--Delta-MIB { iso(1) org(3) dod(6) internet(1) private(4) enterprises(1) delta(2254) ups(2) upsv4(4) }


DeltaUPS-MIB DEFINITIONS ::= BEGIN


IMPORTS
	enterprises, IpAddress
		FROM RFC1155-SMI
	DisplayString
		FROM RFC1213-MIB
	OBJECT-TYPE
		FROM RFC-1212
	TRAP-TYPE
		FROM RFC-1215;


delta				OBJECT IDENTIFIER ::=  { enterprises 2254 }

ups					OBJECT IDENTIFIER ::=  { delta 2 }

upsv4				OBJECT IDENTIFIER ::=  { ups 4 }

dupsIdent			OBJECT IDENTIFIER ::=  { upsv4 1 }
dupsControl			OBJECT IDENTIFIER ::=  { upsv4 2 }
dupsConfig			OBJECT IDENTIFIER ::=  { upsv4 3 }
dupsInput			OBJECT IDENTIFIER ::=  { upsv4 4 }
dupsOutput			OBJECT IDENTIFIER ::=  { upsv4 5 }
dupsBypass			OBJECT IDENTIFIER ::=  { upsv4 6 }
dupsBattery			OBJECT IDENTIFIER ::=  { upsv4 7 }
dupsTest 			OBJECT IDENTIFIER ::=  { upsv4 8 }
dupsAlarm 			OBJECT IDENTIFIER ::=  { upsv4 9 }
dupsEnvironment		OBJECT IDENTIFIER ::=  { upsv4 10 }
dupsTraps			OBJECT IDENTIFIER ::=  { upsv4 20 }


----------------------
-- dups Ident group --
----------------------
   dupsIdentManufacturer OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..20))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The name of the UPS manufacturer."
       ::= { dupsIdent 1 }

   dupsIdentModel OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..31))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The UPS Model designation."
       ::= { dupsIdent 2 }

   dupsIdentUPSSoftwareVersion OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..15))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The UPS firmware/software version(s). This variable
               may or may not has the same value as
               upsIdentAgentSoftwareVersion in some implementations."
       ::= { dupsIdent 3 }

   dupsIdentAgentSoftwareVersion OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..15))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The UPS agent software version. This variable may or
               may not has the same value as
               upsIdentUPSSoftwareVersion in some implementations."
       ::= { dupsIdent 4 }

   dupsIdentName OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..63))
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "A string identifying the UPS. This object should be
               set by the administrator."
       ::= { dupsIdent 5 }

   dupsAttachedDevices OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..63))
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "A string identifying the devices attached to the
               output(s) of the UPS. This object should be set by
               the administrator."
       ::= { dupsIdent 6 }

   dupsRatingOutputVA OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the nominal output VA rating."
       ::= { dupsIdent 7 }

   dupsRatingOutputVoltage OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the nominal output voltage rating."
       ::= { dupsIdent 8 }

   dupsRatingOutputFrequency OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the nominal output frequency rating."
       ::= { dupsIdent 9 }

   dupsRatingInputVoltage OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the nominal input voltage rating."
       ::= { dupsIdent 10 }

   dupsRatingInputFrequency OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the nominal input frequency rating."
       ::= { dupsIdent 11 }

   dupsRatingBatteryVoltage OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the nominal battery voltage rating."
       ::= { dupsIdent 12 }

   dupsLowTransferVoltUpBound OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Volt"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The minimum input line voltage upper bound allowed
               before the UPS system transfers to battery backup."
       ::= { dupsIdent 13 }

   dupsLowTransferVoltLowBound OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Volt"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The minimum input line voltage lower bound allowed
               before the UPS system transfers to battery backup."
       ::= { dupsIdent 14 }

   dupsHighTransferVoltUpBound OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Volt"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The maximum input line voltage upper bound allowed
               before the UPS system transfers to battery backup."
       ::= { dupsIdent 15 }

   dupsHighTransferVoltLowBound OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Volt"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The maximum input line voltage lower bound allowed
               before the UPS system transfers to battery backup."
       ::= { dupsIdent 16 }

   dupsLowBattTime OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Minutes, time from low battery to low battery shutdown."
       ::= { dupsIdent 17 }

   dupsOutletRelays OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Number of outlet relay. If it is 0, the function is not
               available for the UPS."
       ::= { dupsIdent 18 }

   dupsType OBJECT-TYPE
       SYNTAX     INTEGER {
           on-line(1),
           off-line(2),
           line-interactive(3),
           3phase(4),
           splite-phase(5)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Indicate the UPS type."
       ::= { dupsIdent 19 }

------------------------
-- dups Control group --
------------------------
   dupsShutdownType OBJECT-TYPE
       SYNTAX     INTEGER {
           output(1),
           system(2)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "This object determines the nature of the action to be
               taken at the time when the countdown of the
               upsShutdownAfterDelay and upsRebootWithDuration
               objects reaches zero.
               Setting this object to output(1) indicates that
               shutdown requests should cause only the output of the
               UPS to turn off.  Setting this object to system(2)
               indicates that shutdown requests will cause the entire
               UPS system to turn off."
       ::= { dupsControl 1 }

   dupsAutoReboot OBJECT-TYPE
       SYNTAX     INTEGER {
           on(1),
           off(2)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "In backup mode, the UPS may shutdown normally by SDA command, 
               dry-contact remote shutdown signal or low battery shutdown. 
               This command is used to determine the unit should restart or 
               not next time when the power restores"
       ::= { dupsControl 2 }

   dupsShutdownAction OBJECT-TYPE
       SYNTAX     INTEGER
--       UNITS      "Second"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "If the value is greater than 0 the UPS performs
               shutdown action that defined by ShutdownType after
               the seconds. 0, aborted."
       ::= { dupsControl 3 }

   dupsRestartAction OBJECT-TYPE
       SYNTAX     INTEGER
--       UNITS      "Minute"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "UPS will restart after the indicated number of minutes.
                -1, aborted."
       ::= { dupsControl 4 }

   dupsSetOutletRelay OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Indicate which outlet relay, from 1,2,3... ."
       ::= { dupsControl 5 }

   dupsRelayOffDelay OBJECT-TYPE
       SYNTAX     INTEGER
--       UNITS      "Second"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Turn the relay off after the seconds. The relay was indicated
                by SetOutletRelay."
       ::= { dupsControl 6 }

   dupsRelayOnDelay OBJECT-TYPE
       SYNTAX     INTEGER
--       UNITS      "Minute"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Turn the relay on after the seconds. The relay was indicated
                by SetOutletRelay."
       ::= { dupsControl 7 }

--------------------------
-- dups Configure group --
--------------------------
   dupsConfigBuzzerAlarm OBJECT-TYPE
       SYNTAX     INTEGER {
           alarm(1),
           silence(2)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "UPS will keep silence but will alarm again when 
               next power event is occurred"
       ::= { dupsConfig 1 }

   dupsConfigBuzzerState OBJECT-TYPE
       SYNTAX     INTEGER {
           enable(1),
           disable(2)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "If it is disabled then the UPS is always muted."
       ::= { dupsConfig 2 }

   dupsConfigSensitivity OBJECT-TYPE
       SYNTAX     INTEGER {
           normal(0),
           reduced(1),
           low(2)
       }
       ACCESS    read-write
       STATUS    mandatory
       DESCRIPTION
               "The seneitivity of the UPS to utility line
               abnormalities or noises."
       ::= { dupsConfig 3 }

   dupsConfigLowVoltageTransferPoint OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Volt"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "The minimum input line voltage allowed before the UPS
               system transfers to battery backup."
       ::= { dupsConfig 4 }

   dupsConfigHighVoltageTransferPoint OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Volt"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "The maximum line voltage allowed before the UPS
               system transfers to battery backup."
       ::= { dupsConfig 5 }

   dupsConfigShutdownOSDelay OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Second"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "The operating system shutdown delay time when the 
                input power fail. -1 will disable this option."
       ::= { dupsConfig 6 }

   dupsConfigUPSBootDelay OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "Second"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Delay the UPS startup after power restores. The power
               quality may not stable when power restores, this 
               feature let the UPS wait a period of time to startup 
               the system."
       ::= { dupsConfig 7 }

   dupsConfigExternalBatteryPack OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Indicate the number of external battery pack."
       ::= { dupsConfig 8 }

----------------------
-- dups Input group --
----------------------
   dupsInputNumLines OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The number of input lines utilized in this device."
       ::= { dupsInput 1 }

   dupsInputFrequency1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current input line 1 frequency to the UPS
                system in 1/10 Hz."
	::= { dupsInput 2 }

   dupsInputVoltage1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Input line 1 voltage of the UPS system in 1/10 V."
	::= { dupsInput 3 }

   dupsInputCurrent1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Input line 1 current to the UPS system in 1/10 A."
	::= { dupsInput 4 }

   dupsInputFrequency2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current input line 2 frequency to the UPS system
                in 1/10 Hz."
	::= { dupsInput 5 }

   dupsInputVoltage2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Input line 2 voltage of the UPS system in 1/10 V."
	::= { dupsInput 6 }

   dupsInputCurrent2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Input line 2 current to the UPS system in 1/10 A."
	::= { dupsInput 7 }

   dupsInputFrequency3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current input line 3 frequency to the UPS system
                in 1/10 Hz."
	::= { dupsInput 8 }

   dupsInputVoltage3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Input line 3 voltage of the UPS system in 1/10 V."
	::= { dupsInput 9 }

   dupsInputCurrent3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Input line 3 current to the UPS system in 1/10 A."
	::= { dupsInput 10 }

-----------------------
-- dups Output group --
-----------------------
   dupsOutputSource OBJECT-TYPE
       SYNTAX     INTEGER {
           normal(0),
           battery(1),
           bypass(2),
           reducing(3),
           boosting(4),
           manualBypass(5),
           other(6),
           none(7)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The present source of output power. The enumeration
               none(7) indicates that there is no source of output
               power (and therefore no output power), for example,
               the system has opened the output breaker."
       ::= { dupsOutput 1 }

   dupsOutputFrequency OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "0.1 Hertz"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The present output frequency in 1/10 Hz."
       ::= { dupsOutput 2 }

   dupsOutputNumLines OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The number of output lines utilized in this device."
       ::= { dupsOutput 3 }

   dupsOutputVoltage1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 1 voltage of the UPS system in 1/10 V."
	::= { dupsOutput 4 }

   dupsOutputCurrent1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 1 current of the UPS system in 1/10 A."
	::= { dupsOutput 5 }

   dupsOutputPower1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 1 real power of the UPS system in watts."
	::= { dupsOutput 6 }

   dupsOutputLoad1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current UPS output line 1 load expressed in percent
		 of rated capacity."
	::= { dupsOutput 7 }

   dupsOutputVoltage2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 2 voltage of the UPS system in 1/10 V."
	::= { dupsOutput 8 }

   dupsOutputCurrent2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 2 current of the UPS system in 1/10 A."
	::= { dupsOutput 9 }

   dupsOutputPower2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 2 real power of the UPS system in watts."
	::= { dupsOutput 10 }

   dupsOutputLoad2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current UPS output line 2 load expressed in percent
		 of rated capacity."
	::= { dupsOutput 11 }

   dupsOutputVoltage3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 3 voltage of the UPS system in 1/10 V."
	::= { dupsOutput 12 }

   dupsOutputCurrent3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 3 current of the UPS system in 1/10 A."
	::= { dupsOutput 13 }

   dupsOutputPower3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The Output line 3 real power of the UPS system in watts."
	::= { dupsOutput 14 }

   dupsOutputLoad3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The current UPS output line 3 load expressed in percent
		 of rated capacity."
	::= { dupsOutput 15 }

-----------------------
-- dups Bypass group --
-----------------------
   dupsBypassFrequency OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "0.1 Hertz"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The present bypass frequency in 1/10 Hz."
       ::= { dupsBypass 1 }

   dupsBypassNumLines OBJECT-TYPE
       SYNTAX     INTEGER
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The number of bypass lines utilized in this device."
       ::= { dupsBypass 2 }

   dupsBypassVoltage1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 1 voltage of the UPS system in 1/10 V."
	::= { dupsBypass 3 }

   dupsBypassCurrent1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 1 current of the UPS system in 1/10 A."
	::= { dupsBypass 4 }

   dupsBypassPower1 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 1 real power of the UPS system in watts."
	::= { dupsBypass 5 }

   dupsBypassVoltage2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 2 voltage of the UPS system in 1/10 V."
	::= { dupsBypass 6 }

   dupsBypassCurrent2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 2 current of the UPS system in 1/10 A."
	::= { dupsBypass 7 }

   dupsBypassPower2 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 2 real power of the UPS system in watts."
	::= { dupsBypass 8 }

   dupsBypassVoltage3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 3 voltage of the UPS system in 1/10 V."
	::= { dupsBypass 9 }

   dupsBypassCurrent3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 3 current of the UPS system in 1/10 A."
	::= { dupsBypass 10 }

   dupsBypassPower3 OBJECT-TYPE
	SYNTAX INTEGER
	ACCESS read-only
	STATUS mandatory
	DESCRIPTION
		"The bypass line 3 real power of the UPS system in watts."
	::= { dupsBypass 11 }

------------------------
-- dups Battery group --
------------------------
   dupsBatteryCondiction OBJECT-TYPE
       SYNTAX     INTEGER {
           good(0),
           weak(1),
           replace(2)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The indication of the capacity remaining in the UPS
               system's batteries when AC normal."
       ::= { dupsBattery 1 }

   dupsBatteryStatus OBJECT-TYPE
       SYNTAX     INTEGER {
           ok(0),
           low(1),
           depleted(2)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The indication of the capacity remaining in the UPS
               system's batteries when AC failed.   A value of ok
               indicates that the remaining run-time is greater than
               upsConfigLowBattTime.  A value of low indicates
               that the remaining battery run-time is less than or
               equal to upsConfigLowBattTime.  A value of
               depleted indicates that the UPS will be unable
               to sustain the present load when and if the utility
               power is lost (including the possibility that the
               utility power is currently absent and the UPS is
               unable to sustain the output)."
       ::= { dupsBattery 2 }

   dupsBatteryCharge OBJECT-TYPE
       SYNTAX     INTEGER {
           floating(0),
           charging(1),
           resting(2),
           discharging(3)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
	           ""
       ::= { dupsBattery 3 }

   dupsSecondsOnBattery OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "seconds"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "If the unit is on battery power, the elapsed time
               since the UPS last switched to battery power, or the
               time since the network management subsystem was last
               restarted, whichever is less.  Zero shall be returned
               if the unit is not on battery power."
       ::= { dupsBattery 4 }

   dupsBatteryEstimatedTime OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "minutes"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Estimated time from backup to low battery shutdown."
       ::= { dupsBattery 5 }

   dupsBatteryVoltage OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "0.1 Volt DC"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The magnitude of the present battery voltage 
               in 1/10 V."
       ::= { dupsBattery 6 }

   dupsBatteryCurrent OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "0.1 Amp DC"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The present battery current in 1/10 A."
       ::= { dupsBattery 7 }

   dupsBatteryCapacity OBJECT-TYPE
       SYNTAX     INTEGER (0..100)
       UNITS      "percent"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "An estimate of the battery charge remaining expressed
               as a percent of full charge."
       ::= { dupsBattery 8 }

   dupsTemperature OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "degrees Centigrade"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The ambient temperature at or near the UPS Battery
               casing."
       ::= { dupsBattery 9 }

   dupsLastReplaceDate OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..8))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The last battery replacement date. The format is YYYYMMDD."
       ::= { dupsBattery 10 }

   dupsNextReplaceDate OBJECT-TYPE
       SYNTAX     DisplayString (SIZE(0..8))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The next battery replacement date. The format is YYYYMMDD."
       ::= { dupsBattery 11 }

-------------------
-- dups Test group 
-------------------
   dupsTestType OBJECT-TYPE
       SYNTAX     INTEGER {
           abort(0),
           generalTest(1),
           batteryTest(2),
           testFor10sec(3),
           testUntilBattlow(4)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Perform the UPS Test procedure."
       ::= { dupsTest 1 }

   dupsTestResultsSummary OBJECT-TYPE
       SYNTAX     INTEGER {
           noTestsInitiated(0),
           donePass(1),
           inProgress(2),
           generalTestFail(3),
           batteryTestFail(4),
           deepBatteryTestFail(5)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The results of the current or last UPS diagnostics
               test performed. The values for donePass(1),
               generalTestFail(3), and batteryTestFail(4) indicate that the
               test completed either successfully, with a warning, or
               with an error, respectively.Tests which have not yet
               concluded are indicated by inProgress(2).  The value
               noTestsInitiated(0) indicates that no previous test
               results are available."
       ::= { dupsTest 2 }

   dupsTestResultsDetail OBJECT-TYPE
       SYNTAX     DisplayString (SIZE (0..255))
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Additional information about upsTestResultsSummary.
               If no additional information available, a zero length
               string is returned."
       ::= { dupsTest 3 }

-----------------------
-- dups Alarm group --
-----------------------
   dupsAlarmDisconnect OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS disconnect?"
       ::= { dupsAlarm 1 }

   dupsAlarmPowerFail OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the input power fail?"
       ::= { dupsAlarm 2 }

   dupsAlarmBatteryLow OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Are the UPS batteries low?"
       ::= { dupsAlarm 3 }

   dupsAlarmLoadWarning OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS load percent over the load warning value?"
       ::= { dupsAlarm 4 }

   dupsAlarmLoadSeverity OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS load percent over the load severity value?"
       ::= { dupsAlarm 5 }

   dupsAlarmLoadOnBypass OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS load on bypass?"
       ::= { dupsAlarm 6 }

   dupsAlarmUPSFault OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS general fail?"
       ::= { dupsAlarm 7 }

   dupsAlarmBatteryGroundFault OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS battery ground fault?"
       ::= { dupsAlarm 8 }

   dupsAlarmTestInProgress OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS test in progress?"
       ::= { dupsAlarm 9 }

   dupsAlarmBatteryTestFail OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS test fail?"
       ::= { dupsAlarm 10 }

   dupsAlarmFuseFailure OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS fuse failure?"
       ::= { dupsAlarm 11 }

   dupsAlarmOutputOverload OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS output overload?"
       ::= { dupsAlarm 12 }

   dupsAlarmOutputOverCurrent OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS output overcurrent?"
       ::= { dupsAlarm 13 }

   dupsAlarmInverterAbnormal OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS inverter abnormal?"
       ::= { dupsAlarm 14 }

   dupsAlarmRectifierAbnormal OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS rectifier abnormal?"
       ::= { dupsAlarm 15 }

   dupsAlarmReserveAbnormal OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS reserve abnormal?"
       ::= { dupsAlarm 16 }

   dupsAlarmLoadOnReserve OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS load on reserve?"
       ::= { dupsAlarm 17 }

   dupsAlarmOverTemperature OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS over heat?"
       ::= { dupsAlarm 18 }

   dupsAlarmOutputBad OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Is the UPS output abnormal?"
       ::= { dupsAlarm 19 }

   dupsAlarmBypassBad OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Is the UPS bypass bad?"
       ::= { dupsAlarm 20 }

   dupsAlarmUPSOff OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Is the UPS in standby mode?"
       ::= { dupsAlarm 21 }

   dupsAlarmChargerFail OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS charger fail?"
       ::= { dupsAlarm 22 }

   dupsAlarmFanFail OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the UPS fan fail?"
       ::= { dupsAlarm 23 }

   dupsAlarmEconomicMode OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Indicates whether the UPS is in the economic mode."
       ::= { dupsAlarm 24 }

   dupsAlarmOutputOff OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Indicates whether the UPS output is turned off or not."
       ::= { dupsAlarm 25 }

   dupsAlarmSmartShutdown OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Indicates whether the Smart Shutdown is in progress."
       ::= { dupsAlarm 26 }

   dupsAlarmEmergencyPowerOff OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "UPS emergency power off."
       ::= { dupsAlarm 27 }

   dupsAlarmUPSShutdown OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "UPS shutdown."
       ::= { dupsAlarm 28 }

-----------------------
-- dups Environment group --
-----------------------

   dupsEnvTemperature OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "degrees Centigrade"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The ambient environmental temperature."
       ::= { dupsEnvironment 1 }

   dupsEnvHumidity OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "percentage"
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "The environmental humidity."
       ::= { dupsEnvironment 2 }

   dupsEnvSetTemperatureLimit OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "degrees Centigrade"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Alarm dupsAlarmOverTemperature on when the environmental
		temperature over the value."
       ::= { dupsEnvironment 3 }

   dupsEnvSetHumidityLimit OBJECT-TYPE
       SYNTAX     INTEGER
       UNITS      "percentage"
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               "Alarm dupsAlarmOverHumidity on when the environmental
		humidity over the value."
       ::= { dupsEnvironment 4 }

   dupsEnvSetEnvRelay1 OBJECT-TYPE
       SYNTAX     INTEGER{
                  normalOpen(0),
                  normalClose(1)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 5 }

   dupsEnvSetEnvRelay2 OBJECT-TYPE
       SYNTAX     INTEGER{
                  normalOpen(0),
                  normalClose(1)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 6 }

   dupsEnvSetEnvRelay3 OBJECT-TYPE
       SYNTAX     INTEGER{
                  normalOpen(0),
                  normalClose(1)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 7 }

   dupsEnvSetEnvRelay4 OBJECT-TYPE
       SYNTAX     INTEGER{
                  normalOpen(0),
                  normalClose(1)
       }
       ACCESS     read-write
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 8 }

   dupsAlarmOverEnvTemperature OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the environment over temperature?"
       ::= { dupsEnvironment 9 }

   dupsAlarmOverEnvHumidity OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               "Does the environment over humidity?"
       ::= { dupsEnvironment 10 }

   dupsAlarmEnvRelay1 OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 11 }
       
   dupsAlarmEnvRelay2 OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 12 }
          
    dupsAlarmEnvRelay3 OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 13 }

   dupsAlarmEnvRelay4 OBJECT-TYPE
       SYNTAX     INTEGER{
                  off(0),
                  on(1)
       }
       ACCESS     read-only
       STATUS     mandatory
       DESCRIPTION
               ""
       ::= { dupsEnvironment 14 }

-----------------------
-- dups Trap group --
-----------------------

   dupsCommunicationLost TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: Communication with the UPS failed."
       ::= 1

   dupsCommunicationEstablished TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Communication with the UPS reestablished."
       ::= 2

   dupsPowerFail TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"WARNING: Power failed! The UPS is operating on battery power."
       ::= 3

   dupsPowerRestored TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Power restored! The utility power restored."
       ::= 4

   dupsLowBattery TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS batteries are low and will soon be exhausted."
       ::= 5

   dupsReturnFromLowBattery TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS has returned from a low battery condition."
       ::= 6

   dupsLoadWarning TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Loading percent of the UPS over the Load Warning value."
       ::= 7

   dupsNoLongerLoadWarning TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Returnd from Load Warning condition."
       ::= 8

   dupsLoadSeverity TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"Warning: Loading percent of the UPS over the Load Severity value."
       ::= 9

   dupsNoLongerLoadSeverity TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Returned from Load Severity condition."
       ::= 10

   dupsLoadOnBypass TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS loads on bypass."
       ::= 11

   dupsNoLongerLoadOnBypass TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS is not on bypass mode."
       ::= 12

   dupsUPSFault TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: A general fault caused in the UPS."
       ::= 13

   dupsReturnFromUPSFault TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS is returned from general fault."
       ::= 14

   dupsBatteryGroundFault TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS battery ground fault."
       ::= 15

   dupsNoLongerBatteryFault TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS recovered from battery ground fault."
       ::= 16

   dupsTestInProgress TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS test in progress."
       ::= 17

   dupsBatteryTestFail TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS test fail."
       ::= 18

   dupsFuseFailure TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS fuse failed."
       ::= 19

   dupsFuseRecovered TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS fuse recovered."
       ::= 20

   dupsOutputOverload TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS overload!."
       ::= 21

   dupsNoLongerOverload TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Recovered from UPS overload."
       ::= 22

   dupsOutputOverCurrent TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS output overcurrent."
       ::= 23

   dupsNoLongerOutputOverCurrent TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Recovered from UPS overcurrent."
       ::= 24

   dupsInverterAbnormal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS inverter abnormal."
       ::= 25

   dupsInverterRecovered TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Recovered from UPS inverter abnormal."
       ::= 26

   dupsRectifierAbnormal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS rectifier abnormal."
       ::= 27

   dupsRectifierRecovered TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS recovered from rectifier abnormal."
       ::= 28

   dupsReserveAbnormal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS rectifier abnormal."
       ::= 29

   dupsReserveRecovered TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS rectifier abnormal."
       ::= 30

   dupsLoadOnReserve TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: The UPS load on reserve."
       ::= 31

   dupsNoLongerLoadOnReserve TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS no longer load on reserve."
       ::= 32

   dupsEnvOverTemperature TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"WARNING: The environment overtemperature."
       ::= 33

   dupsNoLongerEnvOverTemperature TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment recovered from overtemperature."
       ::= 34

   dupsEnvOverHumidity TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"WARNING: The environment overhumidity."
       ::= 35

   dupsNoLongerEnvOverHumidity TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment recovered from overhumidity."
       ::= 36

   dupsEnvRelay1Alarm TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay1 is not in normal state."
       ::= 37

   dupsEnvRelay1Normal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay1 is in normal state."
       ::= 38

   dupsEnvRelay2Alarm TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay2 is not in normal state."
       ::= 39

   dupsEnvRelay2Normal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay2 is in normal state."
       ::= 40

   dupsEnvRelay3Alarm TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay3 is not in normal state."
       ::= 41

   dupsEnvRelay3Normal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay3 is in normal state."
       ::= 42

   dupsEnvRelay4Alarm TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay4 is not in normal state."
       ::= 43

   dupsEnvRelay4Normal TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The environment relay4 is in normal state."
       ::= 44

   dupsSmartShutdown TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: Smart Shutdown is initiated."
       ::= 45

   dupsCancelShutdown TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: Cancel UPS Shutdown."
       ::= 46
       
   dupsTestCompleted TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: This trap is sent upon completion of a UPS diagnostic test."
       ::= 47
       
   dupsEPOON TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: This trap is sent when emergency power off is on."
       ::= 48

   dupsEPOOFF TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: This trap is sent when UPS recover from emergency power off."
       ::= 49

   dupsOverTemperature TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"SEVER: This trap is sent when the UPS is over heat."
       ::= 50

   dupsNormalTemperature TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: This trap is sent when UPS recover from over heat."
       ::= 51

   dupsBattReplace TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"WARNING: The battery needs to be replaced."
       ::= 52

   dupsReturnFromBattReplace TRAP-TYPE
       ENTERPRISE dupsTraps
       DESCRIPTION
	"INFORMATION: The UPS recovered from battery replacement."
       ::= 53
END