensorHysteresis,                
                          unitSensorStateChangeDelay,                
                          unitSensorLowerCriticalThreshold,    
                          unitSensorLowerWarningThreshold,     
                          unitSensorUpperCriticalThreshold,    
                          unitSensorUpperWarningThreshold,
                          unitSensorEnabledThresholds, 
                          unitSensorSignedMaximum,
                          unitSensorSignedMinimum,
                          unitSensorSignedLowerCriticalThreshold,
                          unitSensorSignedLowerWarningThreshold,
                          unitSensorSignedUpperCriticalThreshold,
                          unitSensorSignedUpperWarningThreshold,
                          inletLabel,                
                          inletName,                  
                          inletPlug,           
                          inletPoleCount,             
                          inletRatedVoltage,          
                          inletRatedCurrent,
                          inletRatedFrequency,
                          inletRatedVA,
                          inletDeviceCapabilities,
                          inletPoleCapabilities, 
                          inletPlugDescriptor,
                          inletEnableState,
                          inletSensorLogAvailable, 
                          inletSensorUnits,
                          inletSensorDecimalDigits,
                          inletSensorResolution,
                          inletSensorMaximum,
                          inletSensorMinimum,               
                          inletSensorHysteresis,                
                          inletSensorStateChangeDelay,                
                          inletSensorLowerCriticalThreshold,    
                          inletSensorLowerWarningThreshold,     
                          inletSensorUpperCriticalThreshold,    
                          inletSensorUpperWarningThreshold, 
                          inletSensorEnabledThresholds,  
                          inletSensorSignedMaximum,
                          inletSensorSignedMinimum,
                          inletSensorSignedLowerCriticalThreshold,
                          inletSensorSignedLowerWarningThreshold,
                          inletSensorSignedUpperCriticalThreshold,
                          inletSensorSignedUpperWarningThreshold,
                          inletPoleSensorLogAvailable,
                          inletPoleSensorUnits,
                          inletPoleSensorDecimalDigits,
                          inletPoleSensorResolution,
                          inletPoleSensorMaximum,
                          inletPoleSensorMinimum,                
                          inletPoleSensorHysteresis,                
                          inletPoleSensorStateChangeDelay,                
                          inletPoleSensorLowerCriticalThreshold,    
                          inletPoleSensorLowerWarningThreshold,     
                          inletPoleSensorUpperCriticalThreshold,    
                          inletPoleSensorUpperWarningThreshold,
                          inletPoleSensorEnabledThresholds,
                          inletPoleSensorSignedMaximum,
                          inletPoleSensorSignedMinimum,
                          inletPoleSensorSignedLowerCriticalThreshold,
                          inletPoleSensorSignedLowerWarningThreshold,
                          inletPoleSensorSignedUpperCriticalThreshold,
                          inletPoleSensorSignedUpperWarningThreshold,
                          inletRCMResidualOperatingCurrent,
                          overCurrentProtectorLabel,                 
                          overCurrentProtectorName,                  
                          overCurrentProtectorType,               
                          overCurrentProtectorRatedCurrent,
                          overCurrentProtectorCapabilities,                   
                          overCurrentProtectorSensorLogAvailable,
                          overCurrentProtectorSensorUnits,
                          overCurrentProtectorSensorDecimalDigits,
                          overCurrentProtectorSensorResolution,
                          overCurrentProtectorSensorMaximum,
                          overCurrentProtectorSensorMinimum,                
                          overCurrentProtectorSensorHysteresis,                
                          overCurrentProtectorSensorStateChangeDelay,                
                          overCurrentProtectorSensorLowerCriticalThreshold,    
                          overCurrentProtectorSensorLowerWarningThreshold,     
                          overCurrentProtectorSensorUpperCriticalThreshold,    
                          overCurrentProtectorSensorUpperWarningThreshold,
                          overCurrentProtectorSensorEnabledThresholds,
                          overCurrentProtectorSensorSignedMaximum,
                          overCurrentProtectorSensorSignedMinimum,
                          overCurrentProtectorSensorSignedLowerCriticalThreshold,
                          overCurrentProtectorSensorSignedLowerWarningThreshold,
                          overCurrentProtectorSensorSignedUpperCriticalThreshold,
                          overCurrentProtectorSensorSignedUpperWarningThreshold,
                          overCurrentProtectorPowerSource,
                          outletLabel,                
                          outletName,            
                          outletReceptacle,           
                          outletPoleCount,             
                          outletRatedVoltage,          
                          outletRatedCurrent,          
                          outletRatedVA,
                          outletDeviceCapabilities,
                          outletPoleCapabilities,
                          outletPowerCyclingPowerOffPeriod,
                          outletStateOnStartup,
                          outletUseGlobalPowerCyclingPowerOffPeriod,   
                          outletSwitchable,
                          outletReceptacleDescriptor, 
                          outletNonCritical,
                          outletSequenceDelay,          
                          outletSensorLogAvailable,
                          outletSensorUnits,
                          outletSensorDecimalDigits,
                          outletSensorResolution,
                          outletSensorMaximum,
                          outletSensorMinimum,                
                          outletSensorHysteresis,                
                          outletSensorStateChangeDelay,                
                          outletSensorLowerCriticalThreshold,    
                          outletSensorLowerWarningThreshold,     
                          outletSensorUpperCriticalThreshold,    
                          outletSensorUpperWarningThreshold,
                          outletSensorEnabledThresholds,
                          outletSensorSignedMaximum,
                          outletSensorSignedMinimum,
                          outletSensorSignedLowerCriticalThreshold,
                          outletSensorSignedLowerWarningThreshold,
                          outletSensorSignedUpperCriticalThreshold,
                          outletSensorSignedUpperWarningThreshold,
                          outletPoleSensorLogAvailable,
                          outletPoleSensorUnits,
                          outletPoleSensorDecimalDigits,
                          outletPoleSensorResolution,
                          outletPoleSensorMaximum,
                          outletPoleSensorMinimum,                
                          outletPoleSensorHysteresis,                
                          outletPoleSensorStateChangeDelay,                
                          outletPoleSensorLowerCriticalThreshold,    
                          outletPoleSensorLowerWarningThreshold,     
                          outletPoleSensorUpperCriticalThreshold,    
                          outletPoleSensorUpperWarningThreshold,
                          outletPoleSensorEnabledThresholds,
                          outletPoleSensorSignedMaximum,
                          outletPoleSensorSignedMinimum,
                          outletPoleSensorSignedLowerCriticalThreshold,
                          outletPoleSensorSignedLowerWarningThreshold,
                          outletPoleSensorSignedUpperCriticalThreshold,
                          outletPoleSensorSignedUpperWarningThreshold,
                          outletPowerSource,
                          externalSensorType,                     
                          externalSensorSerialNumber,              
                          externalSensorName,             
                          externalSensorDescription,               
                          externalSensorXCoordinate,               
                          externalSensorYCoordinate,               
                          externalSensorZCoordinate, 
                          externalSensorChannelNumber, 
                          externalOnOffSensorSubtype,            
                          externalSensorLogAvailable,
                          externalSensorUnits,
                          externalSensorDecimalDigits,
                          externalSensorResolution,
                          externalSensorMaximum,
                          externalSensorMinimum,                
                          externalSensorHysteresis,                
                          externalSensorStateChangeDelay,                
                          externalSensorLowerCriticalThreshold,    
                          externalSensorLowerWarningThreshold,     
                          externalSensorUpperCriticalThreshold,    
                          externalSensorUpperWarningThreshold,
                          externalSensorEnabledThresholds, 
                          externalSensorsZCoordinateUnits,
                          externalSensorIsActuator,
                          externalSensorPosition,
                          externalSensorUseDefaultThresholds,
                          externalSensorTypeDefaultHysteresis,
                          externalSensorTypeDefaultStateChangeDelay,
                          externalSensorTypeDefaultLowerCriticalThreshold,
                          externalSensorTypeDefaultLowerWarningThreshold,
                          externalSensorTypeDefaultUpperCriticalThreshold,
                          externalSensorTypeDefaultUpperWarningThreshold,
                          externalSensorTypeDefaultEnabledThresholds,
                          measurementPeriod,                 
                          measurementsPerLogEntry,           
                          logSize,
                          unitDeviceCapabilities,
                          globalOutletPowerCyclingPowerOffPeriod,
                          globalOutletStateOnStartup,
			  relayBehaviorOnPowerLoss,
                          pduPowerCyclingPowerOffPeriod,
                          pduDaisychainMemberType,
                          managedExternalSensorCount,
                          outletPowerupSequence, 
                          loadShedding,
                          serverCount,
                          serverIPAddress,
                          serverPingEnabled,
                          inrushGuardDelay,
                          cascadedDeviceConnected,
                          synchronizeWithNTPServer,
                          useDHCPProvidedNTPServer,
                          firstNTPServerAddressType,
                          firstNTPServerAddress,
                          secondNTPServerAddressType,
                          secondNTPServerAddress,
                          transferSwitchLabel,                                   
                          transferSwitchName,                                   
                          transferSwitchPreferredInlet,                          
                          transferSwitchAutoReTransferEnabled,                 
                          transferSwitchAutoReTransferWaitTime,                  
                          transferSwitchAutoReTransferRequiresPhaseSync,
                          transferSwitchFrontPanelManualTransferButtonEnabled,
                          transferSwitchCapabilities,
                          transferSwitchSensorLogAvailable,
                          transferSwitchSensorUnits,
                          transferSwitchSensorDecimalDigits,
                          transferSwitchSensorResolution,
                          transferSwitchSensorMaximum,
                          transferSwitchSensorMinimum,
                          transferSwitchSensorHysteresis,
                          transferSwitchSensorStateChangeDelay,
                          transferSwitchSensorLowerCriticalThreshold,
                          transferSwitchSensorLowerWarningThreshold,
                          transferSwitchSensorUpperCriticalThreshold,
                          transferSwitchSensorUpperWarningThreshold,
                          transferSwitchSensorEnabledThresholds,
                          transferSwitchSensorSignedMaximum,
                          transferSwitchSensorSignedMinimum,
                          transferSwitchSensorSignedLowerCriticalThreshold,
                          transferSwitchSensorSignedLowerWarningThreshold,
                          transferSwitchSensorSignedUpperCriticalThreshold,
                          transferSwitchSensorSignedUpperWarningThreshold,
                          transferSwitchPowerSource1,
                          transferSwitchPowerSource2,
                          peripheralDevicePackageSerialNumber,
                          peripheralDevicePackageModel,
                          peripheralDevicePackageFirmwareVersion,
                          peripheralDevicePackageMinFirmwareVersion,
                          peripheralDevicePackageFirmwareTimeStamp,
                          peripheralDevicePackagePosition,
                          peripheralDevicePackageState,
                          deviceCascadeType,
                          deviceCascadePosition,
                          peripheralDevicesAutoManagement,
                          externalSensorAlarmedToNormalDelay,
                          frontPanelOutletSwitching,
                          frontPanelRCMSelfTest,
                          frontPanelActuatorControl
                         }
                STATUS  current
                DESCRIPTION
                    "A collection of objects representing configuration data."
                ::= { groups 1 }

ipAddressGroup       OBJECT-GROUP
                OBJECTS {      
                          pxIPAddress,                  
                          netmask,                    
                          gateway,
                          pxInetAddressType, 
                          pxInetIPAddress,                  
                          pxInetNetmask,                    
                          pxInetGateway    
                         }
                STATUS  deprecated
                DESCRIPTION
                    "A collection of objects representing configuration data."
                ::= { groups 12 }


oldConfigGroup       OBJECT-GROUP
                OBJECTS {      
                          outletSequencingDelay,
                          unitSensorAccuracy,
                          unitSensorTolerance,
                          inletSensorAccuracy,
                          inletSensorTolerance,
                          inletPoleSensorAccuracy,
                          inletPoleSensorTolerance,
                          outletSensorAccuracy,
                          outletSensorTolerance,
                          outletPoleSensorAccuracy,
                          outletPoleSensorTolerance,
                          overCurrentProtectorSensorAccuracy,
                          overCurrentProtectorSensorTolerance,
                          externalSensorAccuracy,
                          externalSensorTolerance,
                          wireSensorAccuracy,
                          wireSensorTolerance,
                          transferSwitchSensorAccuracy,
                          transferSwitchSensorTolerance,
                          wireCount,
                          wireLabel,
                          wireCapabilities,
                          wireSensorLogAvailable,
                          wireSensorUnits,
                          wireSensorDecimalDigits,
                          wireSensorResolution,
                          wireSensorMaximum,
                          wireSensorMinimum,
                          wireSensorHysteresis,
                          wireSensorStateChangeDelay,
                          wireSensorLowerCriticalThreshold,
                          wireSensorLowerWarningThreshold,
                          wireSensorUpperCriticalThreshold,
                          wireSensorUpperWarningThreshold,
                          wireSensorEnabledThresholds,
                          wirePowerSource
                         }
                STATUS  deprecated
                DESCRIPTION
                    "A collection of objects representing old (deprecated) configuration data."
                ::= { groups 13 }


logGroup       OBJECT-GROUP
                OBJECTS {                 
                          dataLogging,       
                          oldestLogID,
                          newestLogID,             
                          logTimeStamp,
                          dataLoggingEnableForAllSensors,
                          logUnitSensorDataAvailable,
                          logUnitSensorState,            
                          logUnitSensorAvgValue,
                          logUnitSensorMaxValue,
                          logUnitSensorMinValue,
                          logUnitSensorSignedAvgValue,
                          logUnitSensorSignedMaxValue,
                          logUnitSensorSignedMinValue,
                          logInletSensorDataAvailable,
                          logInletSensorState,           
                          logInletSensorAvgValue,        
                          logInletSensorMaxValue,        
                          logInletSensorMinValue,
                          logInletSensorSignedAvgValue,
                          logInletSensorSignedMaxValue,
                          logInletSensorSignedMinValue,
                          logInletPoleSensorDataAvailable, 
                          logInletPoleSensorState,           
                          logInletPoleSensorAvgValue,        
                          logInletPoleSensorMaxValue,        
                          logInletPoleSensorMinValue,
                          logInletPoleSensorSignedAvgValue,
                          logInletPoleSensorSignedMaxValue,
                          logInletPoleSensorSignedMinValue,
                          logOutletSensorDataAvailable,
                          logOutletSensorState,           
                          logOutletSensorAvgValue,        
                          logOutletSensorMaxValue,        
                          logOutletSensorMinValue,
                          logOutletSensorSignedAvgValue,
                          logOutletSensorSignedMaxValue,
                          logOutletSensorSignedMinValue,
                          logOutletPoleSensorDataAvailable,
                          logOutletPoleSensorState,           
                          logOutletPoleSensorAvgValue,        
                          logOutletPoleSensorMaxValue,        
                          logOutletPoleSensorMinValue,
                          logOutletPoleSensorSignedAvgValue,
                          logOutletPoleSensorSignedMaxValue,
                          logOutletPoleSensorSignedMinValue,
                          logOverCurrentProtectorSensorDataAvailable,
                          logOverCurrentProtectorSensorState,           
                          logOverCurrentProtectorSensorAvgValue,        
                          logOverCurrentProtectorSensorMaxValue,        
                          logOverCurrentProtectorSensorMinValue,
                          logOverCurrentProtectorSensorSignedAvgValue,
                          logOverCurrentProtectorSensorSignedMaxValue,
                          logOverCurrentProtectorSensorSignedMinValue,
                          logExternalSensorDataAvailable, 
                          logExternalSensorState,           
                          logExternalSensorAvgValue,        
                          logExternalSensorMaxValue,        
                          logExternalSensorMinValue,
                          logTransferSwitchSensorDataAvailable,
                          logTransferSwitchSensorState,
                          logTransferSwitchSensorAvgValue,
                          logTransferSwitchSensorMaxValue,
                          logTransferSwitchSensorMinValue,
                          logTransferSwitchSensorSignedAvgValue,
                          logTransferSwitchSensorSignedMaxValue,
                          logTransferSwitchSensorSignedMinValue
                         }
                STATUS  current
                DESCRIPTION
                    "A collection of objects providing logging (history of readings) capabilities 
                     about the PDU."
                ::= { groups 2 }


oldLogGroup       OBJECT-GROUP
                OBJECTS {
                          logWireSensorDataAvailable,
                          logWireSensorState,
                          logWireSensorAvgValue,
                          logWireSensorMaxValue,
                          logWireSensorMinValue
                         }
                STATUS  deprecated
                DESCRIPTION
                    "A collection of objects representing old (deprecated) logging data."
                ::= { groups 14 }

measurementsGroup       OBJECT-GROUP
                OBJECTS { 
                          measurementsUnitSensorIsAvailable,
                          measurementsUnitSensorState,            
                          measurementsUnitSensorValue,         
                          measurementsUnitSensorTimeStamp,
                          measurementsUnitSensorSignedValue,
                          measurementsInletSensorIsAvailable,         
                          measurementsInletSensorState,            
                          measurementsInletSensorValue,         
                          measurementsInletSensorTimeStamp,
                          measurementsInletSensorSignedValue,
                          measurementsInletPoleSensorIsAvailable,         
                          measurementsInletPoleSensorState,            
                          measurementsInletPoleSensorValue,         
                          measurementsInletPoleSensorTimeStamp,
                          measurementsInletPoleSensorSignedValue,
                          measurementsOutletSensorIsAvailable,         
                          measurementsOutletSensorState,            
                          measurementsOutletSensorValue,         
                          measurementsOutletSensorTimeStamp,
                          measurementsOutletSensorSignedValue,
                          measurementsOutletPoleSensorIsAvailable,         
                          measurementsOutletPoleSensorState,            
                          measurementsOutletPoleSensorValue,         
                          measurementsOutletPoleSensorTimeStamp,
                          measurementsOutletPoleSensorSignedValue,
                          measurementsOverCurrentProtectorSensorIsAvailable,      
                          measurementsOverCurrentProtectorSensorState,            
                          measurementsOverCurrentProtectorSensorValue,         
                          measurementsOverCurrentProtectorSensorTimeStamp,
                          measurementsOverCurrentProtectorSensorSignedValue,
                          measurementsExternalSensorIsAvailable,         
                          measurementsExternalSensorState,            
                          measurementsExternalSensorValue,         
                          measurementsExternalSensorTimeStamp,
                          measurementsTransferSwitchSensorIsAvailable,
                          measurementsTransferSwitchSensorState,
                          measurementsTransferSwitchSensorValue,
                          measurementsTransferSwitchSensorTimeStamp,
                          measurementsTransferSwitchSensorSignedValue
                         }
                STATUS  current
                DESCRIPTION
                    "A collection of objects providing measurements (most recent data) capabilities.
                     about the PDU."
                ::= { groups 3 }


oldMeasurementsGroup       OBJECT-GROUP
                OBJECTS {
                          measurementsWireSensorIsAvailable,
                          measurementsWireSensorState,
                          measurementsWireSensorValue,
                          measurementsWireSensorTimeStamp
                         }
                STATUS  deprecated
                DESCRIPTION
                    "A collection of objects representing old (deprecated) measurement data."
                ::= { groups 15 }

controlGroup       OBJECT-GROUP
                OBJECTS {       
                          switchingOperation,
                          outletSwitchingState,
                          outletSwitchingTimeStamp,
                          transferSwitchActiveInlet,
                          transferSwitchTransferToInlet,
                          transferSwitchAlarmOverride,
                          transferSwitchLastTransferReason,
                          actuatorState,
                          rcmState,
                          inletSensorResetValue,
                          outletSensorResetValue,
                          unitSensorResetValue
                         }
                STATUS  current
                DESCRIPTION
                    "A collection of objects providing the ability to control various components
                     of a PDU."
                ::= { groups 4 }


trapInformationGroup  OBJECT-GROUP
                OBJECTS {       
                          userName,
                          targetUser,
                          imageVersion,
                          roleName,
                          oldSensorState,                          
                          pduNumber,
                          inletPoleNumber,
                          outletPoleNumber,
                          externalSensorNumber,
                          typeOfSensor,
                          smtpMessageRecipients,
                          smtpServer,
                          errorDescription,
                          deviceChangedParameter,
                          changedParameterNewValue,
			  lhxSupportEnabled,
                          webcamModel,
                          webcamConnectionPort,
                          agentInetPortNumber,
			  peripheralDeviceRomcode,
			  peripheralDeviceFirmwareUpdateState
                         }
                STATUS  current
                DESCRIPTION
                    "A collection of objects providing information in the traps."
                ::= { groups 5 }


trapsGroup      NOTIFICATION-GROUP
                NOTIFICATIONS { systemStarted,
                                systemReset,
                                userLogin,
                                userLogout,
                                userAuthenticationFailure,
                                userSessionTimeout,
                                userAdded,
                                userModified,
                                userDeleted,
                                roleAdded,
                                roleModified,
                                roleDeleted,
                                deviceUpdateStarted,
                                deviceUpdateCompleted,
                                userBlocked,
                                powerControl,
                                userPasswordChanged,
                                passwordSettingsChanged,
                                firmwareValidationFailed,
                                logFileCleared, 
                                bulkConfigurationSaved,
                                bulkConfigurationCopied,
                                inletSensorStateChange,
                                inletPoleSensorStateChange,
                                outletSensorStateChange,
                                outletPoleSensorStateChange,
                                overCurrentProtectorSensorStateChange,
                                externalSensorStateChange,
                                smtpMessageTransmissionFailure,
                                ldapError,
                                deviceUpdateFailed,
                                loadSheddingModeEntered,
                                loadSheddingModeExited,
                                pingServerEnabled, 
                                pingServerDisabled,
                                serverNotReachable, 
                                serverReachable,
                                rfCodeTagConnected,
                                rfCodeTagDisconnected,
                                deviceIdentificationChanged,
                                usbSlaveConnected,
                                usbSlaveDisconnected,
				lhxSupportChanged,
				userAcceptedRestrictedServiceAgreement,
				userDeclinedRestrictedServiceAgreement,
                                transferSwitchSensorStateChange,
                                deviceSettingsSaved,
                                deviceSettingsRestored,
                                webcamInserted,
                                webcamRemoved,
                                inletEnabled,
                                inletDisabled,
                                serverConnectivityUnrecoverable,
                                radiusError,
                                serverReachabilityError,
                                inletSensorReset,
                                outletSensorReset,
                                unitSensorReset,
                                unknownPeripheralDeviceAttached,
				peripheralDeviceFirmwareUpdate,
                                unitSensorStateChange
                               }
                STATUS  current
                DESCRIPTION
                    "A collection of traps."
                ::= { groups 9 }

oldTrapsGroup      NOTIFICATION-GROUP
                NOTIFICATIONS { wireSensorStateChange,
                                pduSensorStateChange
                         }
                STATUS  deprecated
                DESCRIPTION
                    "A collection of objects representing old (deprecated) traps."
                ::= { groups 16 }

reliabilityGroup  OBJECT-GROUP
                OBJECTS {
                         reliabilityId,
                         reliabilityDataValue,
                         reliabilityDataMaxPossible,
                         reliabilityDataWorstValue,
                         reliabilityDataThreshold,
                         reliabilityDataRawUpperBytes,
                         reliabilityDataRawLowerBytes,
                         reliabilityDataFlags,
                         reliabilityErrorLogId,
                         reliabilityErrorLogValue,
                         reliabilityErrorLogThreshold,
                         reliabilityErrorLogRawUpperBytes,
                         reliabilityErrorLogRawLowerBytes,
                         reliabilityErrorLogPOH,
                         reliabilityErrorLogTime,
                         reliabilityDataTableSequenceNumber       
                         
                         }
                STATUS  current
                DESCRIPTION
                    "A collection of objects providing reliability data."
                ::= { groups 10 }

-- Textual Conventions



SensorTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The types a sensor can be."
                          SYNTAX        INTEGER { 
                                                  rmsCurrent(1),
                                                  peakCurrent(2),
                                                  unbalancedCurrent(3),
                                                  rmsVoltage(4),
                                                  activePower(5),
                                                  apparentPower(6),
                                                  powerFactor(7),
                                                  activeEnergy(8),
                                                  apparentEnergy(9),
                                                  temperature(10),
                                                  humidity(11),
                                                  airFlow(12),
                                                  airPressure(13),
                                                  onOff(14),
                                                  trip(15),
                                                  vibration(16),
                                                  waterDetection(17),
                                                  smokeDetection(18),
                                                  binary(19),
                                                  contact(20),
                                                  fanSpeed(21),
                                                  surgeProtectorStatus(22),
                                                  frequency(23),
                                                  phaseAngle(24),
						  rmsVoltageLN(25),
                                                  residualCurrent(26),
                                                  rcmState(27),
                                                  other(30),
                                                  none(31),
                                                  powerQuality(32),
                                                  overloadStatus(33),
                                                  overheatStatus(34),
                                                  fanStatus(37),
                                                  inletPhaseSyncAngle(38),
                                                  inletPhaseSync(39),
                                                  operatingState(40),
                                                  activeInlet(41),
						  illuminance(42),
						  doorContact(43),
						  tamperDetection(44),
						  motionDetection(45),
                                                  i1smpsStatus(46),  
                                                  i2smpsStatus(47),  
                                                  switchStatus(48)
                                                   }



SensorStateEnumeration ::= TEXTUAL-CONVENTION
                           STATUS  current
                           DESCRIPTION
                               "The states a sensor can be in."
                           SYNTAX        INTEGER { unavailable(-1),
                                                   open(0),
                                                   closed(1),
                                                   belowLowerCritical(2),
                                                   belowLowerWarning(3),
                                                   normal(4),
                                                   aboveUpperWarning(5),
                                                   aboveUpperCritical(6),
                                                   on(7),
                                                   off(8),
                                                   detected(9),
                                                   notDetected(10),
                                                   alarmed(11),
                                                   ok(12),
                                                   fail(14),
                                                   yes(15),
                                                   no(16),
                                                   standby(17),
                                                   one(18),
                                                   two(19),
                                                   inSync(20),
                                                   outOfSync(21),
                                                   i1OpenFault(22),
                                                   i1ShortFault(23),
                                                   i2OpenFault(24),
                                                   i2ShortFault(25),
                                                   fault(26),
                                                   warning(27),
                                                   critical(28),
                                                   selfTest(29)
                                                 }

--                    Possible  Sensor States for each  Sensor Type
--                    This comment must be updated whenever a new sensor type is added.
--                    Sensor Type                  Sensor States
--                      rmsCurrent                 unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      peakCurrent                unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      unbalancedCurrent          unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      rmsVoltage                 unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      activePower                unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      apparentPower              unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      powerFactor                unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      activeEnergy               unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      apparentEnergy             unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      temperature                unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      humidity                   unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      airFlow                    unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      airPressure                unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      onOff                      unavailable,on,off
--                      trip                       unavailable,open,closed
--                      vibration                  unavailable,normal,alarmed
--                      waterDetection             unavailable,normal,alarmed
--                      smokeDetection             unavailable,normal,alarmed
--                      binary                     unavailable,normal,alarmed
--                      contact                    unavailable,normal,alarmed
--                      fanSpeed                   unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      surgeProtectorStatus       unavailable,ok,fault
--                      frequency                  unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      phaseAngle                 unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      powerQuality               unavailable,normal,warning,critical
--                      overloadStatus             unavailable,ok,fault
--                      overheatStatus             unavailable,ok,fault
--                      fanStatus                  unavailable,ok,fault
--                      residualCurrent            unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      rcmState                   unavailable,normal,alarmed,selfTest,fail
--                      inletPhaseSyncAngle        unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      inletPhaseSync             unavailable,inSync,outOfSync
--                      operatingState             unavailable,normal,standby,off
--                      activeInlet                unavailable,one,two,none
--                      illuminance                unavailable,belowLowerCritical,belowLowerWarning,normal,aboveUpperWarning,aboveUpperCritical
--                      doorContact                unavailable,open,closed
--                      tamperDetection            unavailable,normal,alarmed
--                      motionDetection            unavailable,??
--                      i1smpsStatus               unavailable,ok,fault
--                      i2smpsStatus               unavailable,ok,fault
--                      switchStatus               unavailable,ok,i1OpenFault,i1ShortFault,i2OpenFault,i2ShortFault




PlugTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The types of inlet plug."
                          SYNTAX        INTEGER { plugOTHER(-1),
                                                  plugNONE(0),
                                                  plug56P320(1), 
                                                  plug56P520(2), 
                                                  plug56P532(3), 
                                                  plugCS8365C(4), 
					          plugIEC320C14(5), 
						  plugIEC320C20(6), 
						  plugIEC603093WIRE250V16A(7), 
						  plugIEC603093WIRE250V20A(8), 
						  plugIEC603093WIRE250V30A(9), 
						  plugIEC603093WIRE250V32A(10), 
						  plugIEC603093WIRE250V60A(11), 
						  plugIEC603093WIRE250V63A(12), 
						  plugIEC603093WIRE250V100A(13), 
						  plugIEC603093WIRE250V125A(14), 
						  plugIEC603094WIRE250V20A(15), 
						  plugIEC603094WIRE250V30A(16), 
						  plugIEC603094WIRE250V60A(17), 
						  plugIEC603094WIRE250V100A(18), 
						  plugIEC603095WIRE208V20A(23), 
						  plugIEC603095WIRE208V30A(24), 
						  plugIEC603095WIRE208V60A(25), 
						  plugIEC603095WIRE208V100A(26), 
						  plugIEC603095WIRE415V16A(27), 
						  plugIEC603095WIRE415V32A(28), 
						  plugIEC603095WIRE415V63A(29), 
						  plugIEC603095WIRE415V125A(30), 
						  plugIEC603095WIRE480V20A(31),
                                                  plugIEC603095WIRE480V30A(32),
                                                  plugIEC603095WIRE480V60A(33),
                                                  plugIEC603095WIRE480V100A(34),
						  plugNEMA515P(35), 
						  plugNEMAL515P(36), 
						  plugNEMA520P(37), 
						  plugNEMAL520P(38), 
						  plugNEMAL530P(39), 
						  plugNEMAL615P(40), 
						  plugNEMAL620P(41), 
						  plugNEMAL630P(42), 
						  plugNEMAL1520P(43), 
						  plugNEMAL1530P(44), 
						  plugNEMAL2120P(45), 
						  plugNEMAL2130P(46),
                                                  plugNEMAL2230P(47),
                                                  plug56P320F(48),
                                                  plug56PA320(49)

                                                   }

ReceptacleTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The types of outlet receptacle."
                          SYNTAX        INTEGER { receptacleOTHER(-1),
                                                receptacleNONE(0),
                                                receptacleBS1363(1), 
						receptacle56P532(3), 
						receptacleCS8364C(4), 
						receptacleIEC320C13(5), 
						receptacleIEC320C19(6), 
						receptacleIEC603093WIRE250V16A(7), 
						receptacleIEC603093WIRE250V20A(8), 
						receptacleIEC603093WIRE250V30A(9), 
						receptacleIEC603093WIRE250V32A(10), 
						receptacleIEC603093WIRE250V60A(11), 
						receptacleIEC603093WIRE250V63A(12), 
						receptacleIEC603093WIRE250V100A(13), 
						receptacleIEC603093WIRE250V125A(14), 
						receptacleIEC603094WIRE250V20A(15), 
						receptacleIEC603094WIRE250V30A(16), 
						receptacleIEC603094WIRE250V60A(17), 
						receptacleIEC603094WIRE250V100A(18), 
						receptacleIEC603095WIRE208V20A(23), 
						receptacleIEC603095WIRE208V30A(24), 
						receptacleIEC603095WIRE208V60A(25), 
						receptacleIEC603095WIRE208V100A(26), 
						receptacleIEC603095WIRE415V16A(27), 
						receptacleIEC603095WIRE415V32A(28), 
						receptacleIEC603095WIRE415V63A(29), 
						receptacleIEC603095WIRE415V125A(30), 
						receptacleIEC603095WIRE480V20A(31),
                                                receptacleIEC603095WIRE480V30A(32),
                                                receptacleIEC603095WIRE480V60A(33),
                                                receptacleIEC603095WIRE480V100A(34),
						receptacleNEMA515R(35), 
						receptacleNEMAL515R(36), 
						receptacleNEMA520R(37), 
						receptacleNEMAL520R(38), 
						receptacleNEMAL530R(39), 
						receptacleNEMAL615R(40), 
						receptacleNEMAL620R(41), 
						receptacleNEMAL630R(42), 
						receptacleNEMAL1520R(43), 
						receptacleNEMAL1530R(44), 
						receptacleNEMAL2120RP(45), 
						receptacleNEMAL2130R(46),
                                                receptacleSCHUKOTYPEE(47),
                                                receptacleSCHUKOTYPEF(48)
                                                   }

OverCurrentProtectorTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The types of overcurrent protectors."
                          SYNTAX        INTEGER { ocpBREAKER1POLE(1), 
						ocpBREAKER2POLE(2), 
						ocpBREAKER3POLE(3), 
						ocpFUSE(4),
                                                ocpFUSEPAIR(5),
						ocpRCBO2POLE(6),
						ocpRCBO3POLE(7),
						ocpRCBO4POLE(8)
                                                   }


BoardTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The types of boards."
                          SYNTAX        INTEGER { mainController(1), 
						inletController(2), 
						outletController(3),
						meteringController(4)
                                                   }


OutletSwitchingOperationsEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The switching operations on an outlet."
                          SYNTAX        INTEGER { off(0),
                                                  on(1),                                               
                                                  cycle(2)
                                                   }




SensorUnitsEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The sensor units."
                          SYNTAX        INTEGER { none(-1),
                                                  other(0),
                                                  volt(1),
                                                  amp(2),
                                                  watt(3),
                                                  voltamp(4),
                                                  wattHour(5),
                                                  voltampHour(6),
                                                  degreeC(7),
                                                  hertz(8),
                                                  percent(9),
                                                  meterpersec(10),
                                                  pascal(11),
                                                  psi(12),
                                                  g(13),
                                                  degreeF(14), 
                                                  feet(15),
                                                  inches(16),
                                                  cm(17),
                                                  meters(18),
                                                  rpm(19),
                                                  degrees(20),
						  lux(21)
                                                  }

DaisychainMemberTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The daisy chain member type."
                          SYNTAX        INTEGER { standalone(0),
                                                  master(1),                                               
                                                  slave(2)
                                                   }


URL ::= TEXTUAL-CONVENTION
        DISPLAY-HINT "255a"
        STATUS  current
        DESCRIPTION
             "A Uniform Resource Locator (URL), as defined in RFC1738."
        SYNTAX  OCTET STRING (SIZE (0..255))


GlobalOutletStateOnStartupEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The global outlet state on device start up; can be overridden per outlet."
                          SYNTAX        INTEGER { 
                                                  off(0),
                                                  on(1),
                                                  lastKnownState(2)
                                                   }

OutletStateOnStartupEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The outlet state on device start up; this overrides the global value."
                          SYNTAX        INTEGER { off(0),
                                                  on(1),
                                                  lastKnownState(2),
                                                  globalOutletStateOnStartup(3)
                                                   }


ExternalSensorsZCoordinateUnitsEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The units of the external Sensor Z Coordinate.
                                rackUnits implies that the Z Coordinate for all external sensors 
                                   is in rack Units (U)
                                text implies that the Z Coordinate for all external sensors 
                                   is a text string (label) "
                          SYNTAX        INTEGER { rackUnits(0),
                                                  text(1)
                                                   }



HundredthsOfAPercentage   ::= TEXTUAL-CONVENTION
                   DISPLAY-HINT "d"
                   STATUS      current
                   DESCRIPTION
                       "Data type for reporting values in hundredths of percentage, i.e. 0.01 %."
                   SYNTAX Unsigned32 (0..10000)

DeviceIdentificationParameterEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The configurable parameters."
                          SYNTAX        INTEGER { pduName(0),
                                                  sysContact(1),
                                                  sysName(2),
                                                  sysLocation(3)
						}


TransferSwitchTransferReasonEnumeration ::= TEXTUAL-CONVENTION
                                           STATUS  current
                                           DESCRIPTION
                                             "Transfer Switch Transfer Reason"
                                           SYNTAX        INTEGER { 
                                                  unknown(0),
                                                  startup(1),
                                                  manualTransfer(2),
                                                  automaticReTransfer(3),
                                                  powerFailure(4),
                                                  powerQuality(5),
                                                  overloadAlarm(6),
                                                  overheatAlarm(7),
                                                  internalFailure(8)
						}

ProductTypeEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The product types."
                          SYNTAX        INTEGER { rackPdu(0),
                                                  bcm(1),
                                                  transferSwitch(2)
						}

RelayPowerLossBehaviorEnumeration ::= TEXTUAL-CONVENTION
                                      STATUS  current
                                      DESCRIPTION
                                         "The type of relay behavior on power loss."
                                      SYNTAX        INTEGER {
                                              nonLatching(0),
                                              latching(1)
				      }


DeviceCascadeTypeEnumeration ::= TEXTUAL-CONVENTION
                                      STATUS  current
                                      DESCRIPTION
                                         "The type of configured cascading on this device."
                                      SYNTAX        INTEGER {
                                              bridging(0),
                                              portForwarding(1)
				      }

PeripheralDeviceFirmwareUpdateStateEnumeration ::= TEXTUAL-CONVENTION
                          STATUS  current
                          DESCRIPTION
                              "The state of an peripheral device firmware update."
                          SYNTAX        INTEGER { started(1), 
						  successful(2),
						  failed(3)
						}

-- the Unit group

-- Implementation for managing the PDUs

pduCount     OBJECT-TYPE
                SYNTAX        Integer32
                MAX-ACCESS    read-only
                STATUS        current
                DESCRIPTION
                    "The number of PDUs"
                ::= { configuration 1 }


-- the Nameplate table

-- The Nameplate table contains information on the PDU's nameplate.


nameplateTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF NameplateEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of PDU nameplate entries. The number of
                     entries is given by the value of pduCount."
                ::= { unit 1 }

nameplateEntry     OBJECT-TYPE
                SYNTAX        NameplateEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry providing PDU nameplate information."
                INDEX         { pduId }
                ::= { nameplateTable 1 }

NameplateEntryStruct ::= SEQUENCE { pduId                   Integer32,
                                    pduManufacturer            DisplayString,
                                    pduModel                   DisplayString,
                                    pduSerialNumber            DisplayString,
                                    pduRatedVoltage            DisplayString,
                                    pduRatedCurrent            DisplayString,
                                    pduRatedFrequency          DisplayString,
                                    pduRatedVA                 DisplayString,
                                    pduImage                   URL
                                   
                              }

pduId                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each PDU. Its value
                                           ranges between 1 and the value of pduCount."
                                      ::= { nameplateEntry 1 }

pduManufacturer                    OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU manaufacturer."
                                      ::= { nameplateEntry 2 }

pduModel                           OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU model."
                                      ::= { nameplateEntry 3 }


pduSerialNumber                    OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU serial Number."
                                      ::= { nameplateEntry 4 }


pduRatedVoltage                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU voltage rating."
                                      ::= { nameplateEntry 5 }


pduRatedCurrent                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU current rating."
                                      ::= { nameplateEntry 6 }

pduRatedFrequency                      OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU frequency rating."
                                      ::= { nameplateEntry 7 }


pduRatedVA                             OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The PDU VA (VoltAmps) rating."
                                      ::= { nameplateEntry 8 }


pduImage                             OBJECT-TYPE
                                     SYNTAX      URL
                                     MAX-ACCESS  read-only
                                     STATUS      current
                                     DESCRIPTION
                                       "The URL of the wiring diagram for this PDU."
            
                                     ::= { nameplateEntry 9}



-- the UnitConfiguration table

-- The UnitConfiguration table contains information on the PDU's configuration.


unitConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF UnitConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of PDU configuration entries. The number of
                     entries is given by the value of pduCount."
                ::= { unit 2 }

unitConfigurationEntry     OBJECT-TYPE
                SYNTAX        UnitConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing configuration objects for a particular PDU."
                INDEX         { pduId }
                ::= { unitConfigurationTable 1 }

UnitConfigurationEntryStruct ::= SEQUENCE { 
                                    inletCount                               Integer32,
                                    overCurrentProtectorCount                Integer32,
                                    outletCount                              Integer32,
                                    inletControllerCount                     Integer32,
                                    outletControllerCount                    Integer32,
                                    externalSensorCount                      Integer32,
                                    pxIPAddress                              IpAddress,
                                    netmask                                  IpAddress,
                                    gateway                                  IpAddress,
                                    pxMACAddress                             MacAddress,
                                    utcOffset                                DisplayString,
                                    pduName                                  DisplayString,
                                    externalSensorsZCoordinateUnits          ExternalSensorsZCoordinateUnitsEnumeration,
                                    unitDeviceCapabilities                   BITS,
                                    outletSequencingDelay                    Unsigned32,
                                    globalOutletPowerCyclingPowerOffPeriod   Unsigned32,
                                    globalOutletStateOnStartup               GlobalOutletStateOnStartupEnumeration,
                                    outletPowerupSequence                    DisplayString,
                                    pduPowerCyclingPowerOffPeriod            Unsigned32,
                                    pduDaisychainMemberType                  DaisychainMemberTypeEnumeration,
                                    managedExternalSensorCount               Integer32,
                                    pxInetAddressType                        InetAddressType,
                                    pxInetIPAddress                          InetAddress,
                                    pxInetNetmask                            InetAddress,
                                    pxInetGateway                            InetAddress,
                                    loadShedding                             TruthValue,
                                    serverCount                              Integer32,
                                    inrushGuardDelay                         Unsigned32,
                                    cascadedDeviceConnected                  TruthValue,
                                    synchronizeWithNTPServer                 TruthValue,
                                    useDHCPProvidedNTPServer                 TruthValue,
                                    firstNTPServerAddressType                InetAddressType,
                                    firstNTPServerAddress                    InetAddress,
                                    secondNTPServerAddressType               InetAddressType,
                                    secondNTPServerAddress                   InetAddress,
                                    wireCount                                Integer32,
                                    transferSwitchCount                      Integer32,
                                    productType                              ProductTypeEnumeration,
                                    meteringControllerCount                  Integer32,
                                    relayBehaviorOnPowerLoss                 RelayPowerLossBehaviorEnumeration,
                                    deviceCascadeType                        DeviceCascadeTypeEnumeration,
                                    deviceCascadePosition                    Integer32,
                                    peripheralDevicesAutoManagement          TruthValue,
                                    frontPanelOutletSwitching                TruthValue,
                                    frontPanelRCMSelfTest                    TruthValue,
                                    frontPanelActuatorControl                TruthValue
                              }



inletCount                         OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of inlets."
                                      ::= { unitConfigurationEntry 2 }

overCurrentProtectorCount          OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of overcurrent protectors."
                                      ::= { unitConfigurationEntry 3 }

outletCount                         OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of outlets."
                                      ::= { unitConfigurationEntry 4 }

inletControllerCount                OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of inlet controllers."
                                      ::= { unitConfigurationEntry 5 }


outletControllerCount                OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of outlet controllers."
                                      ::= { unitConfigurationEntry 6 }

externalSensorCount                  OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of external sensors."
                                      ::= { unitConfigurationEntry 7 }


pxIPAddress                           OBJECT-TYPE
                                     SYNTAX        IpAddress
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The current IP address. A value of 0.0.0.0 indicates an error
                                             or an unset option."
                                    ::= { unitConfigurationEntry 8 }

netmask                             OBJECT-TYPE
                                     SYNTAX        IpAddress
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The current netmask. A value of 0.0.0.0 indicates an error
                                             or an unset option."
                                    ::= { unitConfigurationEntry 9 }


gateway                             OBJECT-TYPE
                                     SYNTAX        IpAddress
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The current gateway. A value of 0.0.0.0 indicates an error
                                             or an unset option."
                                    ::= { unitConfigurationEntry 10 }

pxMACAddress                          OBJECT-TYPE
                                     SYNTAX        MacAddress
                                     MAX-ACCESS    read-only
                                     STATUS        current
                                     DESCRIPTION
                                          "The current MAC address."
                                    ::= { unitConfigurationEntry 11 }


utcOffset                          OBJECT-TYPE
                                     SYNTAX        DisplayString
                                     MAX-ACCESS    read-only
                                     STATUS        current
                                     DESCRIPTION
                                          "The current UTC offset."
                                    ::= { unitConfigurationEntry 12 }

pduName                           OBJECT-TYPE
                                   SYNTAX        DisplayString
                                   MAX-ACCESS    read-write
                                   STATUS        current
                                   DESCRIPTION
                                      "The user-defined name for the PDU."
                                   ::= { unitConfigurationEntry 13 }  




                       

externalSensorsZCoordinateUnits OBJECT-TYPE
                                  SYNTAX        ExternalSensorsZCoordinateUnitsEnumeration
                                  MAX-ACCESS    read-write
                                  STATUS        current
                                  DESCRIPTION
                                    "External Sensor Z Coordinate units: Freeform Text or Rack Units (U)
                                       Default is U."
                                 ::= { unitConfigurationEntry 34 }  

unitDeviceCapabilities                 OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  i1smpsStatus(45),  
                                                  i2smpsStatus(46)
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which unit sensors are available."
                                      ::= { unitConfigurationEntry 35 }

outletSequencingDelay                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "It is deprecated. This is an alias for  inrushGuardDelay
                                          "
                                      ::= { unitConfigurationEntry 36 }


globalOutletPowerCyclingPowerOffPeriod          OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The power-off period when an outlet is cycled;
                                           applies to all outlets unless overridden at the outlet level;
                                           specified in seconds; 
                                           0 <= value <= 3600 seconds."
                                      ::= { unitConfigurationEntry 37 }


globalOutletStateOnStartup         OBJECT-TYPE
                                      SYNTAX        GlobalOutletStateOnStartupEnumeration
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The outlet state on device startup; applies to all outlets
                                           unless overridden at the outlet level.
			                   Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching."
                                      ::= { unitConfigurationEntry 38 }

outletPowerupSequence              OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The sequence in which will the outlets will be switched on under the following conditions.
                                            1) Switch all outlets on operation is executed
                                            2) Power to the PDU is cycled
                                           String must consist of a comma separated sequence of the outlet numbers and
                                           all outlet numbers must be included. The numbers entered must be a permutation of the numbers
                                           1,2,3,-outletnumber.
                                           Example for a 12 outlet PDU: 1,12,3,5,6,7,10,2,4,11,9,8.

                                           The per outlet sequence delays are defined as outletSequenceDelay in the outletConfigurationTable
                                          "
                                      ::= { unitConfigurationEntry 39 }


pduPowerCyclingPowerOffPeriod          OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "When power to the  PX is cycled (either manually or because of a
                                           temporary power loss), this number determines how many seconds the
                                           PX will wait before it provides power to the outlets.
                                           specified in seconds:
                                           0 <= value <= 3600 seconds.
			       		   Note that this value is ignored if relayBehaviorOnPowerLoss is set to latching."
                                      ::= { unitConfigurationEntry 40 }


pduDaisychainMemberType            OBJECT-TYPE
                                      SYNTAX        DaisychainMemberTypeEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The daisy chain member type."
                                      ::= { unitConfigurationEntry 41 }


managedExternalSensorCount          OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                        "The number of managed external sensors "
                                      ::= { unitConfigurationEntry 42 }


pxInetAddressType                 OBJECT-TYPE
                                     SYNTAX        InetAddressType
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The type of address format
                                           This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293)."
                                    ::= { unitConfigurationEntry 50 }


pxInetIPAddress                           OBJECT-TYPE
                                     SYNTAX        InetAddress
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The current IP address. A value of 0.0.0.0 indicates an error
                                             or an unset option.
                                           This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
                                           For IPv6, its value is 0.0.0.0 "
                                    ::= { unitConfigurationEntry 51 }

pxInetNetmask                             OBJECT-TYPE
                                     SYNTAX        InetAddress
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The current netmask. A value of 0.0.0.0 indicates an error
                                             or an unset option.
                                           This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
                                           For IPv6, its value is 0.0.0.0 "
                                    ::= { unitConfigurationEntry 52 }


pxInetGateway                             OBJECT-TYPE
                                     SYNTAX        InetAddress
                                     MAX-ACCESS    read-only
                                     STATUS        deprecated
                                     DESCRIPTION
                                          "The current gateway. A value of 0.0.0.0 indicates an error
                                             or an unset option.
                                           This object is deprecated in favor of ipAddressTable from the IP-MIB (rfc4293).
                                           For IPv6, its value is 0.0.0.0 "
                                    ::= { unitConfigurationEntry 53 }

loadShedding                             OBJECT-TYPE
                                     SYNTAX        TruthValue
                                     MAX-ACCESS    read-write
                                     STATUS        current
                                     DESCRIPTION
                                          "Enter/Exit Load Shedding Mode"
                                    ::= { unitConfigurationEntry 55 }


serverCount                     OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of servers"
                                      ::= { unitConfigurationEntry 56 }


inrushGuardDelay                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The time interval between switching on two outlets; 
                                            specified in milliseconds; 
                                           100 <= value <= 100000 milliseconds."
                                      ::= { unitConfigurationEntry 57 }


cascadedDeviceConnected                 OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Indicates whether another PX2 is connected using an USB cable to 
                                           the USB-A port of this PX2 in a cascaded configuration.
                                               true: Connected
                                               false: Not Connected"
                                      ::= { unitConfigurationEntry 58 }



synchronizeWithNTPServer OBJECT-TYPE
                                  SYNTAX          TruthValue
                                  MAX-ACCESS      read-write
                                  STATUS          current
                                  DESCRIPTION
                                      "Will time be obtained using NTP?
                                           true:  time will be obtained using NTP servers
                                           false: time will not be obtained using NTP servers
                                           Deafault is false."
                                  
                                  ::= { unitConfigurationEntry 59 }

useDHCPProvidedNTPServer OBJECT-TYPE
                                  SYNTAX          TruthValue
                                  MAX-ACCESS      read-write
                                  STATUS          current
                                  DESCRIPTION
                                      "Will the NTP server addresses be provided by DHCP/BOOTP?
                                       This is used only if synchronizeWithNTPServer is enabled 
                                       Default is enabled, i.e. DHCP provided NTP servers will be used "
                                  
                                  ::= { unitConfigurationEntry 60 }

firstNTPServerAddressType OBJECT-TYPE
                                  SYNTAX          InetAddressType
                                  MAX-ACCESS      read-write
                                  STATUS          current
                                  DESCRIPTION
                                      "Represents the type of the corresponding instance
                                       of firstNTPServerAddress object."
                                  DEFVAL          { ipv4 } 
                                  ::= { unitConfigurationEntry 61 }

firstNTPServerAddress     OBJECT-TYPE
                                 SYNTAX          InetAddress
                                 MAX-ACCESS      read-write
                                 STATUS          current
                                 DESCRIPTION
                                    "The address of the primary ntp server." 
                                 ::= { unitConfigurationEntry 62 }


secondNTPServerAddressType OBJECT-TYPE
                                  SYNTAX          InetAddressType
                                  MAX-ACCESS      read-write
                                  STATUS          current
                                  DESCRIPTION
                                      "Represents the type of the corresponding instance
                                       of secondNTPServerAddress object.
                                       Default is ipv4"
                                 
                                  ::= { unitConfigurationEntry 63 }

secondNTPServerAddress     OBJECT-TYPE
                                 SYNTAX          InetAddress
                                 MAX-ACCESS      read-write
                                 STATUS          current
                                 DESCRIPTION
                                    "The address of the second ntp server." 
                                 ::= { unitConfigurationEntry 64 }

wireCount                        OBJECT-TYPE
                                 SYNTAX        Integer32(0..255)
                                 MAX-ACCESS    read-only
                                 STATUS        deprecated
                                 DESCRIPTION
                                     "The number of wires."
                                 ::= { unitConfigurationEntry 65 }

transferSwitchCount              OBJECT-TYPE
                                 SYNTAX        Integer32(0..255)
                                 MAX-ACCESS    read-only
                                 STATUS        current
                                 DESCRIPTION
                                     "The number of transfer switches."
                                 ::= { unitConfigurationEntry 66 }


productType                     OBJECT-TYPE
                                SYNTAX      ProductTypeEnumeration
                                MAX-ACCESS  read-only
                                STATUS      current
                                DESCRIPTION
                                   "The product type.
                                     Is this product a PDU, STS, BCM,...?
                                    "
                                     ::= { unitConfigurationEntry 67}


meteringControllerCount        OBJECT-TYPE
                                      SYNTAX        Integer32(0..255)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of metering controllers."
                                      ::= { unitConfigurationEntry 68 }

relayBehaviorOnPowerLoss     OBJECT-TYPE
                             SYNTAX      RelayPowerLossBehaviorEnumeration
                             MAX-ACCESS  read-write
                             STATUS      current
                             DESCRIPTION
                                 "The relay behavior on power loss."
                             ::= { unitConfigurationEntry 69}

deviceCascadeType           OBJECT-TYPE
                             SYNTAX      DeviceCascadeTypeEnumeration
                             MAX-ACCESS  read-write
                             STATUS      current
                             DESCRIPTION
                                 "The configured type of cascading:
                                    default is bridging.
                                  This can be set only if the unit is the master."
                             ::= { unitConfigurationEntry 70}

deviceCascadePosition              OBJECT-TYPE
                                 SYNTAX        Integer32(0..99)
                                 MAX-ACCESS    read-only
                                 STATUS        current
                                 DESCRIPTION
                                     "The position of the device in the cascaded chain.
                                         0: master
                                         >= 1: slaves  "
                                 ::= { unitConfigurationEntry 71 }

peripheralDevicesAutoManagement OBJECT-TYPE
			     SYNTAX	 TruthValue
			     MAX-ACCESS  read-write
                             STATUS      current
                             DESCRIPTION
                                 "Auto-management enabled state for peripheral devices."
                             ::= { unitConfigurationEntry 72}

frontPanelOutletSwitching    OBJECT-TYPE
                             SYNTAX      TruthValue
                             MAX-ACCESS  read-write
                             STATUS      current
                             DESCRIPTION
                                 "Enables/disables switching of outlets using the PDU front panel."
                             ::= { unitConfigurationEntry 73}

frontPanelRCMSelfTest        OBJECT-TYPE
                             SYNTAX      TruthValue
                             MAX-ACCESS  read-write
                             STATUS      current
                             DESCRIPTION
                                 "Enables/disables front panel RCM self-test."
                             ::= { unitConfigurationEntry 74}

frontPanelActuatorControl    OBJECT-TYPE
                             SYNTAX      TruthValue
                             MAX-ACCESS  read-write
                             STATUS      current
                             DESCRIPTION
                                 "Enables/disables front panel peripheral actuator control."
                             ::= { unitConfigurationEntry 75}

-- The ControllerConfiguration table contains information on the controllers in the PDU


controllerConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ControllerConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of entries for the boards in each PDU. The number of
                     entries is given by the value of 
                      inletControllerCount + outletControllerCount + 1 (for main controller board)."
                ::= { unit 3}

controllerConfigurationEntry     OBJECT-TYPE
                SYNTAX        ControllerConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An  entry containing objects for a controller."
                INDEX         { pduId, boardType, boardIndex }
                ::= { controllerConfigurationTable 1 }

ControllerConfigurationEntryStruct ::= SEQUENCE { 
                                    boardType                         BoardTypeEnumeration,
                                    boardIndex                        Integer32,
                                    boardVersion                      DisplayString,
                                    boardFirmwareVersion              DisplayString,
                                    boardFirmwareTimeStamp            Unsigned32
                              }



boardType                       OBJECT-TYPE
                                      SYNTAX        BoardTypeEnumeration
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "The type of board."
                                      ::= { controllerConfigurationEntry 1 }

boardIndex                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each controller. Its value
                                           ranges between 1 and the value of 
                                              inletControllerCount + outletControllerCount + 1."
                                      ::= { controllerConfigurationEntry 2 }

boardVersion                    OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The board hardware version."
                                      ::= { controllerConfigurationEntry 4 }

boardFirmwareVersion           OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The firmware version."
                                      ::= { controllerConfigurationEntry 6 }

boardFirmwareTimeStamp        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The time when the board firmware was updated in UNIX(epoch)time.
                                           It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), 
                                           i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT)."
                                      ::= { controllerConfigurationEntry 8 }



-- The LogConfiguration table contains information on the logs in the PDU.


logConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF LogConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A table of parameters for the data logging feature. The number of
                     entries is given by the value of pduCount."
                ::= { unit 4}

logConfigurationEntry     OBJECT-TYPE
                SYNTAX        LogConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing data logging parameters
                     for a particular PDU."
                INDEX         { pduId }
                ::= { logConfigurationTable 1 }

LogConfigurationEntryStruct ::= SEQUENCE { 
                                    dataLogging                       TruthValue,
                                    measurementPeriod                 Integer32,
                                    measurementsPerLogEntry           Integer32,
                                    logSize                           Integer32,
                                    dataLoggingEnableForAllSensors    TruthValue
                              }


dataLogging                       OBJECT-TYPE
                                   SYNTAX        TruthValue
                                   MAX-ACCESS    read-write
                                   STATUS        current
                                   DESCRIPTION
                                      "Data Retrieval: enabled/disabled."
                                   ::= { logConfigurationEntry 1 }  

measurementPeriod             OBJECT-TYPE
                                  SYNTAX           Integer32
                                  MAX-ACCESS    read-only
                                  STATUS        current
                                  DESCRIPTION
                                    "Data Collection periodicity. This is the periodicity of the data collected by the PX.
                                     This value is fixed at 1 second."
                                 ::= { logConfigurationEntry 2 }


measurementsPerLogEntry       OBJECT-TYPE
                                    SYNTAX        Integer32
                                    MAX-ACCESS    read-write
                                    STATUS        current
                                    DESCRIPTION
                                      "The number of measurements used for each entry in the log."
                                   ::= { logConfigurationEntry 3 } 

logSize                      OBJECT-TYPE
                                  SYNTAX           Integer32
                                  MAX-ACCESS    read-only
                                  STATUS        current
                                  DESCRIPTION
                                    "The number of entries in the log."
                                 ::= { logConfigurationEntry 4 } 


dataLoggingEnableForAllSensors    OBJECT-TYPE
                                    SYNTAX TruthValue
                                    MAX-ACCESS read-write
                                    STATUS current
                                    DESCRIPTION
                                     "Operation to control data logging for all sensors.
                                        If this OID is set to true, then all xxxSensorLogAvailable are set to true
                                        If this OID is set to false, then all xxxSensorLogAvailable are set to false

                                     "
                                 ::= { logConfigurationEntry 5 }



-- the TrapInformation

-- The TrapInformation table defines information sent in the traps.



trapInformationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF TrapInformationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of Trap Information entries. The number of
                     entries is given by the value of pduCount."
                ::= { trapInformation 1 }

trapInformationEntry     OBJECT-TYPE
                SYNTAX        TrapInformationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing objects used in traps."
                INDEX         { pduId }
                ::= { trapInformationTable 1 }

TrapInformationEntryStruct ::= SEQUENCE { 
                                    userName                          DisplayString,
                                    targetUser                        DisplayString,
                                    imageVersion                      DisplayString,
                                    roleName                          DisplayString,
                                    smtpMessageRecipients             DisplayString,
                                    smtpServer                        DisplayString
                              }



userName                       OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The user currently logged in."
                                      ::= { trapInformationEntry 2 }

targetUser                     OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The user added, deleted, or modified."
                                      ::= { trapInformationEntry 3 }


imageVersion                   OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The version of the upgrade image."
                                      ::= { trapInformationEntry 5 }

roleName                       OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The role added, deleted, or modified."
                                      ::= { trapInformationEntry 6 }


smtpMessageRecipients         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Comma separated list of SMTP Message recipients"
                                      ::= { trapInformationEntry 7 }


smtpServer                         OBJECT-TYPE
                                             SYNTAX        DisplayString
                                             MAX-ACCESS    read-only
                                             STATUS        current
                                             DESCRIPTION
                                                 "The IP address/host name of the SMTP server"
                                             ::= { trapInformationEntry 8 }





-- Additional Information needed for traps.



oldSensorState              OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The old sensor state used in Sensor State Transition traps."
                                      ::= { trapInformation  2}

pduNumber                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each PDU. Its value
                                           ranges between 1 and the value of pduCount."
                                      ::= { trapInformation 3 }




inletPoleNumber                   OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each inlet Pole. Its value
                                           ranges between 1 and the value of inletPoleCount."
                                      ::= { trapInformation 5 }  





outletPoleNumber                   OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each outlet Pole. Its value
                                           ranges between 1 and the value of outletPoleCount."
                                      ::= { trapInformation 7 }  



externalSensorNumber               OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each external sensor. Its value
                                           ranges between 1 and the value of externalSensorCount."
                                      ::= { trapInformation 8  }  





typeOfSensor                     OBJECT-TYPE
                                      SYNTAX        SensorTypeEnumeration
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The type of sensor."
                                      ::= { trapInformation 10 }    


errorDescription                    OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "Description of the Error"
                                      ::= { trapInformation 11 }


deviceChangedParameter                    OBJECT-TYPE
                                      SYNTAX        DeviceIdentificationParameterEnumeration 
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "Description of the parameter(s) that changed.
                                          "
                                      ::= { trapInformation 12 }


changedParameterNewValue             OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The new value of the changed parameter "
                                      ::= { trapInformation 13 }


lhxSupportEnabled   	 OBJECT-TYPE
                         SYNTAX        TruthValue
                         MAX-ACCESS    accessible-for-notify
                         STATUS        current
                         DESCRIPTION
                             "The new enabled state for Schroff LHX Support."
                         ::= { trapInformation 14 }



webcamModel                        OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The model of the Webcam "
                                      ::= { trapInformation 15 }


webcamConnectionPort                OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The port to which the Webcam is connected "
                                      ::= { trapInformation 16 }

agentInetPortNumber               OBJECT-TYPE
                                      SYNTAX        InetPortNumber
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The UDP port number used for accessing 
                                             the SNMP agent on the device.
                                             Examples: 
                                                  If deviceCascadeType is portForwarding, then
                                                       master: 50500
                                                       slave 1:50501
                                                       slave 2: 50502
                                                       ...... 
                                                  If cascading mode is not portForwarding and default (Standard) ports are being used, then
                                                       port: 161
                                                       
                                           "
                                      ::= { trapInformation 18  }  

peripheralDeviceRomcode            OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The Romcode of an peripheral device"
                                      ::= { trapInformation 19 }


peripheralDeviceFirmwareUpdateState OBJECT-TYPE
                                      SYNTAX        PeripheralDeviceFirmwareUpdateStateEnumeration
                                      MAX-ACCESS    accessible-for-notify
                                      STATUS        current
                                      DESCRIPTION
                                          "The firmware update state of an peripheral device"
                                      ::= { trapInformation 20 }


-- the unitSensorConfiguration table

-- The unitSensorConfiguration table contains information on the PDU's unit Sensors.


unitSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF UnitSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of unit level sensors for a PDU."
                ::= { unit 5 }

unitSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        UnitSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing unit sensor parameters."
                INDEX         { pduId, sensorType }
                ::= { unitSensorConfigurationTable 1 }

UnitSensorConfigurationEntryStruct ::= SEQUENCE {sensorType             SensorTypeEnumeration, 
                                    unitSensorLogAvailable              TruthValue,
                                    unitSensorUnits                     SensorUnitsEnumeration,
                                    unitSensorDecimalDigits             Unsigned32,
                                    unitSensorAccuracy                  HundredthsOfAPercentage,
                                    unitSensorResolution                Unsigned32,
                                    unitSensorTolerance                 Unsigned32,
                                    unitSensorMaximum                   Unsigned32,
                                    unitSensorMinimum                   Unsigned32,
                                    unitSensorHysteresis                Unsigned32,
                                    unitSensorStateChangeDelay          Unsigned32,
                                    unitSensorLowerCriticalThreshold    Unsigned32,
                                    unitSensorLowerWarningThreshold     Unsigned32,
                                    unitSensorUpperCriticalThreshold    Unsigned32,
                                    unitSensorUpperWarningThreshold     Unsigned32,
                                    unitSensorEnabledThresholds         BITS,
                                    unitSensorSignedMaximum                Integer32,
                                    unitSensorSignedMinimum                Integer32,
                                    unitSensorSignedLowerCriticalThreshold Integer32,
                                    unitSensorSignedLowerWarningThreshold  Integer32,
                                    unitSensorSignedUpperCriticalThreshold Integer32,
                                    unitSensorSignedUpperWarningThreshold  Integer32
                                                                                 }

sensorType                            OBJECT-TYPE
                                      SYNTAX        SensorTypeEnumeration
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "The type of sensor."
                                      ::= { unitSensorConfigurationEntry 1 }

unitSensorLogAvailable                OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging enabled for the sensor?"
                                      ::= { unitSensorConfigurationEntry 4 }

unitSensorUnits                       OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The  units in which the sensor data is reported.
                                           "
                                      ::= { unitSensorConfigurationEntry 6 }

unitSensorDecimalDigits               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point."
                                      ::= { unitSensorConfigurationEntry 7 }

unitSensorAccuracy                    OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value."
                                      ::= { unitSensorConfigurationEntry 8 }


unitSensorResolution                  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           unitSensorDecimalDigits.  For example, if the value is 1 and 
                                           unitSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { unitSensorConfigurationEntry 9 }

unitSensorTolerance                   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (unitSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           unitSensorDecimalDigits is 2, then actual value is 0.05."
                                      ::= { unitSensorConfigurationEntry 10 }

unitSensorMaximum                     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 11 }

unitSensorMinimum                     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 12 }

unitSensorHysteresis                  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by 
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 13 }

unitSensorStateChangeDelay            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as 
                                           it is detected; if it is non-zero, say n, then the assertion 
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 14 }

unitSensorLowerCriticalThreshold      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 21 }

unitSensorLowerWarningThreshold       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 22 }

unitSensorUpperCriticalThreshold      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 23 }

unitSensorUpperWarningThreshold       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 24 }

unitSensorEnabledThresholds           OBJECT-TYPE
                                      SYNTAX        BITS {
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 25 }

unitSensorSignedMaximum               OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 26 }

unitSensorSignedMinimum               OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 27 }

unitSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 28 }

unitSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 29 }

unitSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 30 }

unitSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { unitSensorConfigurationEntry 31 }



-- the inletConfiguration table

-- The inletConfiguration table contains information on the PDU's inlets.


inletConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of inlet configuration entries. The number of
                     entries is given by the value of inletCount for the PDU."
                ::= { inlets 3 }

inletConfigurationEntry     OBJECT-TYPE
                SYNTAX        InletConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing parametersfor a particular inlet."
                INDEX         { pduId, inletId }
                ::= { inletConfigurationTable 1 }

InletConfigurationEntryStruct ::= SEQUENCE {inletId                     Integer32, 
                                    inletLabel                          DisplayString,
                                    inletName                           DisplayString,
                                    inletPlug                           PlugTypeEnumeration,
                                    inletPoleCount                      Integer32,
                                    inletRatedVoltage                   DisplayString,
                                    inletRatedCurrent                   DisplayString,
                                    inletRatedFrequency                 DisplayString,
                                    inletRatedVA                        DisplayString,
                                    inletDeviceCapabilities             BITS,
                                    inletPoleCapabilities               BITS,
                                    inletPlugDescriptor                 DisplayString,
                                    inletEnableState                    TruthValue,
                                    inletRCMResidualOperatingCurrent    Unsigned32
                                    }

inletId                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each inlet. Its value
                                           ranges between 1 and the value of inletCount."
                                      ::= { inletConfigurationEntry 1 }


inletLabel                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The label on the PDU identifying the inlet."
                                      ::= { inletConfigurationEntry 2 }

inletName                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The user-defined name."
                                      ::= { inletConfigurationEntry 3 }

inletPlug                         OBJECT-TYPE
                                      SYNTAX        PlugTypeEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The type of plug/receptacle wired to the inlet."
                                      ::= { inletConfigurationEntry 4 }

inletPoleCount                    OBJECT-TYPE
                                      SYNTAX        Integer32(2..4)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of poles. For inlets with neutral poles, this number will 
                                           include the neutral pole; however, sensors are not supported for 
                                           neutral poles"
                                      ::= { inletConfigurationEntry 5 }

inletRatedVoltage                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The inlet voltage rating."
                                      ::= { inletConfigurationEntry 6 }


inletRatedCurrent                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The inlet current rating."
                                      ::= { inletConfigurationEntry 7 }


inletRatedFrequency                      OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The inlet frequency rating."
                                      ::= { inletConfigurationEntry 8 }




inletRatedVA                             OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The inlet VA (VoltAmps) rating."
                                      ::= { inletConfigurationEntry 9 }



inletDeviceCapabilities                 OBJECT-TYPE
                                      SYNTAX        BITS{ 
                                                  rmsCurrent(0),
                                                  peakCurrent(1),
                                                  unbalancedCurrent(2),
                                                  rmsVoltage(3),  
                                                  activePower(4),
                                                  apparentPower(5),
                                                  powerFactor(6),
                                                  activeEnergy(7),
                                                  apparentEnergy(8),
                                                  surgeProtectorStatus(21),
                                                  frequency(22),
                                                  phaseAngle(23),
                                                  residualCurrent(26),
                                                  rcmState(27),
                                                  powerQuality(31)
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which inlet sensors are available."
                                      ::= { inletConfigurationEntry 10 }

inletPoleCapabilities                 OBJECT-TYPE
                                      SYNTAX        BITS{ 
                                                  rmsCurrent(0),
                                                  peakCurrent(1),
                                                  rmsVoltage(3),
                                                  activePower(4),
                                                  apparentPower(5),
                                                  powerFactor(6),
                                                  activeEnergy(7),
                                                  apparentEnergy(8),
                                                  rmsVoltageLN(24)
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which inletpole sensors are available."
                                      ::= { inletConfigurationEntry 11 }

inletPlugDescriptor                   OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Description of the Plug"
                                      ::= { inletConfigurationEntry 12 }

inletEnableState                      OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is this PDU operation is enabled for this inlet?
                                           When PDU operation is disabled the sensors for this inlet and all
                                           children will no longer be updated, and outlet switching is no longer
                                           allowed. This is only meaningful for multi-inlet units if one inlet
                                           is temporarily expected to be powered down.
                                           Disabling the inlet of a single-inlet unit is forbidden and any
                                           attempt to do so will result in an error."
                                      ::= { inletConfigurationEntry 13 }


inletRCMResidualOperatingCurrent     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The Residual Operating Current (Threshold) for the RCM State sensor. 
                                           For inlets without an RCM, any attempt to access this OID will return 
                                           NoSuchInstance error. The value of this OID is in milliamps.
                                           "
                                      ::= { inletConfigurationEntry 14 }







-- The inletSensorConfiguration table contains information on the PDU's inlet Sensors.


inletSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of configuration entries for an inlet sensor."
                ::= { inlets 4 }

inletSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        InletSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing objects for configuring an inlet sensor."
                INDEX         { pduId, inletId, sensorType }
                ::= { inletSensorConfigurationTable 1 }

InletSensorConfigurationEntryStruct ::= SEQUENCE {
                                    inletSensorLogAvailable              TruthValue,
                                    inletSensorUnits                     SensorUnitsEnumeration,
                                    inletSensorDecimalDigits             Unsigned32,
                                    inletSensorAccuracy                  HundredthsOfAPercentage,
                                    inletSensorResolution                Unsigned32,
                                    inletSensorTolerance                 Unsigned32,
                                    inletSensorMaximum                   Unsigned32,
                                    inletSensorMinimum                   Unsigned32,
                                    inletSensorHysteresis                Unsigned32,
                                    inletSensorStateChangeDelay          Unsigned32,
                                    inletSensorLowerCriticalThreshold    Unsigned32,
                                    inletSensorLowerWarningThreshold     Unsigned32,
                                    inletSensorUpperCriticalThreshold    Unsigned32,
                                    inletSensorUpperWarningThreshold     Unsigned32,
                                    inletSensorEnabledThresholds         BITS,
                                    inletSensorSignedMaximum                Integer32,
                                    inletSensorSignedMinimum                Integer32,
                                    inletSensorSignedLowerCriticalThreshold Integer32,
                                    inletSensorSignedLowerWarningThreshold  Integer32,
                                    inletSensorSignedUpperCriticalThreshold Integer32,
                                    inletSensorSignedUpperWarningThreshold  Integer32
                                    }

inletSensorLogAvailable        OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging enabled for the sensor?"
                                      ::= { inletSensorConfigurationEntry 4 }

inletSensorUnits             OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 6 }

inletSensorDecimalDigits    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 7 }

inletSensorAccuracy        OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 8 }

inletSensorResolution        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           inletSensorDecimalDigits.  For example, if the value is 1 and 
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 9 }

inletSensorTolerance        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (inletSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           inletSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 10 }

inletSensorMaximum                    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 11 }

inletSensorMinimum                    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 12 }

inletSensorHysteresis                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by 
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 13 }

inletSensorStateChangeDelay           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 14 }

inletSensorLowerCriticalThreshold     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 21 }

inletSensorLowerWarningThreshold      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 22 }

inletSensorUpperCriticalThreshold     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 23 }

inletSensorUpperWarningThreshold      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 24 }

inletSensorEnabledThresholds          OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 25 }

inletSensorSignedMaximum              OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 26 }

inletSensorSignedMinimum              OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 27 }

inletSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 28 }

inletSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 29 }

inletSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 30 }

inletSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorConfigurationEntry 31 }



-- The inletPoleSensorConfiguration table contains information on the PDU's inlet pole Sensors.


inletPoleSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletPoleSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of configuration entries for an inlet pole sensor."
                ::= { inlets 6 }

inletPoleSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        InletPoleSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing objects 
                     for configuring an inlet pole sensor."
                INDEX         {  pduId, inletId,inletPoleIndex,sensorType }
                ::= { inletPoleSensorConfigurationTable 1 }

InletPoleSensorConfigurationEntryStruct ::= SEQUENCE { inletPoleIndex        Integer32,
                                    inletPoleSensorLogAvailable              TruthValue,
                                    inletPoleSensorUnits                     SensorUnitsEnumeration,
                                    inletPoleSensorDecimalDigits             Unsigned32,
                                    inletPoleSensorAccuracy                  HundredthsOfAPercentage,
                                    inletPoleSensorResolution                Unsigned32,
                                    inletPoleSensorTolerance                 Unsigned32,
                                    inletPoleSensorMaximum                   Unsigned32,
                                    inletPoleSensorMinimum                   Unsigned32,
                                    inletPoleSensorHysteresis                Unsigned32,
                                    inletPoleSensorStateChangeDelay          Unsigned32,
                                    inletPoleSensorLowerCriticalThreshold    Unsigned32,
                                    inletPoleSensorLowerWarningThreshold     Unsigned32,
                                    inletPoleSensorUpperCriticalThreshold    Unsigned32,
                                    inletPoleSensorUpperWarningThreshold     Unsigned32,
                                    inletPoleSensorEnabledThresholds         BITS,
                                    inletPoleSensorSignedMaximum                Integer32,
                                    inletPoleSensorSignedMinimum                Integer32,
                                    inletPoleSensorSignedLowerCriticalThreshold Integer32,
                                    inletPoleSensorSignedLowerWarningThreshold  Integer32,
                                    inletPoleSensorSignedUpperCriticalThreshold Integer32,
                                    inletPoleSensorSignedUpperWarningThreshold  Integer32
                                    }

inletPoleIndex                        OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each inlet Pole. Its value
                                           ranges between 1 and the value of inletPoleCount."
                                      ::= { inletPoleSensorConfigurationEntry 1 }

inletPoleSensorLogAvailable           OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging enabled for the sensor?"
                                      ::= { inletPoleSensorConfigurationEntry 4 }


inletPoleSensorUnits                  OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 6 }


inletPoleSensorDecimalDigits          OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 7 }




inletPoleSensorAccuracy               OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 8 }


inletPoleSensorResolution             OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and 
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 9 }

inletPoleSensorTolerance              OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (inletPoleSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 10 }

inletPoleSensorMaximum                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 11 }

inletPoleSensorMinimum                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 12 }

inletPoleSensorHysteresis             OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by 
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 13 }

inletPoleSensorStateChangeDelay       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 14 }

inletPoleSensorLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 21 }

inletPoleSensorLowerWarningThreshold  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 22 }

inletPoleSensorUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 23 }

inletPoleSensorUpperWarningThreshold  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 24 }

inletPoleSensorEnabledThresholds      OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 25 }

inletPoleSensorSignedMaximum          OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 26 }

inletPoleSensorSignedMinimum          OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 27 }

inletPoleSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 28 }

inletPoleSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 29 }

inletPoleSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 30 }

inletPoleSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorConfigurationEntry 31 }



-- the overCurrentProtectorConfiguration table

-- The overCurrentProtectorConfiguration table contains information on the PDU's overcurrent protectors.


overCurrentProtectorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OverCurrentProtectorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of overCurrentProtector configuration entries. The number of
                     entries is given by the value of overCurrentProtectorCount for the PDU."
                ::= { overCurrentProtector 3 }

overCurrentProtectorConfigurationEntry     OBJECT-TYPE
                SYNTAX        OverCurrentProtectorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing objects for a particular overCurrentProtector."
                INDEX         { pduId, overCurrentProtectorIndex }
                ::= { overCurrentProtectorConfigurationTable 1 }

OverCurrentProtectorConfigurationEntryStruct ::= SEQUENCE { overCurrentProtectorIndex         Integer32, 
                                    overCurrentProtectorLabel                 DisplayString,
                                    overCurrentProtectorName                  DisplayString,
                                    overCurrentProtectorType                  OverCurrentProtectorTypeEnumeration,
                                    overCurrentProtectorRatedCurrent          DisplayString,
                                    overCurrentProtectorCapabilities          BITS,
                                    overCurrentProtectorPowerSource           RowPointer
                                    }


overCurrentProtectorIndex                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each overcurrent protector. Its value
                                           ranges between 1 and the value of overCurrentProtectorCount."
                                      ::= { overCurrentProtectorConfigurationEntry 1 }

overCurrentProtectorLabel                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The label on the PDU identifying the overcurrent protector."
                                      ::= { overCurrentProtectorConfigurationEntry 2 }

overCurrentProtectorName                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The user-defined name."
                                      ::= { overCurrentProtectorConfigurationEntry 3 }

overCurrentProtectorType                         OBJECT-TYPE
                                      SYNTAX        OverCurrentProtectorTypeEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The type of overcurrent protector."
                                      ::= { overCurrentProtectorConfigurationEntry 4 }




overCurrentProtectorRatedCurrent                     OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The current rating."
                                      ::= { overCurrentProtectorConfigurationEntry 5 }



overCurrentProtectorCapabilities       OBJECT-TYPE
                                      SYNTAX        BITS{                                               
                                                  rmsCurrent(0),
                                                  peakCurrent(1),
                                                  trip(14)
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which overcurrent protector sensors are available."
                                      ::= { overCurrentProtectorConfigurationEntry 9 }

overCurrentProtectorPowerSource       OBJECT-TYPE
                                      SYNTAX        RowPointer
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "This object allows discovery of how the PDU is wired. It indicates the
                                           overCurrentProtector's power source which can one of the following:
                                                  overCurrentProtector
                                                  transfer switch
                                                  inlet

                                           If the power source is an OverCurrentProtector, it
                                           contains the OID of an overCurrentProtectorLabel in the
                                           overCurrentProtectorConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the overCurrentProtectorConfigurationTable.

                                           If the power source is an inlet, it contains the OID of
                                           an inletLabel in the inletConfigurationTable. The index of the OID can
                                           then be used to reference other objects in the inletConfigurationTable.

                                           If the power source is a transferSwitch, it
                                           contains the OID of a transferSwitchLabel in the
                                           transferSwitchConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the transferSwitchConfigurationTable.        
                                           "
                                      ::= { overCurrentProtectorConfigurationEntry 10 }




-- The overCurrentProtectorSensorConfiguration table contains information on the PDU's overcurrent protector Sensors.


overCurrentProtectorSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OverCurrentProtectorSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of overCurrentProtectorSensor configuration entries."
                ::= { overCurrentProtector 4 }

overCurrentProtectorSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        OverCurrentProtectorSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An overCurrentProtectorSensor entry containing objects for a 
                     particular overCurrentProtector Sensor."
                INDEX         { pduId, overCurrentProtectorIndex, sensorType }
                ::= { overCurrentProtectorSensorConfigurationTable 1 }

OverCurrentProtectorSensorConfigurationEntryStruct ::= SEQUENCE {
                                    overCurrentProtectorSensorLogAvailable              TruthValue,
                                    overCurrentProtectorSensorUnits                     SensorUnitsEnumeration,
                                    overCurrentProtectorSensorDecimalDigits             Unsigned32,
                                    overCurrentProtectorSensorAccuracy                  HundredthsOfAPercentage,
                                    overCurrentProtectorSensorResolution                Unsigned32,
                                    overCurrentProtectorSensorTolerance                 Unsigned32,
                                    overCurrentProtectorSensorMaximum                   Unsigned32,
                                    overCurrentProtectorSensorMinimum                   Unsigned32,
                                    overCurrentProtectorSensorHysteresis                Unsigned32,
                                    overCurrentProtectorSensorStateChangeDelay          Unsigned32,
                                    overCurrentProtectorSensorLowerCriticalThreshold    Unsigned32,
                                    overCurrentProtectorSensorLowerWarningThreshold     Unsigned32,
                                    overCurrentProtectorSensorUpperCriticalThreshold    Unsigned32,
                                    overCurrentProtectorSensorUpperWarningThreshold     Unsigned32,
                                    overCurrentProtectorSensorEnabledThresholds         BITS,
                                    overCurrentProtectorSensorSignedMaximum                Integer32,
                                    overCurrentProtectorSensorSignedMinimum                Integer32,
                                    overCurrentProtectorSensorSignedLowerCriticalThreshold Integer32,
                                    overCurrentProtectorSensorSignedLowerWarningThreshold  Integer32,
                                    overCurrentProtectorSensorSignedUpperCriticalThreshold Integer32,
                                    overCurrentProtectorSensorSignedUpperWarningThreshold  Integer32
                                    }

overCurrentProtectorSensorLogAvailable OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging available for this sensor?"
                                      ::= { overCurrentProtectorSensorConfigurationEntry 4 }

overCurrentProtectorSensorUnits       OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 6 }

overCurrentProtectorSensorDecimalDigits OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 7 }

overCurrentProtectorSensorAccuracy    OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 8 }

overCurrentProtectorSensorResolution  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and 
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 9 }

overCurrentProtectorSensorTolerance   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (overCurrentProtectorSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 10 }

overCurrentProtectorSensorMaximum     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 11 }

overCurrentProtectorSensorMinimum     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 12 }

overCurrentProtectorSensorHysteresis  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 13 }

overCurrentProtectorSensorStateChangeDelay OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 14 }

overCurrentProtectorSensorLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 21 }

overCurrentProtectorSensorLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 22 }

overCurrentProtectorSensorUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 23 }

overCurrentProtectorSensorUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 24 }

overCurrentProtectorSensorEnabledThresholds OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 25}

overCurrentProtectorSensorSignedMaximum OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 26 }

overCurrentProtectorSensorSignedMinimum OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 27 }

overCurrentProtectorSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 28 }

overCurrentProtectorSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 29 }

overCurrentProtectorSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 30 }

overCurrentProtectorSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorConfigurationEntry 31 }



-- the outletConfiguration table

-- The outletConfiguration table contains information on the PDU's outlets.


outletConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outlet configuration entries. The number of
                     entries is given by the value of outletCount for the PDU."
                ::= { outlets 3 }

outletConfigurationEntry     OBJECT-TYPE
                SYNTAX        OutletConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An outlet entry containing parameters for a particular outlet."
                INDEX         { pduId, outletId }
                ::= { outletConfigurationTable 1 }

OutletConfigurationEntryStruct ::= SEQUENCE {
                                    outletId                                   Integer32, 
                                    outletLabel                                DisplayString,
                                    outletName                                 DisplayString,
                                    outletReceptacle                           ReceptacleTypeEnumeration,
                                    outletPoleCount                            Integer32,
                                    outletRatedVoltage                         DisplayString,
                                    outletRatedCurrent                         DisplayString,
                                    outletRatedVA                              DisplayString,
                                    outletDeviceCapabilities                   BITS,
                                    outletPoleCapabilities                     BITS,                                    
                                    outletPowerCyclingPowerOffPeriod           Unsigned32,
                                    outletStateOnStartup                       OutletStateOnStartupEnumeration, 
                                    outletUseGlobalPowerCyclingPowerOffPeriod  TruthValue,
                                    outletSwitchable                           TruthValue,
                                    outletReceptacleDescriptor                 DisplayString,
                                    outletNonCritical                          TruthValue,
                                    outletSequenceDelay                        Unsigned32,
                                    outletPowerSource                          RowPointer
                                    }

outletId                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each outlet. Its value
                                           ranges between 1 and the value of outletCount."
                                      ::= { outletConfigurationEntry 1 }


outletLabel                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The label on the PDU identifying the outlet."
                                      ::= { outletConfigurationEntry 2 }

outletName                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The user-defined name."
                                      ::= { outletConfigurationEntry 3 }

outletReceptacle                   OBJECT-TYPE
                                      SYNTAX        ReceptacleTypeEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The plug."
                                      ::= { outletConfigurationEntry 4 }

outletPoleCount                    OBJECT-TYPE
                                      SYNTAX        Integer32(2..4)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of poles."
                                      ::= { outletConfigurationEntry 5 }

outletRatedVoltage                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The outlet voltage rating."
                                      ::= { outletConfigurationEntry 6 }


outletRatedCurrent                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The outlet current rating."
                                      ::= { outletConfigurationEntry 7 }


outletRatedVA                             OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The outlet VA (VoltAmps) rating."
                                      ::= { outletConfigurationEntry 8 }



outletDeviceCapabilities                 OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  rmsCurrent(0),
                                                  peakCurrent(1),
                                                  unbalancedCurrent(2),
                                                  rmsVoltage(3), 
                                                  activePower(4),
                                                  apparentPower(5),
                                                  powerFactor(6),
                                                  activeEnergy(7),
                                                  apparentEnergy(8),
                                                  onOff(13),
                                                  frequency(22),
                                                  phaseAngle(23)
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which outlet sensors are available."
                                      ::= { outletConfigurationEntry 10 }

outletPoleCapabilities                 OBJECT-TYPE
                                      SYNTAX        BITS{ 
                                                  rmsCurrent(0),
                                                  peakCurrent(1),
                                                  rmsVoltage(3),
                                                  activePower(4),
                                                  apparentPower(5),
                                                  powerFactor(6),
                                                  activeEnergy(7),
                                                  apparentEnergy(8),
                                                  rmsVoltageLN(24) 
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which outlet pole sensors are available."
                                      ::= { outletConfigurationEntry 11 }


outletPowerCyclingPowerOffPeriod          OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The power-off period when an outlet is cycled;
                                           overrides the global value;
                                           specified in seconds; 
                                           0 <= value <= 3600 seconds."
                                      ::= { outletConfigurationEntry 12 }


outletStateOnStartup         OBJECT-TYPE
                                      SYNTAX        OutletStateOnStartupEnumeration
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The outlet state on device startup;
                                           overrides the global value.
			       		   Note that this value is ignored if
					   relayBehaviorOnPowerLoss is set to latching."
                                      ::= { outletConfigurationEntry 13}


outletUseGlobalPowerCyclingPowerOffPeriod  OBJECT-TYPE
                                     SYNTAX        TruthValue
                                     MAX-ACCESS    read-write
                                     STATUS        current
                                     DESCRIPTION
                                        "If this true, then use globalOutletPowerCyclingPowerOffPeriod."
                                    ::= { outletConfigurationEntry 14 }




outletSwitchable                    OBJECT-TYPE
                                     SYNTAX        TruthValue
                                     MAX-ACCESS    read-only
                                     STATUS        current
                                     DESCRIPTION
                                        "Is this outlet switchable?"
                                    ::= { outletConfigurationEntry 28 }


outletReceptacleDescriptor          OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Description of the Receptacle"
                                      ::= { outletConfigurationEntry 29 }


outletNonCritical                    OBJECT-TYPE
                                     SYNTAX        TruthValue
                                     MAX-ACCESS    read-write
                                     STATUS        current
                                     DESCRIPTION
                                        "Is this outlet non-critical?"
                                    ::= { outletConfigurationEntry 30 }





outletSequenceDelay                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The time interval between switching on this outlet and the next outlet in the
                                           outlet sequence. 
                                           This applies to the following operations.
                                            1) Switch all outlets on operation is executed
                                            2) Power to the PDU is cycledThis applies only when all outlets are being switched on or cycled. 
                                          It is specified in seconds; 
                                           1 <= value <= 3600 seconds.
                                           The actual time interval used can never be less than  the inrushGuardDelay defined 
                                           in the unitConfigurationTable.
                                           Examples: 
                                             1)  inrush Guard Delay is 2 seconds and outletSequenceDelay is 5 seconds.
                                                 The time interval will be 5 seconds 
                                             2)  inrush Guard Delay is 5 seconds and outletSequenceDelay is 2 seconds.
                                                 The time interval will be 5 seconds
                                          "
                                      ::= { outletConfigurationEntry 32 }


outletPowerSource                    OBJECT-TYPE
                                      SYNTAX        RowPointer
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "This object allows discovery of how the PDU is wired. It indicates the
                                           outlet's power source which can one of the following:
                                                  overCurrentProtector
                                                  transfer switch
                                                  inlet

                                           If the power source is an OverCurrentProtector, it
                                           contains the OID of an overCurrentProtectorLabel in the
                                           overCurrentProtectorConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the overCurrentProtectorConfigurationTable.

                                           If the power source is an inlet, it contains the OID of
                                           an inletLabel in the inletConfigurationTable. The index of the OID can
                                           then be used to reference other objects in the inletConfigurationTable.

                                           If the power source is a transferSwitch, it
                                           contains the OID of a transferSwitchLabel in the
                                           transferSwitchConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the transferSwitchConfigurationTable.
                               
                                           "
                                      ::= { outletConfigurationEntry 33}



-- The outletSensorConfiguration table contains information on the PDU's inlet Sensors.


outletSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outlet configuration entries. The number of
                     entries is given by the value of outletCount for the PDU."
                ::= { outlets 4 }

outletSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        OutletSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing parameters for an outlet sensor."
                INDEX         { pduId, outletId,sensorType }
                ::= { outletSensorConfigurationTable 1 }

OutletSensorConfigurationEntryStruct ::= SEQUENCE {
                                    outletSensorLogAvailable              TruthValue,
                                    outletSensorUnits                     SensorUnitsEnumeration,
                                    outletSensorDecimalDigits             Unsigned32,
                                    outletSensorAccuracy                  HundredthsOfAPercentage,
                                    outletSensorResolution                Unsigned32,
                                    outletSensorTolerance                 Unsigned32,
                                    outletSensorMaximum                   Unsigned32,
                                    outletSensorMinimum                   Unsigned32,
                                    outletSensorHysteresis                Unsigned32,
                                    outletSensorStateChangeDelay          Unsigned32,
                                    outletSensorLowerCriticalThreshold    Unsigned32,
                                    outletSensorLowerWarningThreshold     Unsigned32,
                                    outletSensorUpperCriticalThreshold    Unsigned32,
                                    outletSensorUpperWarningThreshold     Unsigned32,
                                    outletSensorEnabledThresholds         BITS,
                                    outletSensorSignedMaximum                Integer32,
                                    outletSensorSignedMinimum                Integer32,
                                    outletSensorSignedLowerCriticalThreshold Integer32,
                                    outletSensorSignedLowerWarningThreshold  Integer32,
                                    outletSensorSignedUpperCriticalThreshold Integer32,
                                    outletSensorSignedUpperWarningThreshold  Integer32
                                    }

outletSensorLogAvailable              OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging available for this sensor?"
                                      ::= { outletSensorConfigurationEntry 4 }

outletSensorUnits                     OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 6 }

outletSensorDecimalDigits             OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 7 }

outletSensorAccuracy                  OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 8 }

outletSensorResolution                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           outletSensorDecimalDigits.  For example, if the value is 1 and 
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 9 }

outletSensorTolerance                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (outletSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           outletSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 10 }

outletSensorMaximum                   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 11 }

outletSensorMinimum                   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 12 }

outletSensorHysteresis                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 13 }

outletSensorStateChangeDelay          OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 14 }

outletSensorLowerCriticalThreshold    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 21 }

outletSensorLowerWarningThreshold     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 22 }

outletSensorUpperCriticalThreshold    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 23 }

outletSensorUpperWarningThreshold     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 24 }

outletSensorEnabledThresholds         OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 25 }

outletSensorSignedMaximum             OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 26 }

outletSensorSignedMinimum             OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 27 }

outletSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 28 }

outletSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 29 }

outletSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 30 }

outletSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorConfigurationEntry 31 }



-- The outletPoleSensorConfiguration table contains information on the PDU's outlet pole Sensors.


outletPoleSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletPoleSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outlet pole sensor configuration entries. The number of
                     entries is given by the value of outletPoleCount."
                ::= { outlets 6 }

outletPoleSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        OutletPoleSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing objects 
                     for configuring an outlet pole sensor."
                INDEX         {  pduId, outletId,outletPoleIndex,sensorType }
                ::= { outletPoleSensorConfigurationTable 1 }

OutletPoleSensorConfigurationEntryStruct ::= SEQUENCE { outletPoleIndex       Integer32,
                                    outletPoleSensorLogAvailable              TruthValue,
                                    outletPoleSensorUnits                     SensorUnitsEnumeration,
                                    outletPoleSensorDecimalDigits             Unsigned32,
                                    outletPoleSensorAccuracy                  HundredthsOfAPercentage,
                                    outletPoleSensorResolution                Unsigned32,
                                    outletPoleSensorTolerance                 Unsigned32,
                                    outletPoleSensorMaximum                   Unsigned32,
                                    outletPoleSensorMinimum                   Unsigned32,
                                    outletPoleSensorHysteresis                Unsigned32,
                                    outletPoleSensorStateChangeDelay          Unsigned32,
                                    outletPoleSensorLowerCriticalThreshold    Unsigned32,
                                    outletPoleSensorLowerWarningThreshold     Unsigned32,
                                    outletPoleSensorUpperCriticalThreshold    Unsigned32,
                                    outletPoleSensorUpperWarningThreshold     Unsigned32,
                                    outletPoleSensorEnabledThresholds         BITS,
                                    outletPoleSensorSignedMaximum                Integer32,
                                    outletPoleSensorSignedMinimum                Integer32,
                                    outletPoleSensorSignedLowerCriticalThreshold Integer32,
                                    outletPoleSensorSignedLowerWarningThreshold  Integer32,
                                    outletPoleSensorSignedUpperCriticalThreshold Integer32,
                                    outletPoleSensorSignedUpperWarningThreshold  Integer32
                                    }

outletPoleIndex                       OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each outlet Pole. Its value
                                           ranges between 1 and the value of outletPoleCount."
                                      ::= { outletPoleSensorConfigurationEntry 1 }

outletPoleSensorLogAvailable          OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging enabled for the sensor?"
                                      ::= { outletPoleSensorConfigurationEntry 4 }

outletPoleSensorUnits                 OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 6 }

outletPoleSensorDecimalDigits         OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 7 }

outletPoleSensorAccuracy              OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 8 }


outletPoleSensorResolution            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           outletPoleSensorDecimalDigits.  For example, if the value is 50 and 
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 9 }

outletPoleSensorTolerance             OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (outletPoleSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 10 }

outletPoleSensorMaximum               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 11 }

outletPoleSensorMinimum               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 12 }

outletPoleSensorHysteresis            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 13 }

outletPoleSensorStateChangeDelay      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 14 }

outletPoleSensorLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 21 }

outletPoleSensorLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 22 }

outletPoleSensorUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 23 }

outletPoleSensorUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 24 }

outletPoleSensorEnabledThresholds     OBJECT-TYPE
                                      SYNTAX        BITS{
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 25 }

outletPoleSensorSignedMaximum         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 26 }

outletPoleSensorSignedMinimum         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 27 }

outletPoleSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 28 }

outletPoleSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 29 }

outletPoleSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 30 }

outletPoleSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorConfigurationEntry 31 }



-- the externalSensorConfiguration table

-- The externalSensorConfiguration table contains information on the PDU's external Sensors.



externalSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ExternalSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of externalSensor configuration entries. The number of
                     entries is given by the value of externalSensorCount for the PDU."
                ::= { externalSensors 3 }

externalSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        ExternalSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing parameters for an external sensor."
                INDEX         { pduId, sensorID }
                ::= { externalSensorConfigurationTable 1 }

ExternalSensorConfigurationEntryStruct ::= SEQUENCE {sensorID              Integer32, 
                                    externalSensorType                     SensorTypeEnumeration,
                                    externalSensorSerialNumber              DisplayString,
                                    externalSensorName                      DisplayString,
                                    externalSensorDescription               DisplayString,
                                    externalSensorXCoordinate               DisplayString,
                                    externalSensorYCoordinate               DisplayString,
                                    externalSensorZCoordinate               DisplayString,
                                    externalSensorChannelNumber             Integer32,
                                    externalOnOffSensorSubtype              SensorTypeEnumeration,
                                    externalSensorLogAvailable              TruthValue,
                                    externalSensorUnits                     SensorUnitsEnumeration,
                                    externalSensorDecimalDigits             Unsigned32,
                                    externalSensorAccuracy                  HundredthsOfAPercentage,
                                    externalSensorResolution                Unsigned32,
                                    externalSensorTolerance                 Unsigned32,
                                    externalSensorMaximum                   Integer32,
                                    externalSensorMinimum                   Integer32,
                                    externalSensorHysteresis                Unsigned32,
                                    externalSensorStateChangeDelay          Unsigned32,
                                    externalSensorLowerCriticalThreshold    Integer32,
                                    externalSensorLowerWarningThreshold     Integer32,
                                    externalSensorUpperCriticalThreshold    Integer32,
                                    externalSensorUpperWarningThreshold     Integer32,
                                    externalSensorEnabledThresholds         BITS,
                                    externalSensorIsActuator                TruthValue,
                                    externalSensorPosition                  DisplayString,
                                    externalSensorUseDefaultThresholds      TruthValue,
				    externalSensorAlarmedToNormalDelay	    Integer32
                                    }

sensorID                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each sensor. Its value
                                           ranges between 1 and the value of externalSensorCount."
                                      ::= { externalSensorConfigurationEntry 1 }


externalSensorType                 OBJECT-TYPE
                                      SYNTAX        SensorTypeEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The type of sensor."
                                      ::= { externalSensorConfigurationEntry 2 }





externalSensorSerialNumber         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor serial number."
                                      ::= { externalSensorConfigurationEntry 3 }

externalSensorName                 OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The user-defined name."
                                      ::= { externalSensorConfigurationEntry 4 }

externalSensorDescription          OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The user-defined description."
                                      ::= { externalSensorConfigurationEntry 5 }

externalSensorXCoordinate          OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The X coordinate."
                                      ::= { externalSensorConfigurationEntry 6 }

externalSensorYCoordinate          OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The Y coordinate."
                                      ::= { externalSensorConfigurationEntry 7 }

externalSensorZCoordinate          OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The Z coordinate."
                                      ::= { externalSensorConfigurationEntry 8 }


externalSensorChannelNumber      OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The channel number, applies only to contact sensors;
                                           -1 for other sensors"
                                      ::= { externalSensorConfigurationEntry 9 }

externalOnOffSensorSubtype       OBJECT-TYPE
                                      SYNTAX        SensorTypeEnumeration
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The subtype of the binary sensor"
                                      ::= { externalSensorConfigurationEntry 10 }




externalSensorLogAvailable        OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging available for this sensor?"
                                      ::= { externalSensorConfigurationEntry 14 }

externalSensorUnits             OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units
                                           This parameter does not apply   
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 16 }

externalSensorDecimalDigits    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point
                                           This parameter does not apply  
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 17 }




externalSensorAccuracy        OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 18 }


externalSensorResolution        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 19 }

externalSensorTolerance        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (externalSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply 
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 20 }

externalSensorMaximum        OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible value
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 21 }

externalSensorMinimum        OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible value
                                            The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply 
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 22 }



externalSensorHysteresis        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 23 }

externalSensorStateChangeDelay  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion 
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           At present, this value cannot be written (set)"
                                      ::= { externalSensorConfigurationEntry 24 }

externalSensorLowerCriticalThreshold        OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 31 }

externalSensorLowerWarningThreshold      OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower non-critical (warning) threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 32 }

externalSensorUpperCriticalThreshold        OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical  threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 33 }

externalSensorUpperWarningThreshold         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper non-critical (warning) threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorConfigurationEntry 34 }


externalSensorEnabledThresholds            OBJECT-TYPE
                                      SYNTAX        BITS{                                     
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply 
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors 
                                           "
                                      ::= { externalSensorConfigurationEntry 35}


externalSensorIsActuator        OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is this an actuator?
                                           True:  It is an actuator
                                           False: It is not an actuator"
                                      ::= { externalSensorConfigurationEntry 36 }


externalSensorPosition          OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The position of the sensor.
                                           The format is a semicolon separated list of Keyword:value pairs - Keyword1:Value1;Keyword2:value2;...
                                              Keyword can be one of the following: ONBOARD,DEVICE-1WIREPORT;HUBPORT,CHAIN-POSITION
                                              Examples
                                             1)  Onboard Sensor
                                                       ONBOARD:CC1
                                             2)  Old sensor connected to device 1-wire port 
                                                       DEVICE-1WIREPORT:2
                                             3)  Old sensor connected to hub port 
                                                       DEVICE-1WIREPORT:2;HUBPORT:3
                                             4)  New style sensor connected to device 1-wire port 
                                                       DEVICE-1WIREPORT:2;CHAIN-POSITION:3
                                             5)  Old style sensor connected to end of new style sensor chain 
                                                       DEVICE-1WIREPORT:2;CHAIN-POSITION:7   
                                            "
                                      ::= { externalSensorConfigurationEntry 37 }


externalSensorUseDefaultThresholds  OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Use default thresholds for this sensor?
                                           True:  Use Default thresholds for this sensor
                                                  
                                           False: Do not Use Default thresholds for this sensor"
                                      ::= { externalSensorConfigurationEntry 38 }

externalSensorAlarmedToNormalDelay OBJECT-TYPE
	SYNTAX        Integer32
	MAX-ACCESS    read-write
	STATUS        current
	DESCRIPTION
	    "The delay in seconds for transitions from the alarmed state to the normal state.
	      If the sensor type is  motionDetection,
		  then it can set to a value greater >= 0
	      For all other sensor types,
		  the value is 0 and cannot be set to any other value.
	    "
	 ::= { externalSensorConfigurationEntry 39 }


--  This table applies only to G1 External sensors.
--  This table is used for bulk configuration of G1 External sensors.



externalSensorTypeDefaultThresholdsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ExternalSensorTypeDefaultThresholdsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of entries listing the default thresholds for each sensor type. "
                ::= { externalSensors 4 }

externalSensorTypeDefaultThresholdsEntry     OBJECT-TYPE
                SYNTAX        ExternalSensorTypeDefaultThresholdsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing default thresholds for a sensor type."
                INDEX         { pduId, sensorType }
                ::= { externalSensorTypeDefaultThresholdsTable 1 }

ExternalSensorTypeDefaultThresholdsEntryStruct ::= SEQUENCE {
                                    externalSensorTypeDefaultHysteresis               Unsigned32,
                                    externalSensorTypeDefaultStateChangeDelay         Unsigned32,
                                    externalSensorTypeDefaultLowerCriticalThreshold    Integer32,
                                    externalSensorTypeDefaultLowerWarningThreshold    Integer32,
                                    externalSensorTypeDefaultUpperCriticalThreshold   Integer32,
                                    externalSensorTypeDefaultUpperWarningThreshold    Integer32,
                                    externalSensorTypeDefaultEnabledThresholds        BITS
                                    
                                             }




externalSensorTypeDefaultHysteresis        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorTypeDefaultThresholdsEntry 3 }

externalSensorTypeDefaultStateChangeDelay  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion 
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           At present, this value cannot be written (set)"
                                      ::= { externalSensorTypeDefaultThresholdsEntry 4 }

externalSensorTypeDefaultLowerCriticalThreshold        OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorTypeDefaultThresholdsEntry 5 }



externalSensorTypeDefaultLowerWarningThreshold      OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower non-critical (warning) threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorTypeDefaultThresholdsEntry 6 }


externalSensorTypeDefaultUpperCriticalThreshold        OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical  threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorTypeDefaultThresholdsEntry 7 }


externalSensorTypeDefaultUpperWarningThreshold         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper non-critical (warning) threshold
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors."
                                      ::= { externalSensorTypeDefaultThresholdsEntry 8 }


externalSensorTypeDefaultEnabledThresholds            OBJECT-TYPE
                                      SYNTAX        BITS{                                     
                                                  lowerCritical(0),
                                                  lowerWarning(1),
                                                  upperWarning(2),
                                                  upperCritical(3)
                                                        }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply 
                                           to onOff, trip, vibration, waterDetection, 
                                           smokeDetection sensors 
                                           "
                                      ::= { externalSensorTypeDefaultThresholdsEntry 9}






-- the server reachability table

-- The server Reachability table contains information on the ping feature.




serverReachabilityTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ServerReachabilityEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of server entries. The number of
                     entries is given by the value of serverCount for the PDU."
                ::= { serverReachability 3 }

serverReachabilityEntry     OBJECT-TYPE
                SYNTAX        ServerReachabilityEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing parameters for a server."
                INDEX         { pduId, serverID }
                ::= { serverReachabilityTable 1 }

ServerReachabilityEntryStruct ::= SEQUENCE {serverID                        Integer32, 
                                    serverIPAddress                         DisplayString,
                                    serverPingEnabled                       TruthValue
                                    }

serverID                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each server. Its value
                                           ranges between 1 and the value of serverCount for that PDU"
                                      ::= { serverReachabilityEntry 1 }





serverIPAddress                    OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The IP Address/host name of the server"
                                      ::= { serverReachabilityEntry 3 }


serverPingEnabled                  OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is ping enabled for this server?"
                                      ::= { serverReachabilityEntry 4 }


-- the wireConfiguration table

-- The wireConfiguration table contains information on the PDU's wires.


wireConfigurationTable                OBJECT-TYPE
                                      SYNTAX        SEQUENCE OF WireConfigurationEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A list of wire configuration entries. The number of
                                           entries is given by the value of wireCount for the PDU."
                                      ::= { wires 3 }

wireConfigurationEntry                OBJECT-TYPE
                                      SYNTAX        WireConfigurationEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "An entry containing objects for a particular wire."
                                      INDEX         { pduId, wireId }
                                      ::= { wireConfigurationTable 1 }

WireConfigurationEntryStruct ::= SEQUENCE {
                                     wireId                    Integer32,
                                     wireLabel                 DisplayString,
                                     wireCapabilities          BITS,
                                     wirePowerSource           RowPointer
                                 }

wireId                                OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A unique value for each wire. Its value
                                           ranges between 1 and the value of wireCount."
                                      ::= { wireConfigurationEntry 1 }

wireLabel                             OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The label on the PDU identifying the wire."
                                      ::= { wireConfigurationEntry 2 }

wireCapabilities                      OBJECT-TYPE
                                      SYNTAX        BITS {
                                                        rmsCurrent(0),
                                                        peakCurrent(1),
                                                        unbalancedCurrent(2),
                                                        rmsVoltage(3),  
                                                        activePower(4),
                                                        apparentPower(5),
                                                        powerFactor(6),
                                                        activeEnergy(7),
                                                        apparentEnergy(8)
                                                    }
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A bit string  which indicates which wire sensors are available."
                                      ::= { wireConfigurationEntry 3 }


wirePowerSource                          OBJECT-TYPE
                                      SYNTAX        RowPointer
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "This object allows discovery of how the PDU is wired. It indicates the
                                           wire's power source which can one of the following:
                                                  overCurrentProtector
                                                  transfer switch
                                                  inlet

                                           If the power source is an OverCurrentProtector, it
                                           contains the OID of an overCurrentProtectorLabel in the
                                           overCurrentProtectorConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the overCurrentProtectorConfigurationTable.

                                           If the power source is an inlet, it contains the OID of
                                           an inletLabel in the inletConfigurationTable. The index of the OID can
                                           then be used to reference other objects in the inletConfigurationTable.

                                           If the power source is a transferSwitch, it
                                           contains the OID of a transferSwitchLabel in the
                                           transferSwitchConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the transferSwitchConfigurationTable.  
                               
                                           "
                                      ::= { wireConfigurationEntry 4}







-- The wireSensorConfiguration table contains information on the PDU's wire Sensors.

wireSensorConfigurationTable          OBJECT-TYPE
                                      SYNTAX        SEQUENCE OF WireSensorConfigurationEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A list of wireSensor configuration entries."
                                      ::= { wires 4 }

wireSensorConfigurationEntry          OBJECT-TYPE
                                      SYNTAX        WireSensorConfigurationEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "An wireSensor entry containing objects for a
                                           particular wire Sensor."
                                      INDEX         { pduId, wireId, sensorType }
                                      ::= { wireSensorConfigurationTable 1 }

WireSensorConfigurationEntryStruct ::= SEQUENCE {
                                           wireSensorLogAvailable              TruthValue,
                                           wireSensorUnits                     SensorUnitsEnumeration,
                                           wireSensorDecimalDigits             Unsigned32,
                                           wireSensorAccuracy                  HundredthsOfAPercentage,
                                           wireSensorResolution                Unsigned32,
                                           wireSensorTolerance                 Unsigned32,
                                           wireSensorMaximum                   Unsigned32,
                                           wireSensorMinimum                   Unsigned32,
                                           wireSensorHysteresis                Unsigned32,
                                           wireSensorStateChangeDelay          Unsigned32,
                                           wireSensorLowerCriticalThreshold    Unsigned32,
                                           wireSensorLowerWarningThreshold     Unsigned32,
                                           wireSensorUpperCriticalThreshold    Unsigned32,
                                           wireSensorUpperWarningThreshold     Unsigned32,
                                           wireSensorEnabledThresholds         BITS
                                       }

wireSensorLogAvailable                OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "Is logging available for this sensor?"
                                      ::= { wireSensorConfigurationEntry 4 }


wireSensorUnits                       OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The base units"
                                      ::= { wireSensorConfigurationEntry 6 }

wireSensorDecimalDigits               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point."
                                      ::= { wireSensorConfigurationEntry 7 }

wireSensorAccuracy                    OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value"
                                      ::= { wireSensorConfigurationEntry 8 }

wireSensorResolution                  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits. For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 9 }

wireSensorTolerance                   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by
                                           (wireSensorDecimalDigits + 1).  For example, if the value is 50 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.05."
                                      ::= { wireSensorConfigurationEntry 10 }

wireSensorMaximum                     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The largest possible value
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 11 }

wireSensorMinimum                     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The smallest possible value
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 12 }

wireSensorHysteresis                  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 13 }

wireSensorStateChangeDelay            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           At present, this value cannot be written (set)"
                                      ::= { wireSensorConfigurationEntry 14 }

wireSensorLowerCriticalThreshold      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The lower critical threshold
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 21 }

wireSensorLowerWarningThreshold       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The lower non-critical (warning) threshold
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 22 }

wireSensorUpperCriticalThreshold      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The upper critical  threshold
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 23 }

wireSensorUpperWarningThreshold       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The upper non-critical (warning) threshold
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits.  For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { wireSensorConfigurationEntry 24 }

wireSensorEnabledThresholds           OBJECT-TYPE
                                      SYNTAX        BITS {
                                                        lowerCritical(0),
                                                        lowerWarning(1),
                                                        upperWarning(2),
                                                        upperCritical(3)
                                                    }
                                      MAX-ACCESS    read-write
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled."
                                      ::= { wireSensorConfigurationEntry 25 }




-- the transferSwitchConfiguration table

-- The tsConfiguration table contains information on the TS ( Transfer Switch).


transferSwitchConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF TransferSwitchConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of transfer switch configuration entries. The number of
                     entries is given by the value of transferSwitchCount."
                ::= { transferSwitch 3 }

transferSwitchConfigurationEntry     OBJECT-TYPE
                SYNTAX        TransferSwitchConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing objects for a particular transferSwitch."
                INDEX         { pduId, transferSwitchId }
                ::= { transferSwitchConfigurationTable 1 }

TransferSwitchConfigurationEntryStruct ::= SEQUENCE { transferSwitchId                    Integer32, 
                                    transferSwitchLabel                                   DisplayString,
                                    transferSwitchName                                    DisplayString,
                                    transferSwitchPreferredInlet                          Integer32,
                                    transferSwitchAutoReTransferEnabled                   TruthValue,
                                    transferSwitchAutoReTransferWaitTime                  Unsigned32,
                                    transferSwitchAutoReTransferRequiresPhaseSync         TruthValue,
                                    transferSwitchFrontPanelManualTransferButtonEnabled   TruthValue,
                                    transferSwitchCapabilities                            BITS,
                                    transferSwitchPowerSource1                            RowPointer,
                                    transferSwitchPowerSource2                            RowPointer
                                    }


transferSwitchId                           OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each transfer switch. Its value
                                           ranges between 1 and the value of transferSwitchCount."
                                      ::= { transferSwitchConfigurationEntry 1 }

transferSwitchLabel                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The label on the PDU identifying the TS."
                                      ::= { transferSwitchConfigurationEntry 2 }

transferSwitchName                         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The user-defined name of the transferSwitch."
                                      ::= { transferSwitchConfigurationEntry 3 }

transferSwitchPreferredInlet                         OBJECT-TYPE
                                      SYNTAX        Integer32(1..64)
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The preferred Inlet. The TS powers the outlet from the preferred inlet when acceptable power
                                                is available from the preferred inlet.   "
                                      ::= { transferSwitchConfigurationEntry 4 }


transferSwitchAutoReTransferEnabled            OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The TS can be configured to automatically retransfer back to the preferred inlet when power is restored.  
                                           Re-transfer only occurs if this variable is true."
                                      ::= { transferSwitchConfigurationEntry 20 }


transferSwitchAutoReTransferWaitTime           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The Auto Re-Transfer Wait Time. Re-transfer occurs this many seconds after the condition causing the 
                                              original transfer has been corrected."
                                      ::= { transferSwitchConfigurationEntry 21 }


transferSwitchAutoReTransferRequiresPhaseSync   OBJECT-TYPE
                                          SYNTAX        TruthValue
                                          MAX-ACCESS    read-write
                                          STATUS        current
                                          DESCRIPTION
                                          "If this parameter is False, then do not retransfer if there is a PHASE_SYNC_FAULT in effect. A 
                                           PHASE_SYNC_FAULT occurs when the phase difference between the inlets is too high."
                                        ::= { transferSwitchConfigurationEntry 22 }


transferSwitchFrontPanelManualTransferButtonEnabled   OBJECT-TYPE
                                           SYNTAX        TruthValue
                                           MAX-ACCESS    read-write
                                           STATUS        current
                                           DESCRIPTION
                                          "If this parameter is false, then  manual transfers caused by pressing the front panel switch are disabled. "
                                        ::= { transferSwitchConfigurationEntry 23 }


transferSwitchCapabilities                                 OBJECT-TYPE
                                      SYNTAX        BITS {
                                                        overloadStatus(32),
                                                        inletPhaseSyncAngle(37),
                                                        inletPhaseSync(38),
                                                        operatingState(39),
                                                        activeInlet(40),
                                                        switchStatus(47)
                                                        
                                                    }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which sensors are available for the transfer switch."
                                      ::= { transferSwitchConfigurationEntry 24 }


transferSwitchPowerSource1          OBJECT-TYPE
                                      SYNTAX        RowPointer
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "This object allows discovery of how the PDU is wired. It indicates the
                                           transferSwitch's first power source which can one of the following:
                                                  overCurrentProtector
                                                  transfer switch
                                                  inlet

                                           If the power source is an OverCurrentProtector, it
                                           contains the OID of an overCurrentProtectorLabel in the
                                           overCurrentProtectorConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the overCurrentProtectorConfigurationTable.

                                           If the power source is an inlet, it contains the OID of
                                           an inletLabel in the inletConfigurationTable. The index of the OID can
                                           then be used to reference other objects in the inletConfigurationTable.

                                           If the power source is a transferSwitch, it
                                           contains the OID of a transferSwitchLabel in the
                                           transferSwitchConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the transferSwitchConfigurationTable.                 
                               
                                           "
                                      ::= { transferSwitchConfigurationEntry 31 }



transferSwitchPowerSource2           OBJECT-TYPE
                                      SYNTAX        RowPointer
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "This object allows discovery of how the PDU is wired. It indicates the
                                           transferSwitch's second power source which can one of the following:
                                                  overCurrentProtector
                                                  transfer switch
                                                  inlet

                                           If the power source is an OverCurrentProtector, it
                                           contains the OID of an overCurrentProtectorLabel in the
                                           overCurrentProtectorConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the overCurrentProtectorConfigurationTable.

                                           If the power source is an inlet, it contains the OID of
                                           an inletLabel in the inletConfigurationTable. The index of the OID can
                                           then be used to reference other objects in the inletConfigurationTable.

                                           If the power source is a transferSwitch, it
                                           contains the OID of a transferSwitchLabel in the
                                           transferSwitchConfiguration Table. The index of the OID can then be
                                           used to reference other objects in the transferSwitchConfigurationTable       
                               
                                           "
                                      ::= { transferSwitchConfigurationEntry 32 }





-- The transfer switch sensor configuration table contains information on the transfer switch's sensors.

transferSwitchSensorConfigurationTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF TransferSwitchSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of transfer switch sensor configuration entries. "
                ::= { transferSwitch 4 }

transferSwitchSensorConfigurationEntry     OBJECT-TYPE
                SYNTAX        TransferSwitchSensorConfigurationEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing parameters for a transfer switch sensor."
                INDEX         { pduId, transferSwitchId, sensorType }
                ::= { transferSwitchSensorConfigurationTable 1 }

TransferSwitchSensorConfigurationEntryStruct ::= SEQUENCE {
                                                     transferSwitchSensorLogAvailable              TruthValue,
                                                     transferSwitchSensorUnits                     SensorUnitsEnumeration,
                                                     transferSwitchSensorDecimalDigits             Unsigned32,
                                                     transferSwitchSensorAccuracy                  HundredthsOfAPercentage,
                                                     transferSwitchSensorResolution                Unsigned32,
                                                     transferSwitchSensorTolerance                 Unsigned32,
                                                     transferSwitchSensorMaximum                   Unsigned32,
                                                     transferSwitchSensorMinimum                   Unsigned32,
                                                     transferSwitchSensorHysteresis                Unsigned32,
                                                     transferSwitchSensorStateChangeDelay          Unsigned32,
                                                     transferSwitchSensorLowerCriticalThreshold    Unsigned32,
                                                     transferSwitchSensorLowerWarningThreshold     Unsigned32,
                                                     transferSwitchSensorUpperCriticalThreshold    Unsigned32,
                                                     transferSwitchSensorUpperWarningThreshold     Unsigned32,
                                                     transferSwitchSensorEnabledThresholds         BITS,
                                                     transferSwitchSensorSignedMaximum             Integer32,
                                                     transferSwitchSensorSignedMinimum             Integer32,
                                                     transferSwitchSensorSignedLowerCriticalThreshold    Integer32,
                                                     transferSwitchSensorSignedLowerWarningThreshold     Integer32,
                                                     transferSwitchSensorSignedUpperCriticalThreshold    Integer32,
                                                     transferSwitchSensorSignedUpperWarningThreshold     Integer32
                                                 }

transferSwitchSensorLogAvailable      OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "Is logging available for this sensor?"
                                      ::= { transferSwitchSensorConfigurationEntry 4 }

transferSwitchSensorUnits             OBJECT-TYPE
                                      SYNTAX        SensorUnitsEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The base units.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 6 }

transferSwitchSensorDecimalDigits     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The number of digits displayed to the right of the decimal point
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 7 }

transferSwitchSensorAccuracy          OBJECT-TYPE
                                      SYNTAX        HundredthsOfAPercentage
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The accuracy: how close (in percent) the measurement is to the actual value
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 8 }

transferSwitchSensorResolution        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The resolution: the minimum difference between any two measured values
                                           The value of this OID variable should be scaled by 
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and 
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 9 }

transferSwitchSensorTolerance         OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The resolution: the  difference between a sensor value and the actual value
                                           The value of this OID variable should be scaled by 
                                           (transferSwitchSensorDecimalDigits + 1).  For example, if the value is 50 and 
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.05.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 10 }

transferSwitchSensorMaximum           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled maximum exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 11 }

transferSwitchSensorMinimum           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 12 }

transferSwitchSensorHysteresis        OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The hysteresis used for deassertions
                                           The value of this OID variable should be scaled by 
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 13 }

transferSwitchSensorStateChangeDelay  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The delay measured in samples before a state is asserted.
                                           If the value is zero, then the state is asserted as soon as
                                           it is detected; if it is non-zero, say n, then the assertion
                                           condition must exist for n+1 consecutive samples before the corresponding
                                           assertion event is reported.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 14 }

transferSwitchSensorLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 21 }

transferSwitchSensorLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 22 }

transferSwitchSensorUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 23 }

transferSwitchSensorUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is clamped if the scaled threshold exceeds 4294967295. It
                                           is undefined for sensors which can have negative readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 24 }

transferSwitchSensorEnabledThresholds OBJECT-TYPE
                                      SYNTAX        BITS {
                                                        lowerCritical(0),
                                                        lowerWarning(1),
                                                        upperWarning(2),
                                                        upperCritical(3)
                                                    }
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "A bit string  which indicates which thresholds are enabled.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 25 }

transferSwitchSensorSignedMaximum     OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The largest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 26 }

transferSwitchSensorSignedMinimum     OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The smallest possible reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value determines whether to use the signed or unsigned threshold
                                           and value columns: If the minimum is below zero the sensor can have
                                           negative readings and the signed columns should be used.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 27 }

transferSwitchSensorSignedLowerCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 28 }

transferSwitchSensorSignedLowerWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 29 }

transferSwitchSensorSignedUpperCriticalThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper critical threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 30 }

transferSwitchSensorSignedUpperWarningThreshold OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The upper warning threshold as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           The value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorConfigurationEntry 31 }



-- The PeripheralDevicePackageTable table contains information on the peripheral Device Packages connected to the PDU


peripheralDevicePackageTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF PeripheralDevicePackageEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of entries for the peripheral Device Packages connected to each PDU. The number of
                     entries is given by the value of peripheralDevicePackagesCount."
                ::= { externalSensors 5}

peripheralDevicePackageEntry     OBJECT-TYPE
                SYNTAX        PeripheralDevicePackageEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An  entry containing objects for a controller."
                INDEX         { pduId, peripheralDevicePackageId }
                ::= { peripheralDevicePackageTable 1 }

PeripheralDevicePackageEntryStruct ::= SEQUENCE { 
                                    peripheralDevicePackageId                           Integer32,
                                    peripheralDevicePackageSerialNumber                 DisplayString,
                                    peripheralDevicePackageModel                        DisplayString,
                                    peripheralDevicePackageFirmwareVersion              DisplayString,
                                    peripheralDevicePackageMinFirmwareVersion           DisplayString,
                                    peripheralDevicePackageFirmwareTimeStamp            Unsigned32,
                                    peripheralDevicePackagePosition	            	DisplayString,
                                    peripheralDevicePackageState   	            	DisplayString
                              }





peripheralDevicePackageId                  OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each peripheral device package."
                                      ::= { peripheralDevicePackageEntry 1 }


peripheralDevicePackageSerialNumber         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The peripheral device package  serial number."
                                      ::= { peripheralDevicePackageEntry 3 }

peripheralDevicePackageModel         OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The peripheral device package  model.
                                            Examples are DX-D2C6, DPX2-T1, DPX2-T1H1, DPX2-T2H1, DPX2-T3H1"
                                      ::= { peripheralDevicePackageEntry 4 }



peripheralDevicePackageFirmwareVersion           OBJECT-TYPE
                                          SYNTAX        DisplayString
                                          MAX-ACCESS    read-only
                                          STATUS        current
                                          DESCRIPTION
                                              "The peripheral device package firmware version."
                                      ::= { peripheralDevicePackageEntry 5 }


peripheralDevicePackageMinFirmwareVersion           OBJECT-TYPE
                                            SYNTAX        DisplayString
                                            MAX-ACCESS    read-only
                                            STATUS        current
                                            DESCRIPTION
                                              "The peripheral device package minimum firmware version.
                                               This field may be empty. If it is not empty, then it shall not be possible
                                               to downgrade the peripheral device firmware to a 
                                               version < minimum firmware version number."
                                      ::= { peripheralDevicePackageEntry 6 }


peripheralDevicePackageFirmwareTimeStamp        OBJECT-TYPE
                                         SYNTAX        Unsigned32
                                         MAX-ACCESS    read-only
                                         STATUS        current
                                         DESCRIPTION
                                          "The time when the peripheralDevicePackage firmware was updated in UNIX(epoch)time.
                                           It is measured in seconds relative to January 1, 1970 (midnight UTC/GMT), 
                                           i.e a value of 0 indicates January 1, 1970 (midnight UTC/GMT)."
                                      ::= { peripheralDevicePackageEntry 7 }

peripheralDevicePackagePosition OBJECT-TYPE
	 SYNTAX        DisplayString
	 MAX-ACCESS    read-only
	 STATUS        current
	 DESCRIPTION
	    "The position of the package.
	     The format is a semicolon separated list of Keyword:value pairs -
		 Keyword1:Value1;Keyword2:value2;...
	       Keyword can be one of the following:
		 ONBOARD,DEVICE-1WIREPORT;HUBPORT,CHAIN-POSITION
	       Examples
	       1) Onboard Sensor
			ONBOARD:CC1
	       2) Old sensor connected to device 1-wire port
			DEVICE-1WIREPORT:2
	       3) Old sensor connected to hub port
			DEVICE-1WIREPORT:2;HUBPORT:3
	       4) New style sensor connected to device 1-wire port
			DEVICE-1WIREPORT:2;CHAIN-POSITION:3
	       5) Old style sensor connected to end of new style sensor chain
			DEVICE-1WIREPORT:2;CHAIN-POSITION:7
	      "
	 ::= { peripheralDevicePackageEntry 8 }

peripheralDevicePackageState OBJECT-TYPE
	 SYNTAX        DisplayString
	 MAX-ACCESS    read-only
	 STATUS        current
	 DESCRIPTION
	    "The state of the package."
	 ::= { peripheralDevicePackageEntry 9 }


-- the log table

-- The logIndexTable

logIndexTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF LogIndexEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A table of log entries."
                ::= { logUnit 1 }

logIndexEntry     OBJECT-TYPE
                SYNTAX        LogIndexEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry in the log containing sensor data."
                INDEX         { pduId  }
                ::= { logIndexTable 1 }

LogIndexEntryStruct ::= SEQUENCE {
                                  oldestLogID                Integer32, 
                                  newestLogID                Integer32
                                 }




oldestLogID                     OBJECT-TYPE
                                   SYNTAX      Integer32
                                   MAX-ACCESS    read-only
                                   STATUS        current
                                   DESCRIPTION
                                       "The index of the oldest data in the buffer for this PDU."
                                   ::= { logIndexEntry 2 }

newestLogID                     OBJECT-TYPE
                                   SYNTAX      Integer32
                                   MAX-ACCESS    read-only
                                   STATUS        current
                                   DESCRIPTION
                                       "The index of the newest data in the buffer for this PDU."
                                   ::= { logIndexEntry 3 }



-- The logTimeStampTable

logTimeStampTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF LogTimeStampEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of entries containing the timestamps of the entries in the log."
                ::= { logUnit 2 }

logTimeStampEntry     OBJECT-TYPE
                SYNTAX        LogTimeStampEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing the timestamp for log entries."
                INDEX         { pduId, logIndex  }
                ::= { logTimeStampTable 1 }

LogTimeStampEntryStruct ::= SEQUENCE {logIndex                 Integer32,
                                      logTimeStamp               Unsigned32
                                     }

logIndex                      OBJECT-TYPE
                                      SYNTAX        Integer32(1..256)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A unique value for each entry in the log. Its value
                                           ranges between 1 and the value of logSize."
                                      ::= { logTimeStampEntry 1 }


logTimeStamp                OBJECT-TYPE
                                   SYNTAX      Unsigned32
                                   MAX-ACCESS    read-only
                                   STATUS        current
                                   DESCRIPTION
                                       "The time when the data was collected. It is measured in seconds relative to
                                        January 1, 1970 (midnight UTC/GMT), i.e a value of 0 indicates
                                        January 1, 1970 (midnight UTC/GMT)."
                                   ::= { logTimeStampEntry 2 }




-- The unitSensorLogTable

unitSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF UnitSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of unit sensor entries in the log."
                ::= { logUnit 3 }

unitSensorLogEntry     OBJECT-TYPE
                SYNTAX        UnitSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an unit sensor."
                INDEX         {  pduId, sensorType, logIndex }
                ::= { unitSensorLogTable 1 }

UnitSensorLogEntryStruct ::= SEQUENCE {
                                    logUnitSensorDataAvailable    TruthValue,
                                    logUnitSensorState            SensorStateEnumeration,
                                    logUnitSensorAvgValue         Unsigned32,
                                    logUnitSensorMaxValue         Unsigned32,
                                    logUnitSensorMinValue         Unsigned32,
                                    logUnitSensorSignedAvgValue   Integer32,
                                    logUnitSensorSignedMaxValue   Integer32,
                                    logUnitSensorSignedMinValue   Integer32
                                    }

logUnitSensorDataAvailable            OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { unitSensorLogEntry 2 }

logUnitSensorState                    OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { unitSensorLogEntry 3 }

logUnitSensorAvgValue                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { unitSensorLogEntry 4 }

logUnitSensorMaxValue                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { unitSensorLogEntry 5 }

logUnitSensorMinValue                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { unitSensorLogEntry 6 }

logUnitSensorSignedAvgValue           OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { unitSensorLogEntry 7 }

logUnitSensorSignedMaxValue           OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { unitSensorLogEntry 8 }

logUnitSensorSignedMinValue           OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { unitSensorLogEntry 9 }



-- The inletSensorLogTable

 

inletSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of inlet sensor entries. The number of
                     entries is given by the value of inletCount for the PDU."
                ::= { logInlet 3 }

inletSensorLogEntry     OBJECT-TYPE
                SYNTAX        InletSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an inlet sensor."
                INDEX         { pduId, inletId, sensorType, logIndex  }
                ::= { inletSensorLogTable 1 }

InletSensorLogEntryStruct ::= SEQUENCE {
                                    logInletSensorDataAvailable   TruthValue,
                                    logInletSensorState           SensorStateEnumeration,
                                    logInletSensorAvgValue        Unsigned32,
                                    logInletSensorMaxValue        Unsigned32,
                                    logInletSensorMinValue        Unsigned32,
                                    logInletSensorSignedAvgValue  Integer32,
                                    logInletSensorSignedMaxValue  Integer32,
                                    logInletSensorSignedMinValue  Integer32
                                    }

logInletSensorDataAvailable           OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { inletSensorLogEntry 2 }

logInletSensorState                   OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { inletSensorLogEntry 3 }

logInletSensorAvgValue                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { inletSensorLogEntry 4 }

logInletSensorMaxValue                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { inletSensorLogEntry 5 }

logInletSensorMinValue                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { inletSensorLogEntry 6 }

logInletSensorSignedAvgValue          OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { inletSensorLogEntry 7 }

logInletSensorSignedMaxValue          OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { inletSensorLogEntry 8 }

logInletSensorSignedMinValue          OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { inletSensorLogEntry 9 }


-- The inletPoleSensorLogTable

inletPoleSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletPoleSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of inletPole sensor entries. The number of
                     entries is given by the value of inletPoleCount for the inlet."
                ::= { logInlet 4 }

inletPoleSensorLogEntry     OBJECT-TYPE
                SYNTAX        InletPoleSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an inletPole sensor."
                INDEX         { pduId,inletId, inletPoleIndex,sensorType,logIndex  }
                ::= { inletPoleSensorLogTable 1 }

InletPoleSensorLogEntryStruct ::= SEQUENCE {
                                    logInletPoleSensorDataAvailable   TruthValue,
                                    logInletPoleSensorState           SensorStateEnumeration,
                                    logInletPoleSensorAvgValue        Unsigned32,
                                    logInletPoleSensorMaxValue        Unsigned32,
                                    logInletPoleSensorMinValue        Unsigned32,
                                    logInletPoleSensorSignedAvgValue  Integer32,
                                    logInletPoleSensorSignedMaxValue  Integer32,
                                    logInletPoleSensorSignedMinValue  Integer32
                                    }

logInletPoleSensorDataAvailable       OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { inletPoleSensorLogEntry 2 }


logInletPoleSensorState               OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { inletPoleSensorLogEntry 3 }

logInletPoleSensorAvgValue            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { inletPoleSensorLogEntry 4 }

logInletPoleSensorMaxValue            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { inletPoleSensorLogEntry 5 }

logInletPoleSensorMinValue            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { inletPoleSensorLogEntry 6 }

logInletPoleSensorSignedAvgValue      OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { inletPoleSensorLogEntry 7 }

logInletPoleSensorSignedMaxValue      OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { inletPoleSensorLogEntry 8 }

logInletPoleSensorSignedMinValue      OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { inletPoleSensorLogEntry 9 }



-- The outletSensorLogTable

outletSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outlet sensor entries. The number of
                     entries is given by the value of outletCount for the PDU."
                ::= { logOutlet 3 }

outletSensorLogEntry     OBJECT-TYPE
                SYNTAX        OutletSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an outlet sensor."
                INDEX         { pduId, outletId, sensorType,logIndex  }
                ::= { outletSensorLogTable 1 }

OutletSensorLogEntryStruct ::= SEQUENCE {
                                    logOutletSensorDataAvailable   TruthValue,
                                    logOutletSensorState           SensorStateEnumeration,
                                    logOutletSensorAvgValue        Unsigned32,
                                    logOutletSensorMaxValue        Unsigned32,
                                    logOutletSensorMinValue        Unsigned32,
                                    logOutletSensorSignedAvgValue  Integer32,
                                    logOutletSensorSignedMaxValue  Integer32,
                                    logOutletSensorSignedMinValue  Integer32
                                    }

logOutletSensorDataAvailable          OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { outletSensorLogEntry 2 }

logOutletSensorState                  OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { outletSensorLogEntry 3 }

logOutletSensorAvgValue               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { outletSensorLogEntry 4 }

logOutletSensorMaxValue               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { outletSensorLogEntry 5 }

logOutletSensorMinValue               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { outletSensorLogEntry 6 }

logOutletSensorSignedAvgValue         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { outletSensorLogEntry 7 }

logOutletSensorSignedMaxValue         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { outletSensorLogEntry 8 }

logOutletSensorSignedMinValue         OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { outletSensorLogEntry 9 }



-- The outletPoleSensorLogTable

outletPoleSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletPoleSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outletPole sensor entries. The number of
                     entries is given by the value of outletPoleCount for the outlet."
                ::= { logOutlet 4 }

outletPoleSensorLogEntry    OBJECT-TYPE
                SYNTAX        OutletPoleSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an outletPole sensor."
                INDEX         { pduId, outletId, outletPoleIndex,sensorType,logIndex  }
                ::= { outletPoleSensorLogTable 1 }

OutletPoleSensorLogEntryStruct ::= SEQUENCE {
                                    logOutletPoleSensorDataAvailable   TruthValue,
                                    logOutletPoleSensorState           SensorStateEnumeration,
                                    logOutletPoleSensorAvgValue        Unsigned32,
                                    logOutletPoleSensorMaxValue        Unsigned32,
                                    logOutletPoleSensorMinValue        Unsigned32,
                                    logOutletPoleSensorSignedAvgValue  Integer32,
                                    logOutletPoleSensorSignedMaxValue  Integer32,
                                    logOutletPoleSensorSignedMinValue  Integer32
                                    }

logOutletPoleSensorDataAvailable      OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { outletPoleSensorLogEntry 2 }

logOutletPoleSensorState              OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { outletPoleSensorLogEntry 3 }

logOutletPoleSensorAvgValue           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { outletPoleSensorLogEntry 4 }

logOutletPoleSensorMaxValue           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { outletPoleSensorLogEntry 5 }

logOutletPoleSensorMinValue           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { outletPoleSensorLogEntry 6 }

logOutletPoleSensorSignedAvgValue     OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { outletPoleSensorLogEntry 7 }

logOutletPoleSensorSignedMaxValue     OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { outletPoleSensorLogEntry 8 }

logOutletPoleSensorSignedMinValue     OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { outletPoleSensorLogEntry 9 }



-- The overCurrentProtectorSensorLogTable

overCurrentProtectorSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OverCurrentProtectorSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of overCurrentProtector sensor entries. The number of
                     entries is given by the value of overCurrentProtectorCount for the PDU."
                ::= { logOverCurrentProtector 3 }

overCurrentProtectorSensorLogEntry     OBJECT-TYPE
                SYNTAX        OverCurrentProtectorSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an overCurrentProtector sensor."
                INDEX         { pduId, overCurrentProtectorIndex, sensorType, logIndex  }
                ::= { overCurrentProtectorSensorLogTable 1 }

OverCurrentProtectorSensorLogEntryStruct ::= SEQUENCE {
                                    logOverCurrentProtectorSensorDataAvailable   TruthValue,
                                    logOverCurrentProtectorSensorState           SensorStateEnumeration,
                                    logOverCurrentProtectorSensorAvgValue        Unsigned32,
                                    logOverCurrentProtectorSensorMaxValue        Unsigned32,
                                    logOverCurrentProtectorSensorMinValue        Unsigned32,
                                    logOverCurrentProtectorSensorSignedAvgValue  Integer32,
                                    logOverCurrentProtectorSensorSignedMaxValue  Integer32,
                                    logOverCurrentProtectorSensorSignedMinValue  Integer32
                                    }

logOverCurrentProtectorSensorDataAvailable OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { overCurrentProtectorSensorLogEntry 2 }

logOverCurrentProtectorSensorState    OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { overCurrentProtectorSensorLogEntry 3 }

logOverCurrentProtectorSensorAvgValue OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { overCurrentProtectorSensorLogEntry 4 }

logOverCurrentProtectorSensorMaxValue OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { overCurrentProtectorSensorLogEntry 5 }

logOverCurrentProtectorSensorMinValue OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { overCurrentProtectorSensorLogEntry 6 }

logOverCurrentProtectorSensorSignedAvgValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { overCurrentProtectorSensorLogEntry 7 }

logOverCurrentProtectorSensorSignedMaxValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { overCurrentProtectorSensorLogEntry 8 }

logOverCurrentProtectorSensorSignedMinValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits.  For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { overCurrentProtectorSensorLogEntry 9 }



-- The externalSensorLogTable

externalSensorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ExternalSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of external sensor entries. The number of
                     entries is given by the value of externalSensorCount for the PDU."
                ::= { logExternalSensor 3 }

externalSensorLogEntry     OBJECT-TYPE
                SYNTAX        ExternalSensorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing log objects for an external sensor."
                INDEX         { pduId, sensorID, logIndex  }
                ::= { externalSensorLogTable 1 }

ExternalSensorLogEntryStruct ::= SEQUENCE {
                                    logExternalSensorDataAvailable   TruthValue, 
                                    logExternalSensorState           SensorStateEnumeration,
                                    logExternalSensorAvgValue        Integer32,
                                    logExternalSensorMaxValue        Integer32,
                                    logExternalSensorMinValue        Integer32
                                    }

logExternalSensorDataAvailable            OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { externalSensorLogEntry 2 }

logExternalSensorState                   OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { externalSensorLogEntry 3 }

logExternalSensorAvgValue               OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading average value.
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { externalSensorLogEntry 4 }

logExternalSensorMaxValue               OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading maximum value.
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { externalSensorLogEntry 5 }

logExternalSensorMinValue               OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading minimum value.
                                           The value of this OID variable should be scaled by 
                                           externalSensorDecimalDigits.  For example, if the value is 1 and 
                                           externalSensorDecimalDigits is 2, then actual value is 0.01."
                                      ::= { externalSensorLogEntry 6 }


-- The wireSensorLogTable

wireSensorLogTable                    OBJECT-TYPE
                                      SYNTAX        SEQUENCE OF WireSensorLogEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A list of wire sensor entries. The number of
                                           entries is given by the value of wireCount for the PDU."
                                      ::= { logWire 3 }

wireSensorLogEntry                    OBJECT-TYPE
                                      SYNTAX        WireSensorLogEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "An entry containing log objects for a wire sensor."
                                      INDEX         { pduId, wireId, sensorType, logIndex  }
                                      ::= { wireSensorLogTable 1 }

WireSensorLogEntryStruct ::= SEQUENCE {
                                 logWireSensorDataAvailable   TruthValue,
                                 logWireSensorState           SensorStateEnumeration,
                                 logWireSensorAvgValue        Unsigned32,
                                 logWireSensorMaxValue        Unsigned32,
                                 logWireSensorMinValue        Unsigned32
                             }

logWireSensorDataAvailable            OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { wireSensorLogEntry 2 }

logWireSensorState                    OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { wireSensorLogEntry 3 }

logWireSensorAvgValue                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The sensor reading average value.
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits. For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the value exceeds 4294967295"
                                      ::= { wireSensorLogEntry 4 }

logWireSensorMaxValue                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The sensor reading maximum value.
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits. For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the value exceeds 4294967295"
                                      ::= { wireSensorLogEntry 5 }

logWireSensorMinValue                 OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The sensor reading minimum value.
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits. For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the value exceeds 4294967295."
                                      ::= { wireSensorLogEntry 6 }






-- The transferSwitchSensorLogTable

transferSwitchSensorLogTable        OBJECT-TYPE
                                      SYNTAX        SEQUENCE OF TransferSwitchSensorLogEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A list of Transfer Switch sensor entries. The number of
                                           entries is given by the value of transferSwitchCount for the PDU."
                                      ::= { logTransferSwitch 3 }

transferSwitchSensorLogEntry        OBJECT-TYPE
                                      SYNTAX        TransferSwitchSensorLogEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "An entry containing log objects for a transfer switch sensor."
                                      INDEX         { pduId, transferSwitchId, sensorType, logIndex  }
                                      ::= { transferSwitchSensorLogTable 1 }

TransferSwitchSensorLogEntryStruct ::= SEQUENCE {
                                 logTransferSwitchSensorDataAvailable   TruthValue,
                                 logTransferSwitchSensorState           SensorStateEnumeration,
                                 logTransferSwitchSensorAvgValue        Unsigned32,
                                 logTransferSwitchSensorMaxValue        Unsigned32,
                                 logTransferSwitchSensorMinValue        Unsigned32,
                                 logTransferSwitchSensorSignedAvgValue  Integer32,
                                 logTransferSwitchSensorSignedMaxValue  Integer32,
                                 logTransferSwitchSensorSignedMinValue  Integer32
                             }

logTransferSwitchSensorDataAvailable  OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is data available for this sensor during this measurement period?"
                                      ::= { transferSwitchSensorLogEntry 2 }

logTransferSwitchSensorState          OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { transferSwitchSensorLogEntry 3 }

logTransferSwitchSensorAvgValue       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { transferSwitchSensorLogEntry 4 }

logTransferSwitchSensorMaxValue       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { transferSwitchSensorLogEntry 5 }

logTransferSwitchSensorMinValue       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings."
                                      ::= { transferSwitchSensorLogEntry 6 }

logTransferSwitchSensorSignedAvgValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The average sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { transferSwitchSensorLogEntry 7 }

logTransferSwitchSensorSignedMaxValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { transferSwitchSensorLogEntry 8 }

logTransferSwitchSensorSignedMinValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The minimum sensor reading for the log period as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647)."
                                      ::= { transferSwitchSensorLogEntry 9 }



-- the Measurements table



-- The unitSensorMeasurementsTable

unitSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF UnitSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of unit sensor entries."
                ::= { measurementsUnit 3 }

unitSensorMeasurementsEntry     OBJECT-TYPE
                SYNTAX        UnitSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an unit sensor."
                INDEX         {  pduId, sensorType  }
                ::= { unitSensorMeasurementsTable 1 }

UnitSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsUnitSensorIsAvailable      TruthValue,
                                    measurementsUnitSensorState            SensorStateEnumeration,
                                    measurementsUnitSensorValue            Unsigned32,
                                    measurementsUnitSensorTimeStamp        Unsigned32,
                                    measurementsUnitSensorSignedValue      Integer32
                                    }



measurementsUnitSensorIsAvailable            OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { unitSensorMeasurementsEntry 2 }



measurementsUnitSensorState                  OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { unitSensorMeasurementsEntry 3 }

measurementsUnitSensorValue           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. power supply status sensors."
                                      ::= { unitSensorMeasurementsEntry 4 }

measurementsUnitSensorTimeStamp       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { unitSensorMeasurementsEntry 5 }

measurementsUnitSensorSignedValue     OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           unitSensorDecimalDigits.  For example, if the value is 1 and
                                           unitSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. power supply status sensors."
                                      ::= { unitSensorMeasurementsEntry 6 }



-- The inletSensorMeasurementsTable

inletSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of inlet sensor entries. The number of
                     entries is given by the value of inletCount for the PDU."
                ::= { measurementsInlet 3 }

inletSensorMeasurementsEntry     OBJECT-TYPE
                SYNTAX        InletSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an inlet sensor."
                INDEX         { pduId, inletId, sensorType  }
                ::= { inletSensorMeasurementsTable 1 }

InletSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsInletSensorIsAvailable      TruthValue,
                                    measurementsInletSensorState            SensorStateEnumeration,
                                    measurementsInletSensorValue            Unsigned32,
                                    measurementsInletSensorTimeStamp        Unsigned32,
                                    measurementsInletSensorSignedValue      Integer32
                                    }

measurementsInletSensorIsAvailable    OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { inletSensorMeasurementsEntry 2 }


measurementsInletSensorState          OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { inletSensorMeasurementsEntry 3 }

measurementsInletSensorValue          OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorMeasurementsEntry 4 }

measurementsInletSensorTimeStamp      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { inletSensorMeasurementsEntry 5 }

measurementsInletSensorSignedValue    OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletSensorDecimalDigits.  For example, if the value is 1 and
                                           inletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. surge protector status sensors."
                                      ::= { inletSensorMeasurementsEntry 6 }



-- The inletPoleSensorMeasurementsTable

inletPoleSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF InletPoleSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of inletPole sensor entries. The number of
                     entries is given by the value of inletPoleCount for the inlet."
                ::= { measurementsInlet 4 }

inletPoleSensorMeasurementsEntry     OBJECT-TYPE
                SYNTAX        InletPoleSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an inletPole sensor."
                INDEX         { pduId, inletId, inletPoleIndex,sensorType  }
                ::= { inletPoleSensorMeasurementsTable 1 }

InletPoleSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsInletPoleSensorIsAvailable      TruthValue,
                                    measurementsInletPoleSensorState            SensorStateEnumeration,
                                    measurementsInletPoleSensorValue            Unsigned32,
                                    measurementsInletPoleSensorTimeStamp        Unsigned32,
                                    measurementsInletPoleSensorSignedValue      Integer32
                                    }


measurementsInletPoleSensorIsAvailable OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { inletPoleSensorMeasurementsEntry 2 }

measurementsInletPoleSensorState      OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { inletPoleSensorMeasurementsEntry 3 }

measurementsInletPoleSensorValue      OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorMeasurementsEntry 4 }

measurementsInletPoleSensorTimeStamp  OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { inletPoleSensorMeasurementsEntry 5 }

measurementsInletPoleSensorSignedValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           inletPoleSensorDecimalDigits.  For example, if the value is 1 and
                                           inletPoleSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { inletPoleSensorMeasurementsEntry 6 }



-- The outletSensorMeasurementsTable

outletSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outlet sensor entries. The number of
                     entries is given by the value of outletCount for the PDU."
                ::= { measurementsOutlet 3 }

outletSensorMeasurementsEntry     OBJECT-TYPE
                SYNTAX        OutletSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an outlet sensor."
                INDEX         { pduId, outletId, sensorType  }
                ::= { outletSensorMeasurementsTable 1 }

OutletSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsOutletSensorIsAvailable      TruthValue,
                                    measurementsOutletSensorState            SensorStateEnumeration,
                                    measurementsOutletSensorValue            Unsigned32,
                                    measurementsOutletSensorTimeStamp        Unsigned32,
                                    measurementsOutletSensorSignedValue      Integer32
                                    }

measurementsOutletSensorIsAvailable   OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { outletSensorMeasurementsEntry 2 }

measurementsOutletSensorState         OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { outletSensorMeasurementsEntry 3 }

measurementsOutletSensorValue         OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorMeasurementsEntry 4 }

measurementsOutletSensorTimeStamp     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { outletSensorMeasurementsEntry 5 }

measurementsOutletSensorSignedValue   OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletSensorDecimalDigits.  For example, if the value is 1 and
                                           outletSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. outlet state sensors."
                                      ::= { outletSensorMeasurementsEntry 6 }



-- The outletPoleSensorMeasurementsTable

outletPoleSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletPoleSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outletPole sensor entries. The number of
                     entries is given by the value of outletPoletCount for the outlet."
                ::= { measurementsOutlet 4 }

outletPoleSensorMeasurementsEntry    OBJECT-TYPE
                SYNTAX        OutletPoleSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an outletPole sensor."
                INDEX         { pduId,  outletId, outletPoleIndex,sensorType  }
                ::= { outletPoleSensorMeasurementsTable 1 }

OutletPoleSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsOutletPoleSensorIsAvailable      TruthValue,
                                    measurementsOutletPoleSensorState            SensorStateEnumeration,
                                    measurementsOutletPoleSensorValue            Unsigned32,
                                    measurementsOutletPoleSensorTimeStamp        Unsigned32,
                                    measurementsOutletPoleSensorSignedValue      Integer32
                                    }

measurementsOutletPoleSensorIsAvailable OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { outletPoleSensorMeasurementsEntry 2 }

measurementsOutletPoleSensorState     OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { outletPoleSensorMeasurementsEntry 3 }

measurementsOutletPoleSensorValue     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 50 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.05.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorMeasurementsEntry 4 }

measurementsOutletPoleSensorTimeStamp OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { outletPoleSensorMeasurementsEntry 5 }

measurementsOutletPoleSensorSignedValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           outletPoleSensorDecimalDigits.  For example, if the value is 50 and
                                           outletPoleSensorDecimalDigits is 2, then actual value is 0.05.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { outletPoleSensorMeasurementsEntry 6 }



-- The overCurrentProtectorSensorMeasurementsTable

overCurrentProtectorSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OverCurrentProtectorSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of overCurrentProtector sensor entries. The number of
                     entries is given by the value of overCurrentProtectorCount for the PDU."
                ::= { measurementsOverCurrentProtector 3 }

overCurrentProtectorSensorMeasurementsEntry     OBJECT-TYPE
                SYNTAX        OverCurrentProtectorSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an overCurrentProtector."
                INDEX         { pduId, overCurrentProtectorIndex, sensorType  }
                ::= { overCurrentProtectorSensorMeasurementsTable 1 }

OverCurrentProtectorSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsOverCurrentProtectorSensorIsAvailable      TruthValue,
                                    measurementsOverCurrentProtectorSensorState           SensorStateEnumeration,
                                    measurementsOverCurrentProtectorSensorValue            Unsigned32,
                                    measurementsOverCurrentProtectorSensorTimeStamp        Unsigned32,
                                    measurementsOverCurrentProtectorSensorSignedValue      Integer32
                                    }


measurementsOverCurrentProtectorSensorIsAvailable OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { overCurrentProtectorSensorMeasurementsEntry 2 }

measurementsOverCurrentProtectorSensorState OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { overCurrentProtectorSensorMeasurementsEntry 3 }

measurementsOverCurrentProtectorSensorValue OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorMeasurementsEntry 4 }

measurementsOverCurrentProtectorSensorTimeStamp OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { overCurrentProtectorSensorMeasurementsEntry 5 }

measurementsOverCurrentProtectorSensorSignedValue OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           overCurrentProtectorSensorDecimalDigits. For example, if the value is 1 and
                                           overCurrentProtectorSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. trip sensors."
                                      ::= { overCurrentProtectorSensorMeasurementsEntry 6 }



-- The externalSensorMeasurementsTable

externalSensorMeasurementsTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ExternalSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of external sensor entries. The number of
                     entries is given by the value of externalSensorCount for the PDU."
                ::= { measurementsExternalSensor 3 }

externalSensorMeasurementsEntry     OBJECT-TYPE
                SYNTAX        ExternalSensorMeasurementsEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing measurement objects for an external sensor."
                INDEX         { pduId, sensorID  }
                ::= { externalSensorMeasurementsTable 1 }

ExternalSensorMeasurementsEntryStruct ::= SEQUENCE {
                                    measurementsExternalSensorIsAvailable      TruthValue,
                                    measurementsExternalSensorState           SensorStateEnumeration,
                                    measurementsExternalSensorValue           Integer32,
                                    measurementsExternalSensorTimeStamp        Unsigned32
                                    }


measurementsExternalSensorIsAvailable            OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { externalSensorMeasurementsEntry 2 }


measurementsExternalSensorState                   OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { externalSensorMeasurementsEntry 3 }

measurementsExternalSensorValue               OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           externalSensorDecimalDigits.  For example, if the value is 1 and
                                           externalSensorDecimalDigits is 2, then actual value is 0.01.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. contact closure or smoke detection sensors."
                                      ::= { externalSensorMeasurementsEntry 4 }

measurementsExternalSensorTimeStamp               OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading timestamp."
                                      ::= { externalSensorMeasurementsEntry 5 }



-- The wireSensorMeasurementsTable

wireSensorMeasurementsTable           OBJECT-TYPE
                                      SYNTAX        SEQUENCE OF WireSensorMeasurementsEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "A list of wire sensor entries. The number of
                                           entries is given by the value of wireCount for the PDU."
                                      ::= { measurementsWire 3 }

wireSensorMeasurementsEntry           OBJECT-TYPE
                                      SYNTAX        WireSensorMeasurementsEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "An entry containing measurement objects for a wire."
                                      INDEX         { pduId, wireId, sensorType }
                                      ::= { wireSensorMeasurementsTable 1 }

WireSensorMeasurementsEntryStruct ::= SEQUENCE {
                                          measurementsWireSensorIsAvailable      TruthValue,
                                          measurementsWireSensorState            SensorStateEnumeration,
                                          measurementsWireSensorValue            Unsigned32,
                                          measurementsWireSensorTimeStamp        Unsigned32
                                      }

measurementsWireSensorIsAvailable     OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { wireSensorMeasurementsEntry 2 }

measurementsWireSensorState           OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { wireSensorMeasurementsEntry 3 }

measurementsWireSensorValue           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The sensor value.
                                           The value of this OID variable should be scaled by
                                           wireSensorDecimalDigits. For example, if the value is 1 and
                                           wireSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the value exceeds 4294967295
                                           This parameter does not apply to sensors without numerical reading."
                                      ::= { wireSensorMeasurementsEntry 4 }

measurementsWireSensorTimeStamp       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        deprecated
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { wireSensorMeasurementsEntry 5 }






-- The transfer switch SensorMeasurementsTable

transferSwitchSensorMeasurementsTable           OBJECT-TYPE
                                      SYNTAX        SEQUENCE OF TransferSwitchSensorMeasurementsEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "A list of transfer switch sensor entries. The number of
                                           entries is given by the value of transferSwitchCount for the PDU."
                                      ::= { measurementsTransferSwitch 3 }

transferSwitchSensorMeasurementsEntry           OBJECT-TYPE
                                      SYNTAX        TransferSwitchSensorMeasurementsEntryStruct
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "An entry containing measurement objects for a transfer switch."
                                      INDEX         { pduId, transferSwitchId, sensorType }
                                      ::= { transferSwitchSensorMeasurementsTable 1 }

TransferSwitchSensorMeasurementsEntryStruct ::= SEQUENCE {
                                          measurementsTransferSwitchSensorIsAvailable      TruthValue,
                                          measurementsTransferSwitchSensorState            SensorStateEnumeration,
                                          measurementsTransferSwitchSensorValue            Unsigned32,
                                          measurementsTransferSwitchSensorTimeStamp        Unsigned32,
                                          measurementsTransferSwitchSensorSignedValue      Integer32
                                      }

measurementsTransferSwitchSensorIsAvailable     OBJECT-TYPE
                                      SYNTAX        TruthValue
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Is the sensor available?"
                                      ::= { transferSwitchSensorMeasurementsEntry 2 }

measurementsTransferSwitchSensorState           OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor state."
                                      ::= { transferSwitchSensorMeasurementsEntry 3 }

measurementsTransferSwitchSensorValue OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as an unsigned integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value will wrap around if the scaled sensor reading exceeds
                                           4294967295. It is undefined for sensors which can have negative
                                           readings.
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorMeasurementsEntry 4 }

measurementsTransferSwitchSensorTimeStamp       OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The timestamp."
                                      ::= { transferSwitchSensorMeasurementsEntry 5 }

measurementsTransferSwitchSensorSignedValue           OBJECT-TYPE
                                      SYNTAX        Integer32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The sensor reading as a signed integer.
                                           The value of this OID variable should be scaled by
                                           transferSwitchSensorDecimalDigits.  For example, if the value is 1 and
                                           transferSwitchSensorDecimalDigits is 2, then actual value is 0.01.
                                           This value is undefined for sensors whose range exceeds the
                                           Integer32 range (-2147483648 .. 2147483647).
                                           This parameter does not apply to sensors without numerical reading,
                                           e.g. operational state or switch fault sensors."
                                      ::= { transferSwitchSensorMeasurementsEntry 6 }



-- the OutletSwitchControlTable

-- The OutletSwitchControl table implements switching of outlets.


outletSwitchControlTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF OutletSwitchControlEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of outlets for a PDU. The number of
                     entries is given by the value of outletCount."
                ::= { outletControl  2 }

outletSwitchControlEntry     OBJECT-TYPE
                SYNTAX        OutletSwitchControlEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry for implementing switching operations on an outlet."
                INDEX         { pduId, outletId }
                ::= { outletSwitchControlTable 1 }

OutletSwitchControlEntryStruct ::= SEQUENCE { 
                                    switchingOperation               OutletSwitchingOperationsEnumeration,
                                    outletSwitchingState             SensorStateEnumeration,
                                    outletSwitchingTimeStamp         Unsigned32
                              }



switchingOperation                    OBJECT-TYPE
                                      SYNTAX        OutletSwitchingOperationsEnumeration
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The switching operation."
                                      ::= { outletSwitchControlEntry 2 }


outletSwitchingState                   OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The outlet state at present"
                                      ::= { outletSwitchControlEntry 3 }


outletSwitchingTimeStamp                OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The  timestamp indicating when the outlet was last switched"
                                      ::= { outletSwitchControlEntry 4 }


-- the transferSwitchControlTable

-- The TransferSwitchControl table implements control operations of transfer switches.


transferSwitchControlTable     OBJECT-TYPE
                               SYNTAX        SEQUENCE OF TransferSwitchControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "A list of transfer switches for a PDU. The number of
                                    entries is given by the value of transferSwitchCount."
                               ::= { transferSwitchControl 1 }

transferSwitchControlEntry     OBJECT-TYPE
                               SYNTAX        TransferSwitchControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "An entry for implementing switching operations on a transfer switch."
                               INDEX         { pduId, transferSwitchId }
                               ::= { transferSwitchControlTable 1 }

TransferSwitchControlEntryStruct ::= SEQUENCE {
                                         transferSwitchActiveInlet      Integer32,
                                         transferSwitchTransferToInlet  Integer32,
                                         transferSwitchAlarmOverride    TruthValue,
                                         transferSwitchLastTransferReason TransferSwitchTransferReasonEnumeration
                                    }

transferSwitchActiveInlet      OBJECT-TYPE
                               SYNTAX        Integer32(1..64)
                               MAX-ACCESS    read-only
                               STATUS        current
                               DESCRIPTION
                                   "The index of the currently active inlet."
                               ::= { transferSwitchControlEntry 1 }

transferSwitchTransferToInlet  OBJECT-TYPE
                               SYNTAX        Integer32(1..64)
                               MAX-ACCESS    read-write 
                               STATUS        current
                               DESCRIPTION
                                   "Select the active inlet. If the new inlet is available, it will become
                                    both active and preferred, otherwise an inconsistentValue error will
                                    be returned.
                                    By default the switching operation will fail if the phase difference
                                    between the inlets is too large. In this case the switch can be forced
                                    by writing transferSwitchAlarmOverride as True in the same request.
                                    This variable will always read as 0."
                               ::= { transferSwitchControlEntry 2 }

transferSwitchAlarmOverride    OBJECT-TYPE
                               SYNTAX        TruthValue
                               MAX-ACCESS    read-write
                               STATUS        current
                               DESCRIPTION
                                   "Force transfer even if the phase difference between the inlets is too
                                    large.
                                    This may only be written together with transferSwitchTransferToInlet,
                                    otherwise an inconsistentValue error will be returned. Always reads as
                                    false."
                               ::= { transferSwitchControlEntry 3 }

transferSwitchLastTransferReason OBJECT-TYPE
                               SYNTAX        TransferSwitchTransferReasonEnumeration
                               MAX-ACCESS    read-only
                               STATUS        current
                               DESCRIPTION
                                   "The reason for the most recent transfer"
                               ::= { transferSwitchControlEntry 4 }


 -- the actuatorControlTable

-- The actuatorControl table implements user-initiated state changes for an actuator.


actuatorControlTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ActuatorControlEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of actuators for a PDU. "
                ::= { actuatorControl  2 }

actuatorControlEntry     OBJECT-TYPE
                SYNTAX        ActuatorControlEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry for implementing user-initiated state changes for an actuator."
                INDEX         { pduId, sensorID }
                ::= { actuatorControlTable 1 }

ActuatorControlEntryStruct ::= SEQUENCE { 
                                    actuatorState                    SensorStateEnumeration
                              }




actuatorState                      OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The actuator state.
                                           A Get operation retrieves the state of the actuator.
                                           A Set operation changes the stae of the sensor.
                                               The valid states for set operations are on and Off.
                                               Attempting to set the state to any other value will generate an error. "
                                      ::= { actuatorControlEntry 2 }


-- the RCM (Residual Control Monitor) Self Test Table

-- The rcmSelfTest table implements self test of the RCM.


rcmSelfTestTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF RcmSelfTestEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of RCMs. "
                ::= { rcmControl  2 }

rcmSelfTestEntry     OBJECT-TYPE
                SYNTAX        RcmSelfTestEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry for implementing self test of an RCM."
                INDEX         { pduId, inletId }
                ::= { rcmSelfTestTable 1 }

RcmSelfTestEntryStruct ::= SEQUENCE { 
                                    rcmState                    SensorStateEnumeration
                              }




rcmState                      OBJECT-TYPE
                                      SYNTAX        SensorStateEnumeration
                                      MAX-ACCESS    read-write
                                      STATUS        current
                                      DESCRIPTION
                                          "The rcm state.
                                           A Get operation retrieves the state of the RCM State Sensor.
                                           A Set operation changes the state of the sensor.
                                               The valid state for set operations is selfTest.
                                               When rcmState is set to selfTest, self test of the RCM starts.
                                               Attempting to set the state to any other value will generate an error.
                                               If the current state is selfTest, then an attempt to set the value to selfTest
                                                 will be ignored. 
                                                                                  
                                          "
                                      ::= { rcmSelfTestEntry 2 }


-- the InletSensorControlTable

-- The InletSensorControl table implements operations on inlet sensors

inletSensorControlTable        OBJECT-TYPE
                               SYNTAX        SEQUENCE OF InletSensorControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "A list of control entries for the inlet sensors of a PDU. The set
                                    of valid indexes is defined by the value of inletCount and the
                                    inletDeviceCapabilities entry for the selected inlet."
                               ::= { inletSensorControl 1 }

inletSensorControlEntry        OBJECT-TYPE
                               SYNTAX        InletSensorControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "An entry used for controlling an inlet sensor."
                               INDEX         { pduId, inletId, sensorType }
                               ::= { inletSensorControlTable 1 }

InletSensorControlEntryStruct ::= SEQUENCE {
                                      inletSensorResetValue Integer32
                                  }

inletSensorResetValue          OBJECT-TYPE
                               SYNTAX        Integer32
                               MAX-ACCESS    read-write
                               STATUS        current
                               DESCRIPTION
                                   "Writing to this variable sets a new value for the addressed sensor. Only
                                    accumulating sensors (e.g. energy counters) can be reset, and currently
                                    the only supported value is 0. Writing any other value returns an error.
                                    This variable will always read as 0."
                               ::= { inletSensorControlEntry 1 }


-- the OutletSensorControlTable

-- The OutletSensorControl table implements operations on outlet sensors

outletSensorControlTable       OBJECT-TYPE
                               SYNTAX        SEQUENCE OF OutletSensorControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "A list of control entries for the outlet sensors of a PDU. The set
                                    of valid indexes is defined by the value of outletCount and the
                                    outletDeviceCapabilities entry for the selected outlet."
                               ::= { outletSensorControl 1 }

outletSensorControlEntry       OBJECT-TYPE
                               SYNTAX        OutletSensorControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "An entry used for controlling an outlet sensor."
                               INDEX         { pduId, outletId, sensorType }
                               ::= { outletSensorControlTable 1 }

OutletSensorControlEntryStruct ::= SEQUENCE {
                                       outletSensorResetValue Integer32
                                   }

outletSensorResetValue         OBJECT-TYPE
                               SYNTAX        Integer32
                               MAX-ACCESS    read-write
                               STATUS        current
                               DESCRIPTION
                                   "Writing to this variable sets a new value for the addressed sensor. Only
                                    accumulating sensors (e.g. energy counters) can be reset, and currently
                                    the only supported value is 0. Writing any other value returns an error.
                                    This variable will always read as 0."
                               ::= { outletSensorControlEntry 1 }

-- the UnitSensorControlTable

-- The UnitSensorControl table implements operations on pdu sensors

unitSensorControlTable        OBJECT-TYPE
                               SYNTAX        SEQUENCE OF UnitSensorControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "A list of control entries for the global sensors of a PDU. The set
                                    of valid indexes is defined by the value of pduCount and the
                                    pduDeviceCapabilities entry."
                               ::= { unitSensorControl 1 }

unitSensorControlEntry        OBJECT-TYPE
                               SYNTAX        UnitSensorControlEntryStruct
                               MAX-ACCESS    not-accessible
                               STATUS        current
                               DESCRIPTION
                                   "An entry used for controlling an global sensor."
                               INDEX         { pduId, sensorType }
                               ::= { unitSensorControlTable 1 }

UnitSensorControlEntryStruct ::= SEQUENCE {
                                      unitSensorResetValue Integer32
                                  }

unitSensorResetValue          OBJECT-TYPE
                               SYNTAX        Integer32
                               MAX-ACCESS    read-write
                               STATUS        current
                               DESCRIPTION
                                   "Writing to this variable sets a new value for the addressed sensor. Only
                                    accumulating sensors (e.g. energy counters) can be reset, and currently
                                    the only supported value is 0. Writing any other value returns an error.
                                    This variable will always read as 0."
                               ::= { unitSensorControlEntry 1 }

-- the ReliabilityData table

-- The ReliabilityData table contains reliability data for the PDU.


reliabilityDataTableSequenceNumber     OBJECT-TYPE
                SYNTAX        Integer32(1..2147483647) 
                MAX-ACCESS    read-only
                STATUS        current
                DESCRIPTION
                    "The sequence number for updates to the reliability data table"
                ::= { reliabilityData 1 }


reliabilityDataTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ReliabilityDataEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of PDU reliability data entries."
                ::= { reliabilityData 2 }

reliabilityDataEntry     OBJECT-TYPE
                SYNTAX        ReliabilityDataEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing reliability data for a particular PDU."
                INDEX         { reliabilityIndex }
                ::= { reliabilityDataTable 1 }

ReliabilityDataEntryStruct ::= SEQUENCE {
                                    reliabilityIndex                             Integer32, 
                                    reliabilityId                                DisplayString,
                                    reliabilityDataValue                         Unsigned32,
                                    reliabilityDataMaxPossible                   Unsigned32,
                                    reliabilityDataWorstValue                    Unsigned32,
                                    reliabilityDataThreshold                     Unsigned32,
                                    reliabilityDataRawUpperBytes                 Unsigned32,
                                    reliabilityDataRawLowerBytes                 Unsigned32,
                                    reliabilityDataFlags                         BITS
                              }



reliabilityIndex                   OBJECT-TYPE
                                      SYNTAX        Integer32(1..4096)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "Index of the entry in the table."
                                      ::= { reliabilityDataEntry 1 }

reliabilityId                      OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Unique ID of the entry.
                                           POH
                                               Power on hours.

                                           CB.<label>.TRIPCNT
                                              Trip count of circuit breaker with label <label>.

                                           CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR
                                              Number of checksum errors in slave (controller board) to master (CPU
                                              board) communication in the last hour on controller with serial
                                              number <serial> and bus address <addr>.

                                           CTRL.<serial>.<addr>.SLAVE.CSUMERRLASTHOUR
                                             Number of checksum errors in master (CPU board) to slave (controller
                                             board) communication in the last hour on controller with serial
                                             number <serial> and bus address <addr>.

                                           CTRL.<serial>.<addr>.TOUTLASTHOUR
                                             Number of communication timeouts to controller with serial
                                             number <serial> and bus address <addr> in the last hour.

                                           CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT
                                             Number of cycles the relay <num> on the controller board with serial
                                             number <serial> and bus address <addr> has made. A cycle is an
                                             off->on followed by an on->off event later. The count is increased on
                                             the off->on transition.

                                           CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR
                                             Number of failed switching operations on relay <num> on the controller
                                             board with serial number <serial> and bus address <addr> in the last
                                             hour. It depends on the specific controller board hardware  and what
                                             error conditions are detected.
                                         "
                                      ::= { reliabilityDataEntry 2 }


reliabilityDataValue            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The normalized value"
                                      ::= { reliabilityDataEntry 3 }

reliabilityDataMaxPossible    OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The maximum possible normalized value"
                                      ::= { reliabilityDataEntry 4 }


reliabilityDataWorstValue     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The worst normalized value seen so far"
                                      ::= { reliabilityDataEntry 5 }

reliabilityDataThreshold     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The normalized Threshold value "
                                      ::= { reliabilityDataEntry 6 }

reliabilityDataRawUpperBytes   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The Upper 4 bytes of the raw ( not normalized) data.
                                          reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes
                                          should be combined and interpreted as a signed 64-bit value"
                                      ::= { reliabilityDataEntry 7 }

reliabilityDataRawLowerBytes   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower 4 bytes of the raw ( not normalized) data.
                                           reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes
                                          should be combined and interpreted as a signed 64-bit value"
                                      ::= { reliabilityDataEntry 8 }



reliabilityDataFlags          OBJECT-TYPE
                                      SYNTAX        BITS{
                                                        invalidFlag(0),
                                                        oldValue(1),
                                                        criticalEntry(2)
                                                        
                                                        }
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Flags"
                                      ::= { reliabilityDataEntry 9 }





-- the ReliabilityErrorLog table

-- The ReliabilityErrorLog table contains the reliability ErrorLog for the PDU.


reliabilityErrorLogTable     OBJECT-TYPE
                SYNTAX        SEQUENCE OF ReliabilityErrorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "A list of PDU reliability ErrorLog entries. "
                ::= { reliabilityErrorLog 2 }

reliabilityErrorLogEntry     OBJECT-TYPE
                SYNTAX        ReliabilityErrorLogEntryStruct
                MAX-ACCESS    not-accessible
                STATUS        current
                DESCRIPTION
                    "An entry containing reliability ErrorLog data for a particular PDU."
                INDEX         { reliabilityErrorLogIndex }
                ::= { reliabilityErrorLogTable 1 }

ReliabilityErrorLogEntryStruct ::= SEQUENCE {
                                    reliabilityErrorLogIndex                     Integer32, 
                                    reliabilityErrorLogId                        DisplayString,
                                    reliabilityErrorLogValue                     Unsigned32,
                                    reliabilityErrorLogThreshold                 Unsigned32,
                                    reliabilityErrorLogRawUpperBytes             Unsigned32,
                                    reliabilityErrorLogRawLowerBytes             Unsigned32,
                                    reliabilityErrorLogPOH                       Unsigned32,
                                    reliabilityErrorLogTime                      Unsigned32
                              }



reliabilityErrorLogIndex                   OBJECT-TYPE
                                      SYNTAX        Integer32(1..2147483647)
                                      MAX-ACCESS    not-accessible
                                      STATUS        current
                                      DESCRIPTION
                                          "Index of the entry in the table."
                                      ::= { reliabilityErrorLogEntry 1 }


reliabilityErrorLogId                   OBJECT-TYPE
                                      SYNTAX        DisplayString
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "Unique ID of the entry.
                                           POH
                                               Power on hours.

                                           CB.<label>.TRIPCNT
                                              Trip count of circuit breaker with label <label>.

                                           CTRL.<serial>.<addr>.MASTER.CSUMERRLASTHOUR
                                              Number of checksum errors in slave (controller board) to master (CPU
                                              board) communication in the last hour on controller with serial
                                              number <serial> and bus address <addr>.

                                           CTRL.<serial>.<addr>.SLAVE.CSUMERRLASTHOUR
                                             Number of checksum errors in master (CPU board) to slave (controller
                                             board) communication in the last hour on controller with serial
                                             number <serial> and bus address <addr>.

                                           CTRL.<serial>.<addr>.TOUTLASTHOUR
                                             Number of communication timeouts to controller with serial
                                             number <serial> and bus address <addr> in the last hour.

                                           CTRL.<serial>.<addr>.RLY.<num>.CYCLECNT
                                             Number of cycles the relay <num> on the controller board with serial
                                             number <serial> and bus address <addr> has made. A cycle is an
                                             off->on followed by an on->off event later. The count is increased on
                                             the off->on transition.

                                           CTRL.<serial>.<addr>.RLY.<num>.FAILLASTHOUR
                                             Number of failed switching operations on relay <num> on the controller
                                             board with serial number <serial> and bus address <addr> in the last
                                             hour. It depends on the specific controller board hardware  and what
                                             error conditions are detected.

                                          "
                                      ::= { reliabilityErrorLogEntry 2 }



reliabilityErrorLogValue            OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The normalized value"
                                      ::= { reliabilityErrorLogEntry 3 }



reliabilityErrorLogThreshold     OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The normalized Threshold value "
                                      ::= { reliabilityErrorLogEntry 6 }

reliabilityErrorLogRawUpperBytes   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The Upper 4 bytes of the raw ( not normalized) data.
                                          reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes
                                          should be combined and interpreted as a signed 64-bit value"
                                      ::= { reliabilityErrorLogEntry 7 }

reliabilityErrorLogRawLowerBytes   OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The lower 4 bytes of the raw ( not normalized) data.
                                           reliabilityDataRawUpperBytes and reliabilityDataRawLowerBytes
                                          should be combined and interpreted as a signed 64-bit value"
                                      ::= { reliabilityErrorLogEntry 8 }

reliabilityErrorLogPOH           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The time of occurrence of the event measured from the last
                                           time the PDU was powered on"
                                      ::= { reliabilityErrorLogEntry 9 }

reliabilityErrorLogTime           OBJECT-TYPE
                                      SYNTAX        Unsigned32
                                      MAX-ACCESS    read-only
                                      STATUS        current
                                      DESCRIPTION
                                          "The UTC time of occurrence of the event "
                                      ::= { reliabilityErrorLogEntry 10 }


-- Start the traps
-- All traps contain the pxInetIPAddressType and  pxInetIPAddress fields. 
-- For IPv4, these parameters contain the IP Address Type and IP address
-- For IPv6, these parameters are not used
 

systemStarted             NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "The system has started. 
                               "
                          ::= { traps 1 }

systemReset           NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                    }
                          STATUS current
                          DESCRIPTION
                              "The system was reset. The conditions under which
                               this trap is sent include, but are not limited to, the following.
                                 using the GUI - Maintenance->Reset Unit
                                 using the CLI - reset pdu unit"
                          ::= { traps 2 }

userLogin                 NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user logged in."
                          ::= { traps 3 }

userLogout                NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user logged out."
                          ::= { traps 4 }

userAuthenticationFailure NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user authentication attempt failed."
                          ::= { traps 5 }

userSessionTimeout        NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user session timed out."
                          ::= { traps 8 }

userAdded                 NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    targetUser,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user was added to the system."
                          ::= { traps 11 }

userModified              NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    targetUser,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user was modified."
                          ::= { traps 12 }

userDeleted               NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    targetUser,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A user was deleted from the system."
                          ::= { traps 13 }

roleAdded                NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    roleName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A role was added to the system."
                          ::= { traps 14 }

roleModified             NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    roleName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A role was modified."
                          ::= { traps 15 }


roleDeleted              NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    roleName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A role was deleted from the system."
                          ::= { traps 16 }

deviceUpdateStarted       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    imageVersion,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "The device update has started."
                          ::= { traps 20 }

deviceUpdateCompleted       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    imageVersion,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "The device update has completed."
                          ::= { traps 21 }

userBlocked               NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "A blocked user tried to log in."
                          ::= { traps 22 }

powerControl              NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    outletLabel,
                                    measurementsOutletSensorState,
                                    switchingOperation,
                                    sysContact,
                                    sysName,
                                    sysLocation }
                          STATUS current
                          DESCRIPTION
                              "An outlet switching operation has been performed.
                               Note that measurementsOutletSensorState represents the state of the outlet at the time the trap was sent. 
                               This may be different from the final state of the outlet. For instance, 
                               if the outlet is cycled and the outlet cycle delay is 20 seconds, this variable will 
                               indicate OFF although the final state of the outlet will be ON. The final state of the
                               outlet will be indicated in the outletSensorStateChange trap for the outlet onOff sensor."
                          ::= { traps 23 }



userPasswordChanged       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    targetUser,
                                    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "User password was changed."
                          ::= { traps 24 }

passwordSettingsChanged   NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "Strong password settings changed."
                          ::= { traps 28 }





firmwareValidationFailed  NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "Firmware validation failed."
                          ::= { traps 38 }



logFileCleared            NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "The log file has been cleared."
                          ::= { traps 41 }






bulkConfigurationSaved        NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               userName,
                                               pxIPAddress,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Bulk Configuration saved."
                                     ::= { traps 53 }

bulkConfigurationCopied        NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               userName,
                                               pxIPAddress,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Bulk Configuration copied to the device."
                                     ::= { traps 54 }



pduSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               typeOfSensor,
                                               measurementsUnitSensorTimeStamp,
                                               measurementsUnitSensorValue,
                                               measurementsUnitSensorState,
                                               measurementsUnitSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS deprecated
                                     DESCRIPTION
                                         "PDU Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsUnitSensorValue is undefined for sensors which can
                                          have negative readings, measurementsUnitSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings."
                                     ::= { traps 60 }

inletSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               inletLabel,
                                               typeOfSensor,
                                               measurementsInletSensorTimeStamp,
                                               measurementsInletSensorValue,
                                               measurementsInletSensorState,
                                               measurementsInletSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Inlet Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsInletSensorValue is undefined for sensors which can
                                          have negative readings, measurementsInletSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings.

                                          For an rcmState sensor transitioning to the fail state, the value is the residual current
                                          just before the sensor transitioned to the fail state i.e.
                                           if typeOfSensor = rcmState and measurementsInletSensorState = fail,
                                             then measurementsInletSensorValue = the residual current just before the sensor transitioned to the fail state
                                          "
                                     ::= { traps 61 }

inletPoleSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               inletLabel,
                                               inletPoleNumber,
                                               typeOfSensor,
                                               measurementsInletPoleSensorTimeStamp,
                                               measurementsInletPoleSensorValue,
                                               measurementsInletPoleSensorState,
                                               measurementsInletPoleSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Inlet Pole Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsInletPoleSensorValue is undefined for sensors which can
                                          have negative readings, measurementsInletPoleSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings."
                                     ::= { traps 62 }

outletSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               outletLabel,
                                               typeOfSensor,
                                               measurementsOutletSensorTimeStamp,
                                               measurementsOutletSensorValue,
                                               measurementsOutletSensorState,
                                               measurementsOutletSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Outlet Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsOutletSensorValue is undefined for sensors which can
                                          have negative readings, measurementsOutletSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings."
                                     ::= { traps 63 }

outletPoleSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               outletLabel,
                                               outletPoleNumber,
                                               typeOfSensor,
                                               measurementsOutletPoleSensorTimeStamp,
                                               measurementsOutletPoleSensorValue,
                                               measurementsOutletPoleSensorState,
                                               measurementsOutletPoleSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Outlet Pole Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsOutletPoleSensorValue is undefined for sensors which can
                                          have negative readings, measurementsOutletPoleSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings."
                                     ::= { traps 64 }

overCurrentProtectorSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               overCurrentProtectorLabel,
                                               typeOfSensor,
                                               measurementsOverCurrentProtectorSensorTimeStamp,
                                               measurementsOverCurrentProtectorSensorValue,
                                               measurementsOverCurrentProtectorSensorState,
                                               measurementsOverCurrentProtectorSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Overcurrent Protector Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsOverCurrentProtectorSensorValue is undefined for sensors which can
                                          have negative readings, measurementsOverCurrentProtectorSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings."
                                     ::= { traps 65 }

externalSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS { 
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               externalSensorNumber,
                                               typeOfSensor,
                                               measurementsExternalSensorTimeStamp,
                                               measurementsExternalSensorValue, 
                                               measurementsExternalSensorState ,
                                               oldSensorState,
                                               externalSensorSerialNumber,
                                               externalOnOffSensorSubtype,
                                               externalSensorChannelNumber,
                                               sysContact,
                                               sysName,
                                               sysLocation 
                                            }
                                     STATUS current
                                     DESCRIPTION
                                         "External Sensor State Change."
                                     ::= { traps 66 }


smtpMessageTransmissionFailure          NOTIFICATION-TYPE
                                    OBJECTS { pduName,
                                              pxInetAddressType,
                                    	      pxInetIPAddress,
                                              agentInetPortNumber,
                                              smtpMessageRecipients,
                                              smtpServer,
                                              sysContact,
                                              sysName,
                                              sysLocation  }
                                    STATUS current
                                    DESCRIPTION
                                           "SMTP message transmission failure"
                                     ::= { traps 67 }


ldapError          NOTIFICATION-TYPE
                                    OBJECTS { pduName,
                                              pxInetAddressType,
                                    	      pxInetIPAddress,
                                              agentInetPortNumber,
                                              errorDescription,
                                              sysContact,
                                              sysName,
                                              sysLocation 
                                               }
                                    STATUS current
                                    DESCRIPTION
                                           "LDAP Error occurred; errorDescription describes the error"
                                     ::= { traps 68 }

deviceUpdateFailed       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    imageVersion,
                                    sysContact,
                                    sysName,
                                    sysLocation  }
                          STATUS current
                          DESCRIPTION
                              "The device update has failed."
                          ::= { traps 70 }

loadSheddingModeEntered       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The PX has enetered Load Shedding Mode"
                          ::= { traps 71 }

loadSheddingModeExited       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The PX has exited Load Shedding Mode"
                          ::= { traps 72 }

pingServerEnabled        NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    serverIPAddress,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The ping feature has been enabled"
                          ::= { traps 73 }

pingServerDisabled        NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    serverIPAddress,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The ping feature has been disabled"
                          ::= { traps 74 }

serverNotReachable        NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    serverIPAddress,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The server is not reachable"
                          ::= { traps 75 }

serverReachable        NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    serverIPAddress,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The server is  reachable"
                          ::= { traps 76 }

rfCodeTagConnected       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The RF Code Tag is Connected"
                          ::= { traps 77 }

rfCodeTagDisconnected       NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The RF Code Tag is Disconnected"
                          ::= { traps 78 }


deviceIdentificationChanged   NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    userName,
                                    deviceChangedParameter,
                                    changedParameterNewValue,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "Device identification has changed"
                          ::= { traps 79 }

usbSlaveConnected   NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "USB Connectivity to slave has been established"
                          ::= { traps 80 }

usbSlaveDisconnected   NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "USB Connectivity to slave has been lost"
                          ::= { traps 81 }

lhxSupportChanged NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation,
				    lhxSupportEnabled
                                  }
                          STATUS current
                          DESCRIPTION
                              "The Schroff LHX Support has been either enabled or disabled."
                          ::= { traps 82 }

userAcceptedRestrictedServiceAgreement NOTIFICATION-TYPE
                          OBJECTS { pduName,
			  	    userName,
				    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation
                                  }
                          STATUS current
                          DESCRIPTION
                              "The user accepted the Restricted Service Agreement."
                          ::= { traps 83 }

userDeclinedRestrictedServiceAgreement NOTIFICATION-TYPE
                          OBJECTS { pduName,
			  	    userName,
				    pxIPAddress,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    sysContact,
                                    sysName,
                                    sysLocation
                                  }
                          STATUS current
                          DESCRIPTION
                              "The user declined the Restricted Service Agreement."
                          ::= { traps 84 }

wireSensorStateChange NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pduNumber,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    wireLabel,
                                    typeOfSensor,
                                    measurementsWireSensorTimeStamp,
                                    measurementsWireSensorValue,
                                    measurementsWireSensorState,
                                    oldSensorState,
                                    sysContact,
                                    sysName,
                                    sysLocation
                                  }
                          STATUS deprecated
                          DESCRIPTION
                              "Wire Sensor State Change."
                          ::= { traps 85 }


transferSwitchSensorStateChange NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pduNumber,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    transferSwitchLabel,
                                    typeOfSensor,
                                    measurementsTransferSwitchSensorTimeStamp,
                                    measurementsTransferSwitchSensorValue,
                                    measurementsTransferSwitchSensorState,
                                    measurementsTransferSwitchSensorSignedValue,
                                    oldSensorState,
                                    sysContact,
                                    sysName,
                                    sysLocation,
                                    transferSwitchLastTransferReason
                                  }
                          STATUS current
                          DESCRIPTION
                              "Transfer Switch Sensor State Change.
                               Which value field to use depends on the metadata of the sensor.
                               measurementsTransferSwitchSensorValue is undefined for sensors which can
                               have negative readings, measurementsTransferSwitchSensorSignedValue is
                               undefined for sensors whose range exceeds the Integer32 range.
                               Both fields do not apply to sensors without numerical readings."
                          ::= { traps 86 }


deviceSettingsSaved        NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               userName,
                                               pxIPAddress,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Device Settings have been saved."
                                     ::= { traps 88 }

deviceSettingsRestored        NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               userName,
                                               pxIPAddress,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Device Settings have been restored."
                                     ::= { traps 89 }

webcamInserted                 NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               webcamModel,
                                               webcamConnectionPort,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "A webcam has been inserted"
                                     ::= { traps 90 }

webcamRemoved                 NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               pxInetAddressType,
                                    	       pxInetIPAddress,
                                               agentInetPortNumber,
                                               webcamModel,
                                               webcamConnectionPort,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "A webcam has been removed"
                                     ::= { traps 91 }

inletEnabled                  NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               userName,
                                               pxInetAddressType,
                                               pxInetIPAddress,
                                               agentInetPortNumber,
                                               inletLabel,
                                               sysContact,
                                               sysName,
                                               sysLocation }
                                     STATUS current
                                     DESCRIPTION
                                         "PDU operation has been enabled for an inlet"
                                     ::= { traps 92 }

inletDisabled                 NOTIFICATION-TYPE
                                     OBJECTS { pduName,
                                               userName,
                                               pxInetAddressType,
                                               pxInetIPAddress,
                                               agentInetPortNumber,
                                               inletLabel,
                                               sysContact,
                                               sysName,
                                               sysLocation }
                                     STATUS current
                                     DESCRIPTION
                                         "PDU operation has been disabled for an inlet"
                                     ::= { traps 93 }

serverConnectivityUnrecoverable NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    serverIPAddress,
                                    sysContact,
                                    sysName,
                                    sysLocation 
                                     }
                          STATUS current
                          DESCRIPTION
                              "The connection to the server could not be recovered"
                          ::= { traps 94 }


radiusError          NOTIFICATION-TYPE
                                    OBJECTS { pduName,
                                              pxInetAddressType,
                                    	      pxInetIPAddress,
                                              agentInetPortNumber,
                                              errorDescription,
                                              sysContact,
                                              sysName,
                                              sysLocation 
                                               }
                                    STATUS current
                                    DESCRIPTION
                                           "LDAP Error occurred; errorDescription describes the error"
                                     ::= { traps 95 }


serverReachabilityError          NOTIFICATION-TYPE
                                    OBJECTS { pduName,
                                              pxInetAddressType,
                                    	      pxInetIPAddress,
                                              agentInetPortNumber,
                                              serverIPAddress,
                                              errorDescription,
                                              sysContact,
                                              sysName,
                                              sysLocation 
                                               }
                                    STATUS current
                                    DESCRIPTION
                                           "Server Reachability Error occurred; errorDescription describes the error.
                                              This trap is sent when the Error state is entered.
                                              Reasons for transitioning to the Error state include the following:
                                                     Unable to resolve the server hostname.  "
                                     ::= { traps 96 }

inletSensorReset          NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pduNumber,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    inletLabel,
                                    typeOfSensor,
                                    sysContact,
                                    sysName,
                                    sysLocation }
                          STATUS current
                          DESCRIPTION
                              "An inlet sensor was reset."
                          ::= { traps 97 }

outletSensorReset         NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pduNumber,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    outletLabel,
                                    typeOfSensor,
                                    sysContact,
                                    sysName,
                                    sysLocation }
                          STATUS current
                          DESCRIPTION
                              "An outlet sensor was reset."
                          ::= { traps 98 }

unknownPeripheralDeviceAttached NOTIFICATION-TYPE
                                    OBJECTS { pduName,
                                              pxInetAddressType,
					      pxInetIPAddress,
                                              agentInetPortNumber,
					      peripheralDeviceRomcode,
					      peripheralDevicePackagePosition,
                                              sysContact,
                                              sysName,
                                              sysLocation 
                                               }
                                    STATUS current
                                    DESCRIPTION
                                           "An unknown peripheral device was attached."
                                     ::= { traps 99 }

peripheralDeviceFirmwareUpdate NOTIFICATION-TYPE
                                    OBJECTS { pduName,
                                              pxInetAddressType,
					      pxInetIPAddress,
                                              agentInetPortNumber,
					      peripheralDevicePackageSerialNumber,
					      peripheralDeviceFirmwareUpdateState,
					      peripheralDevicePackageFirmwareVersion,
                                              sysContact,
                                              sysName,
                                              sysLocation 
                                               }
                                    STATUS current
                                    DESCRIPTION
                                           "The firmware update state of a peripheral device changed while 
					    performing update to peripheralDevicePackageFirmwareVersion."
                                     ::= { traps 100 }

unitSensorReset          NOTIFICATION-TYPE
                          OBJECTS { pduName,
                                    userName,
                                    pduNumber,
                                    pxInetAddressType,
                                    pxInetIPAddress,
                                    agentInetPortNumber,
                                    typeOfSensor,
                                    sysContact,
                                    sysName,
                                    sysLocation }
                          STATUS current
                          DESCRIPTION
                              "A global sensor was reset."
                          ::= { traps 101 }

unitSensorStateChange                NOTIFICATION-TYPE
                                     OBJECTS {
                                               pduName,
                                               pduNumber,
                                               pxInetAddressType,
                                               pxInetIPAddress,
                                               agentInetPortNumber,
                                               typeOfSensor,
                                               measurementsUnitSensorTimeStamp,
                                               measurementsUnitSensorValue,
                                               measurementsUnitSensorState,
                                               measurementsUnitSensorSignedValue,
                                               oldSensorState,
                                               sysContact,
                                               sysName,
                                               sysLocation  }
                                     STATUS current
                                     DESCRIPTION
                                         "Unit Sensor State Change.
                                          Which value field to use depends on the metadata of the sensor.
                                          measurementsUnitSensorValue is undefined for sensors which can
                                          have negative readings, measurementsUnitSensorSignedValue is
                                          undefined for sensors whose range exceeds the Integer32 range.
                                          Both fields do not apply to sensors without numerical readings."
                                     ::= { traps 102 }