LIEBERT-GP-PDU-MIB DEFINITIONS ::= BEGIN

IMPORTS
    DisplayString
        FROM SNMPv2-TC
    MODULE-IDENTITY,
    OBJECT-IDENTITY,
    OBJECT-TYPE,
    Integer32,
    Unsigned32
        FROM SNMPv2-SMI
    lgpPdu,
    liebertPduModuleReg
        FROM LIEBERT-GP-REGISTRATION-MIB
    ;

-- =============================================================================
-- Module Identification and Registration
-- =============================================================================

liebertGlobalProductsPduModule MODULE-IDENTITY
  LAST-UPDATED "200807020000Z"
  ORGANIZATION "Emerson Network Power/Liebert Corporation"
  CONTACT-INFO
      "Contact:   Technical Support

      Postal:
      Liebert Corporation
      1050 Dearborn Drive
      P.O. Box 29186
      Columbus OH, 43229
      US

      Tel: +1 (800) 222-5877

      E-mail: liebert.monitoring@emerson.com
      Web:    www.liebert.com

      Author:  Keith Sarbaugh"

   DESCRIPTION
      "The MIB module used to register Liebert POWER related SNMP OIDs.

      Copyright 2008-2008 Liebert Corporation. All rights reserved.
      Reproduction of this document is authorized on the condition
      that the forgoing copyright notice is included.

      This Specification is supplied 'AS IS' and Liebert Corporation
      makes no warranty, either express or implied, as to the use,
      operation, condition, or performance of the Specification."

   REVISION "200807020000Z"
   DESCRIPTION
    "Initial Version"

   ::= { liebertPduModuleReg 1 }

-- =============================================================================
--  lgpPdu - Liebert Power Distribution Registrations
-- =============================================================================

-- -----------------------------------------------------------------------------
-- PDU Global Data and Control Information
-- -----------------------------------------------------------------------------

lgpPduGlobalData OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains data and control associated with PDU's controlled
         by this agent.  Data in this sub-tree will affect the behavior of all
         PDU's controlled by this agent."
    REFERENCE
        "The registrations for the objects in this sub-tree are
         defined below."
    ::= { lgpPdu 5 }

lgpPduEntrySWOverTemperatureProtectionConfig OBJECT-TYPE
    SYNTAX      INTEGER
    {
        local(0),
        array(1)
    }
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "This configures the scope of behavior for the PDU Software Over 
        Temperature Protection feature.  
        See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature
        and get further information about what actions will be performed.

            local (0)
               Only receptacles on the PDU with the alarming temperature sensor 
               will be affected.
            array (1)
               All receptacles in the PDU array will be affected, regardless of 
               which PDU the alarming temperature sensor is connected to.
        "
    ::= { lgpPduGlobalData 5 }

lgpPduEntrySWOverTemperatureProtectionDelay OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Seconds"
    MAX-ACCESS  read-write
    STATUS      current
    DESCRIPTION
        "This sets the delay for the PDU Software Over Temperature Protection 
        feature.  This value determines the amount of time to delay, after the
        high temperature alarm becomes active, before taking action on the 
        enabled receptacles.  If the high temperature alarm becomes inactive
        before the expiration of the delay time, no action will be taken on 
        the enabled receptacles.  
        See lgpPduRcpEntrySwOverTemperatureProtection to enable this feature
        and get further information about what actions will be performed.
        "
    ::= { lgpPduGlobalData 10 }

-- -----------------------------------------------------------------------------

-- PDU Group Information

-- -----------------------------------------------------------------------------

lgpPduCluster OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains information about PDU clusters.  Clusters are
         groups of PDU's under a single monitoring or control domain."
    REFERENCE
        "The registrations for the objects in this sub-tree are
         defined below."
    ::= { lgpPdu 10 }

lgpPduGrpSysStatus OBJECT-TYPE
SYNTAX      Unsigned32
MAX-ACCESS  read-only
STATUS      current
DESCRIPTION
    "This value represents a bit-field of the various operational
     states of the PDUs that are part of the cluster of PDUs
     being monitored by this agent.

     This value is the bit-wise logical OR of all of the
     'lgpPduEntrySysStatus' columns in the 'lgpPduTable'
     which represents the combined statuses of all PDUs for this agent.

     Note the bit-position is given parenthetically next to the operational
     state in the description below.  The bit position is big-endian
     (least significant digit is the right-most digit).  The state is
     present in the PDU when the bit is on (value = 1).

     The value is a logical OR of all of the following potential states of
     each PDU in the cluster.

         normalOperation(1)
             One or more PDUs in the cluster are operating normally with no
             active warnings or alarms.
         startUp(2)
             One or more PDUs are in the startup state (initializing).  Control
             and monitoring operations may be inhibited or unavailable
             while the PDU is in this state.  This state will clear
             automatically when the PDU(s) are fully initialized and ready to
             accept control and monitoring commands.
         unknownNoSupport(4)
             The state of one or more PDUs are not known at this time or
             there is no support for this piece of information from 1 or more
             PDUs in the cluster/group.
         normalWithWarning(8)
             One or more PDUs are operating normally with one or more active
             warnings.  Appropriate personnel should investigate the
             warning(s) as soon as possible and take appropriate action.
         normalWithAlarm(16)
             One or more PDUs are operating normally with one or more active
             alarms.  Appropriate personnel should investigate the alarm(s)
             as soon as possible and take appropriate action.
         abnormalOperation(32)
            One ore more PDUs are operating abnormally.  There is a
            failure within the system that is unexpected under normal
            operating conditions.  Appropriate personnel should investigate
            the cause as soon as possible.  The normal functioning of
            the system is likely inhibited.
         unknownCommFailure(64)
            The state of one or more PDUs are not known due to a communications
            failure between the PDU hardware and the communications
            module.  This state is usually indicative of a hardware
            problem.
     "
::= { lgpPduCluster 5 }

-- -----------------------------------------------------------------------------

-- Power Distribution (PDU) Table.

-- -----------------------------------------------------------------------------

lgpPduTableCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of PDUs being monitored by this agent.  This is the
         number of entries in the lgpPduTable."
    ::= { lgpPdu 19 }

lgpPduTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of PDU entries.
         The table contains zero, one, or many rows, depending upon the number
         of PDUs being monitored.  The Network Management System (NMS)
         cannot create or delete rows in the table. The rows are created by
         the agent based upon the number of PDUs being managed.
         Each row in the table represents a PDU in the system."
    ::= { lgpPdu 20 }

    lgpPduEntry OBJECT-TYPE
        SYNTAX      LgpPduEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the columns to be populated in the
             'lgpPduTable'.  Each column represents an attribute of a PDU.
             This table is indexed by the PDU identifier that is unique
             within the agent.
            "
        INDEX
        {
            lgpPduEntryIndex
        }
        ::= { lgpPduTable 1 }

    LgpPduEntry ::= SEQUENCE
    {
            lgpPduEntryIndex               Unsigned32,
            lgpPduEntryId                  Unsigned32,
            lgpPduEntryUsrLabel            DisplayString,
            lgpPduEntrySysAssignLabel      DisplayString,
            lgpPduEntryPositionRelative    Unsigned32,
            lgpPduEntrySysStatus           Unsigned32,
            lgpPduEntryUsrTag1             DisplayString,
            lgpPduEntryUsrTag2             DisplayString,
            lgpPduEntrySerialNumber        DisplayString,
            lgpPduEntryRbCount             Unsigned32,
            lgpPduEntrySWOverCurrentProtection INTEGER
    }

    lgpPduEntryIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is the index that indicates the row of the 'lgpPduTable'."
        ::= { lgpPduEntry 1 }

    lgpPduEntryId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is an internal index representing a unique identifier for
             each PDU represented by this agent.  The value is assigned
             by the agent."
        ::= { lgpPduEntry 5 }

    lgpPduEntryUsrLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This is a user assigned label representing the PDU."
        ::= { lgpPduEntry 10 }

    lgpPduEntrySysAssignLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "System assigned identifier representing the PDU. The value
             is independent of any user assigned label or tag. The exact format
             of this label is system dependent and is subject to change,
             therefore, it should not be referenced for programmatic use."
        ::= { lgpPduEntry 15 }

    lgpPduEntryPositionRelative OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Count"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is a one-based value that indicates the PDU's relative
             position within a rack or other enclosing entity."
        ::= { lgpPduEntry 20 }

    lgpPduEntrySysStatus OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This value represents a bit-field of the various operational
             states of the PDU. The value is a logical OR of all of the
             following potential states of the PDU.  Note the bit-position
             is given parenthetically next to the operational state in the
             description below.  The bit position is assumed to be a big-endian
             format (least significant digit is the right-most digit).  The
             state is present in the PDU when the bit is on (value = 1).

             normalOperation(1)
                 The PDU is operating normally with no active warnings or alarms.
             startUp(2)
                 The PDU is in the startup state (initializing).  Control
                 and monitoring operations maybe inhibited or unavailable
                 while the PDU is in this state.  This state will clear
                 automatically when the PDU(s) are fully initialized and
                 ready to accept control and monitoring commands.
             normalWithWarning(8)
                 The PDU is operating normally with one or more active
                 warnings.  Appropriate personnel should investigate the
                 warning(s) as soon as possible and take appropriate action.
             normalWithAlarm(16)
                 The PDU is operating normally with one or more active
                 alarms.  Appropriate personnel should investigate the alarm(s)
                 as soon as possible and take appropriate action.
             abnormalOperation(32)
                The PDU is operating abnormally.  That is there is some
                failure within the system that is unexpected under normal
                operating conditions.  Appropriate personnel should investigate
                the cause as soon as possible.  The normal functioning of
                the system is likely inhibited.
             "
        ::= { lgpPduEntry 25 }

    lgpPduEntryUsrTag1 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This is a user assigned Tag for the PDU.  This value may be
             useful for end-user grouping or asset tracking purposes.
             The value for this tag does not need to be unique for this
             unit or across other units."
        ::= { lgpPduEntry 35 }

    lgpPduEntryUsrTag2 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This is a user assigned Tag for the PDU.  This value may be
             useful for end-user grouping or asset tracking purposes.
             The value for this tag does not need to be unique for this
             unit or across other units."
        ::= { lgpPduEntry 40 }

    lgpPduEntrySerialNumber OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "System assigned serial number for this PDU.  This number is
             assigned at time of manufacture, is globally unique with respect
             to all PDU units."
        ::= { lgpPduEntry 45 }

    lgpPduEntryRbCount OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Count"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Number of receptacle branches (Rb) within this PDU."
        ::= { lgpPduEntry 50 }

    lgpPduEntrySWOverCurrentProtection OBJECT-TYPE
        SYNTAX      INTEGER
        {
            disabled(0),
            enable(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This is the PDU Software Over Current Protection feature which will
             prevent unused receptacles from turning on when the
             'PDU Over Current Warning' or 'PDU Over Current Alarm' threshold
             is violated. Such receptacles shall get locked to prevent any user
             from switching them ON. Only device-admin shall have the authorization
             to unlock such receptacles.
             If the feature is enabled, in case of PDU Over Current Warning or Alarm condition,
             following action will be taken on the receptacles:
                a. Locked & OFF  No change
                b. Locked & ON -  No change
                c. UnLocked & OFF  Receptacle shall be locked
                d. Unlocked & ON  If the receptacle is being used (current>0), no change.
                   If that outlet is being unused(current=0), turn it off and lock it in that position.

             No action will be taken if the feature is disabled.

             Note: Only applicable to PDU models where receptacle measurement and control is supported.
             Not applicable for PDU models that support only branch monitoring.

         disabled
              This function is disabled.
         enable
              This function is enabled."
        ::= { lgpPduEntry 55 }
-- -----------------------------------------------------------------------------
-- PDU Power Source.
-- -----------------------------------------------------------------------------

lgpPduPowerSource OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains information about PDU power sources."
    REFERENCE
        "The registrations for the objects in this sub-tree are
         defined below."
    ::= { lgpPdu 30 }

lgpPduPsTableCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of power sources in the lgpPduPsTable."
    ::= { lgpPduPowerSource 19 }

lgpPduPsTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduPsEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of the PDU's power source(s).
         The table contains zero, one, or more rows, depending
         upon the number of PDUs being monitored and the number of
         power sources installed for each PDU.
         The NMS cannot create or delete rows in the table. The rows are
         created by the agent based upon the capabilities of the PDUs
         being monitored.  Each row in the table represents a PDU's
         Power Source."
    ::= { lgpPduPowerSource 20 }

    lgpPduPsEntry OBJECT-TYPE
        SYNTAX      LgpPduPsEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduPsTable' (Power Source Table).
             This table is indexed by both the 'lgpPduEntryIndex' which is
             the sole index into the 'lgpPduTable' and the 'lgpPduPsEntryIndex'
             which is a unique identifier for the Power Source within a
             given PDU.  Taken together these two indexes uniquely identify
             a Power Source within this agent.
            "
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduPsEntryIndex
        }
        ::= { lgpPduPsTable 1 }

    LgpPduPsEntry ::= SEQUENCE
    {
        lgpPduPsEntryIndex                        Unsigned32,
        lgpPduPsEntryId                           Unsigned32,
        lgpPduPsEntrySysAssignLabel               DisplayString,
        lgpPduPsEntryModel                        DisplayString,
        lgpPduPsEntryWiringType                   INTEGER,
        lgpPduPsEntryEpInputRated                 Unsigned32,
        lgpPduPsEntryEcInputRated                 Unsigned32,
        lgpPduPsEntryFreqRated                    Unsigned32,
        lgpPduPsEntryEnergyAccum                  Unsigned32,
        lgpPduPsEntrySerialNum                    DisplayString,
        lgpPduPsEntryFirmwareVersion              DisplayString,
        lgpPduPsEntryPwrTotal                     Unsigned32,
        lgpPduPsEntryEcNeutral                    Unsigned32,
        lgpPduPsEntryEcNeutralThrshldOvrWarn      Unsigned32,
        lgpPduPsEntryEcNeutralThrshldOvrAlarm     Unsigned32,
        lgpPduPsEntryUnbalancedLoadThrshldAlarm   Unsigned32,
        lgpPduPsEntryApTotal                      Unsigned32,
        lgpPduPsEntryPfTotal                      Integer32
    }

    lgpPduPsEntryIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is a unique identifier for the Power Source within a
             given PDU. This is one of two indexes used to indicate the row of
             the 'lgpPduTable'."
        ::= { lgpPduPsEntry 5 }

    lgpPduPsEntryId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is a unique entry id representing a given PDU power source
             for the PDU."
        ::= { lgpPduPsEntry 10 }

    lgpPduPsEntrySysAssignLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "System assigned identifier for this power source.  The value
             is independent of any user assigned label or tag. The exact format
             of this label is system dependent and is subject to change,
             therefore, it should not be referenced for programmatic use."
        ::= { lgpPduPsEntry 15 }

    lgpPduPsEntryModel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the model name (identifier) of the power supply."
        ::= { lgpPduPsEntry 20 }

    lgpPduPsEntryWiringType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            single-phase-3-wire-L1-N-PE(1),
            two-phase-3-wire-L1-L2-PE(2),
            three-phase-4-wire-L1-L2-L3-PE(3),
            three-phase-5-wire-L1-L2-L3-N-PE(4),
            two-phase-4-wire-L1-L2-N-PE(5)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The PDU's power supply physical wiring type.
                not-specified
                    The type has not been specified/configured.  The end_user
                    must configure this object to specify the physical wiring
                    type.
                single-phase-3-wire-L1-N-PE
                    Single Phase input with 3 wires (Line 1, Neutral and
                    Protective Earth).
                two-phase-3-wire-L1-L2-PE
                    Two Phase input with 3 wires (Line 1, Line 2, and
                    Protective Earth).
                three-phase-4-wire-L1-L2-L3-PE
                    Three Phase input with 4 wires (Line 1, Line 2, Line 3,
                    and Protective Earth).
                three-phase-5-wire-L1-L2-L3-N-PE
                    Three Phase input with 5 wires (Line 1, Line 2, Line 3,
                    Neutral and Protective Earth).
                two-phase-4-wire-L1-L2-N-PE
                    Two Phase input with 4 wires (Line 1, Line 2, Neutral,
                    and Protective Earth)."
        ::= { lgpPduPsEntry 25 }

    lgpPduPsEntryEpInputRated OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltRMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Rated Input Line Voltage for the power source (i.e. this is the
             nominal line input voltage; it is NOT a measured voltage).

             The value is defined to be the rated line voltage
             (either line-to-neutral or line-to-line depending upon the
             power source's type)."
        ::= { lgpPduPsEntry 30 }

    lgpPduPsEntryEcInputRated OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the rated input line current for the module
             (it is NOT the measured current)."
        ::= { lgpPduPsEntry 35 }

    lgpPduPsEntryFreqRated OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Hertz"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Rated input line frequency for this power source
             (i.e. This is the expected line frequency; it is NOT a
             measured frequency; it is typically 50 Hz or 60 Hz)."
        ::= { lgpPduPsEntry 40 }

    lgpPduPsEntryEnergyAccum OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Kilowatt-Hour"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Total accumulated energy, measured at the power source input, since
             the last energy reset. Writing a value of 0 (zero) to this
             causes the accumulated energy to be reset. Writing a non-zero
             value is invalid and shall result in a write error and the
             total energy value remains unchanged.

             If the energy has not been reset and has not wrapped,
             then this is the total energy since installation.

             This value persists across boot events."
        ::= { lgpPduPsEntry 50 }

    lgpPduPsEntrySerialNum OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is a unique serial number of the power supply.  This number
             is assigned to the power supply at the time of manufacture."
        ::= { lgpPduPsEntry 55 }

    lgpPduPsEntryFirmwareVersion OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the version of the firmware installed on the PDU's
             power supply."
        ::= { lgpPduPsEntry 60 }

    lgpPduPsEntryPwrTotal OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Watt"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Total input power for this power supply.  This is the sum of the
             power for all phases"
        ::= { lgpPduPsEntry 65 }

    lgpPduPsEntryEcNeutral OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The neutral current measured at the PDU's power source."
        ::= { lgpPduPsEntry 70 }

    lgpPduPsEntryEcNeutralThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current warning is activated. If the
             measured neutral current (lgpPduPsEntryEcNeutral) is above this
             percentage of the full scale rated value
             (lgpPduPsEntryEcInputRated), an over neutral current warning
             (lgpConditionSource1NeutralOverCurrent) is activated."
        ::= { lgpPduPsEntry 75 }

    lgpPduPsEntryEcNeutralThrshldOvrAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current alarm is activated. If the
             measured neutral current (lgpPduPsEntryEcNeutral) is above this
             percentage of the full scale rated value
             (lgpPduPsEntryEcInputRated), an over neutral current alarm
             (lgpConditionSource1NeutralOverCurrent) is activated."
        ::= { lgpPduPsEntry 80 }

    lgpPduPsEntryUnbalancedLoadThrshldAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The parameter is for setting the maximum acceptable percentage of
             'Unbalanced Load' between any two phases. This setting shall
             trigger an alarm when the % load between any two phases varies by
             a percentage higher than this configurable value. If this value is
             0% then the alarm would be deactivated."
        ::= { lgpPduPsEntry 85 }

    lgpPduPsEntryApTotal OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltAmp"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Total Apparent power for this power supply.  This is the sum of the
             apparent power for all phases"
        ::= { lgpPduPsEntry 90 }

    lgpPduPsEntryPfTotal OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.01 Power Factor"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Total power factor, which is real power/apparent power for all
             phases combined. This is the sum of the real power for all phases
             divided by the sum of the apparent power for all phases."
        ::= { lgpPduPsEntry 95 }
-- -----------------------------------------------------------------------------

-- PDU - Power Source Line/Phase Table.

-- -----------------------------------------------------------------------------

lgpPduPsLineTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduPsLineEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of PDU's power source line/phase
         measurements. The table contains zero, one, or many rows, depending
         upon the number of PDU's Power Sources being monitored.
         The NMS cannot create or delete rows in the table.
         The rows are created by the agent based upon the capabilities of the
         managed PDU's power supply(s).  Each row in the table represents a
         particular phase/line measurement of a power supply for a
         given PDU."
    ::= { lgpPduPowerSource 40 }

    lgpPduPsLineEntry OBJECT-TYPE
        SYNTAX      LgpPduPsLineEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduPsLineTable'.
             The table is index by three indexes which taken together
             uniquely identify line/phase information for a given power source
             within a PDU.  The 'lgpPduEntryIndex' is an index into the
             'lgpPduTable'.  This identifies the PDU that the power source
             is on.  The 'lgpPduPsEntryIndex' is an index that together with
             the 'lgpPduEntryIndex' uniquely identifies the power source
             within the PDU that the row in this table represents.  The final
             index 'lgpPduPsLineEntryIndex' identifies the particular
             line/phase that the measurement applies to within the identified
             power source."
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduPsEntryIndex,
            lgpPduPsLineEntryIndex
        }
        ::= { lgpPduPsLineTable 1 }

    LgpPduPsLineEntry ::= SEQUENCE
    {
            lgpPduPsLineEntryIndex                Unsigned32,
            lgpPduPsLineEntryId                   Unsigned32,
            lgpPduPsLineEntryLine                 INTEGER,
            lgpPduPsLineEntryEpLNTenths           Unsigned32,
            lgpPduPsLineEntryEpLN                 Unsigned32,
            lgpPduPsLineEntryEc                   Unsigned32,
            lgpPduPsLineEntryEcHundredths         Unsigned32,

            lgpPduPsLineEntryEcThrshldUndrAlarm                         Unsigned32,
            lgpPduPsLineEntryEcThrshldOvrWarn                           Unsigned32,
            lgpPduPsLineEntryEcThrshldOvrAlarm                          Unsigned32,
            lgpPduPsLineEntryEcAvailBeforeAlarm                         Unsigned32,
            lgpPduPsLineEntryEcUsedBeforeAlarm                          Unsigned32,
            lgpPduPsLineEntryEpLL                                       Unsigned32,
            lgpPduPsLineEntryEpLLTenths                                 Unsigned32,
            lgpPduPsLineEntryEcAvailBeforeAlarmHundredths               Unsigned32,
            lgpPduPsLineEntryPwrLN                                      Unsigned32,
            lgpPduPsLineEntryPwrLL                                      Unsigned32,
            lgpPduPsLineEntryApLN                                       Unsigned32,
            lgpPduPsLineEntryApLL                                       Unsigned32,
            lgpPduPsLineEntryPfLN                                       Integer32,
            lgpPduPsLineEntryPfLL                                       Integer32

    }

    lgpPduPsLineEntryIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is the index that indicates the line/phase of the measurements
             in the given row of the 'lgpPduPsLineTable'."
        ::= { lgpPduPsLineEntry 5 }

    lgpPduPsLineEntryId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Unique identifier (within a PDU) for the PDU's power source.
             The object may not be available in non-modular systems."
        ::= { lgpPduPsLineEntry 10 }

    lgpPduPsLineEntryLine OBJECT-TYPE
        SYNTAX      INTEGER
        {
            phase1(1),
            phase2(2),
            phase3(3)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line number (phase) that the measurement represents for all
             measurements in a given row of the table.  Note that this always
             matches the lgpPduPsLineEntryIndex of the same row in the table.
             The line/phases are as follows:

              Line#  Description
              -----  ---------------------------------------------------
                 1   Line 1-N (A) for Line-to-Neutral measurements
                 2   Line 2-N (B) for Line-to-Neutral measurements
                 3   Line 3-N (C) for Line-to-Neutral measurements

                 1   Line 1-2 (A-B) for Line-to-Line measurements
                 2   Line 2-3 (B-C) for Line-to-Line measurements
                 3   Line 3-1 (C-A) for Line-to-Line measurements
             "
        ::= { lgpPduPsLineEntry 15 }

    lgpPduPsLineEntryEpLNTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Volts-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Alternating Current RMS Line to Neutral Electrical Potential
             measurement.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 19 }

    lgpPduPsLineEntryEpLN OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Volts-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Alternating Current RMS Line to Neutral Electrical Potential
             measurement.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 20 }

    lgpPduPsLineEntryEc OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Total input line-to-neutral electrical current.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 21 }

    lgpPduPsLineEntryEcHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Total input line-to-neutral electrical current.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 22 }

    lgpPduPsLineEntryEcThrshldUndrAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an under current alarm is activated.  If
             the measured current (lgpPduPsLineEntryEc) is equal to or below
             this percentage of the full scale rated value
             (lgpPduPsEntryEcInputRated), an under current alarm
             is activated."
        ::= { lgpPduPsLineEntry 35 }

    lgpPduPsLineEntryEcThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current warning is activated.  If
             the measured current (lgpPduPsLineEntryEc) is equal to or over
             this percentage of the full scale rated value
             (lgpPduPsEntryEcInputRated), an over current warning
             is activated."
        ::= { lgpPduPsLineEntry 36 }

    lgpPduPsLineEntryEcThrshldOvrAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current alarm is activated.  If
             the measured current (lgpPduPsLineEntryEc) is equal to or over
             this percentage of the full scale rated value
             (lgpPduPsEntryEcInputRated), an over current alarm
             is activated."
        ::= { lgpPduPsLineEntry 37 }

    lgpPduPsLineEntryEcAvailBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduPsLineEntry 38 }

    lgpPduPsLineEntryEcUsedBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The percent of current utilization relative to the over current
             alarm threshold."
        ::= { lgpPduPsLineEntry 39 }

    lgpPduPsLineEntryEpLL OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Volts-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Line to Line Electrical Potential.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 60 }

    lgpPduPsLineEntryEpLLTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Volts-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Line to Line Electrical Potential.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 61 }

    lgpPduPsLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduPsLineEntry 62 }

    lgpPduPsLineEntryPwrLN OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Watt"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Real Power (Watts).
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 63 }

    lgpPduPsLineEntryPwrLL OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Watt"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-line measurement of the Real Power (Watts).
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 64 }

    lgpPduPsLineEntryApLN OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltAmp"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Apparent Power (VA).
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 65 }

    lgpPduPsLineEntryApLL OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltAmp"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-line measurement of the Apparent Power (VA).
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 66 }

    lgpPduPsLineEntryPfLN OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.01 Power Factor"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Power Factor of the
             power source.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 67 }

    lgpPduPsLineEntryPfLL OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.01 Power Factor"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-line measurement of the Power Factor of the
             power source.
             The line/phase being measured is indicated by the corresponding
             lgpPduPsLineEntryLine value of this row in the table."
        ::= { lgpPduPsLineEntry 68 }

-- -----------------------------------------------------------------------------

-- PDU Receptacle Branch

-- -----------------------------------------------------------------------------

lgpPduReceptacleBranch OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains information about PDU receptacle branches."
    REFERENCE
        "The registrations for the objects in this sub-tree are
         defined below."
    ::= { lgpPdu 40 }

lgpPduRbTableCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of receptacle branches in the lgpPduRbTable."
    ::= { lgpPduReceptacleBranch 19 }

lgpPduRbTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduRbEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of PDU Receptacle branches.
         The table contains zero, one, or many rows, depending
         upon the number of PDUs being managed and how many
         receptacle branches each PDU has installed.
         The NMS cannot create or delete rows in the table. The rows are
         created by the agent based upon the capabilities of the PDUs
         being managed.  Each row in the table represents a receptacle branch
         for a given PDU.  The PDU that a branch is installed
         on is indicated by the column lgpPduEntryIndex.  The branch
         within the lgpPduEntryIndex PDU is indicated by the column
         lgpPduRbEntryIndex."
    ::= { lgpPduReceptacleBranch 20 }

    lgpPduRbEntry OBJECT-TYPE
        SYNTAX      LgpPduRbEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduRbTable'.  The table is indexed
             by both the 'lgpPduEntryIndex' and 'lgpPduRbEntryIndex'.  The
             lgpPduEntryIndex specifies the PDU, defined in the lgpPduTable
             that the branch is on.  The lgpPduRbEntryIndex uniquely identifies
             the branch within that PDU.  Taken together the two indexes
             uniquely identify a branch being monitored by this agent.
            "
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduRbEntryIndex
        }
        ::= { lgpPduRbTable 1 }

    LgpPduRbEntry ::= SEQUENCE
    {
        lgpPduRbEntryIndex                           Unsigned32,
        lgpPduRbEntryId                              Unsigned32,
        lgpPduRbEntryUsrLabel                        DisplayString,
        lgpPduRbEntrySysAssignLabel                  DisplayString,
        lgpPduRbEntryPositionRelative                Unsigned32,
        lgpPduRbEntrySerialNum                       DisplayString,
        lgpPduRbEntryModel                           DisplayString,
        lgpPduRbEntryFirmwareVersion                 DisplayString,
        lgpPduRbEntryUsrTag1                         DisplayString,
        lgpPduRbEntryUsrTag2                         DisplayString,
        lgpPduRbEntryReceptacleType                  INTEGER,
        lgpPduRbEntryCapabilities                    INTEGER,
        lgpPduRbEntryLineSource                      INTEGER,
        lgpPduRbEntryRcpCount                        Unsigned32,
        lgpPduRbEntryEpRated                         Unsigned32,
        lgpPduRbEntryEcRated                         Unsigned32,
        lgpPduRbEntryFreqRated                       Unsigned32,
        lgpPduRbEntryEnergyAccum                     Unsigned32,
        lgpPduRbEntryEpLNTenths                      Unsigned32,
        lgpPduRbEntryPwr                             Unsigned32,
        lgpPduRbEntryAp                              Unsigned32,
        lgpPduRbEntryPf                              Integer32,
        lgpPduRbEntryEcHundredths                    Unsigned32,
        lgpPduRbEntryEcThrshldUndrAlm                Unsigned32,
        lgpPduRbEntryEcThrshldOvrWarn                Unsigned32,
        lgpPduRbEntryEcThrshldOvrAlm                 Unsigned32,
        lgpPduRbEntryEcAvailBeforeAlarmHundredths    Unsigned32,
        lgpPduRbEntryEcUsedBeforeAlarm               Unsigned32,
        lgpPduRbEntryEpLLTenths                      Unsigned32,
        lgpPduRbEntrySwOverCurrentProtection         INTEGER
    }

    lgpPduRbEntryIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is the index that indicates the row of the
             'lgpPduRbTable'"
        ::= { lgpPduRbEntry 1 }

    lgpPduRbEntryId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "A unique id representing the receptacle branch within the
             collection of branches being monitored by this agent.  The
             uniqueness of this id is within the PDUs being managed by
             a single agent."
        ::= { lgpPduRbEntry 5 }

    lgpPduRbEntryUsrLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "A user assigned label representing the receptacle branch."
        ::= { lgpPduRbEntry 8 }

    lgpPduRbEntrySysAssignLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "System assigned identifier for this receptacle branch.  The value
             is independent of any user assigned label or tag. The exact format
             of this label is system dependent and is subject to change,
             therefore, it should not be referenced for programmatic use."
        ::= { lgpPduRbEntry 20 }

    lgpPduRbEntryPositionRelative OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Count"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is a one-based value that indicates the relative
             position of the branch within the PDU."
        ::= { lgpPduRbEntry 25 }

    lgpPduRbEntrySerialNum OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "A globally unique serial number for this branch.  This number
             is assigned to the branch at the time of manufacture and can not
             be modified.  NOTE: Generally only PDUs with replaceable
             receptacle branches will have serial numbers."
        ::= { lgpPduRbEntry 30 }

    lgpPduRbEntryModel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the model designation for this receptacle branch."
        ::= { lgpPduRbEntry 35 }

    lgpPduRbEntryFirmwareVersion OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the firmware version number of the control software
             running on the receptacle branch.  Only PDUs with
             replaceable receptacle branches will typically support this
             object."
        ::= { lgpPduRbEntry 40 }

    lgpPduRbEntryUsrTag1 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This is a user assigned Tag for the receptacle branch.  This
             value may be useful for end-user grouping or asset tracking
             purposes.  The value for this tag does not need to be unique
             for this unit or across other units."
        ::= { lgpPduRbEntry 41 }

    lgpPduRbEntryUsrTag2 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This is a user assigned Tag for the receptacle branch.  This
             value may be useful for end-user grouping or asset tracking
             purposes.  The value for this tag does not need to be unique
             for this unit or across other units."
        ::= { lgpPduRbEntry 42 }

    lgpPduRbEntryReceptacleType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            nema-5-20R-20-Amp(1),
            iec-C13-sheet-F-10-Amp(2),
            iec-C19-sheet-J-16-Amp(3),
            iec-C13-sheet-F-10-Amp-and-iec-C19-sheet-J-16-Amp(4),
            nema-5-20R-20-Amp-and-iec-C13-sheet-F-10-Amp(5),
            nema-5-20R-20-Amp-and-iec-C19-sheet-J-16-Amp(6),
            cee-7-type-E-schuko(7)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This enumeration represents the type of receptacles installed
             on this receptacle branch.  All receptacles on this branch are
             of this type/style.

             not-specified
                 If this value is returned, either the receptacle type has
                 not been specified/configured or the agent monitoring this
                 PDU does not have a SNMP enumeration defined to the type.
            "
        ::= { lgpPduRbEntry 45 }

    lgpPduRbEntryCapabilities OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            no-optional-capabilities(1),
            measurement-only(2),
            measurement-and-control(3),
            control-only(4),
            current-measurement-only(5),
            current-measurement-and-control(6)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Receptacle branch capabilities describes what an individual branch
             is capable of.

             no-optional-capabilities
                 The branch is unable to report measurements and lacks
                 control capabilities.
             measurement-only
                 The branch is capable of reporting multiple measurements.
             measurement-and-control
                 The branch is capable of reporting multiple measurements
                 and controlling the state.
             control-only
                 The branch is capable of controlling the state.
             current-measurement-only
                 The branch is capable of reporting the current/amperage only.
             current-measurement-and-control
                 The branch is capable of reporting the current/amperage and
                 has the ability to control the state."
        ::= { lgpPduRbEntry 50 }

    lgpPduRbEntryLineSource OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            line-1-neutral(1),
            line-2-neutral(2),
            line-3-neutral(3),
            line-1-line-2(4),
            line-2-line-3(5),
            line-3-line-1(6),
            line-1-line-2-and-line-1-neutral(7),
            line-2-line-3-and-line-2-neutral(8),
            line-3-line-1-and-line-3-neutral(9),
            unknown-line-neutral(10),
            unknown-line-line(11)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This represents the line source that is supplying power to this
            receptacle branch.
                not-specified
                    The line source supplying power to the load for this
                    receptacle branch has not been specified/configured.
                line-1-N
                    The load for this receptacle branch is supplied by
                    a line-to-neutral configuration. (line 1 to neutral).
                line-2-N
                    The load for this receptacle branch is supplied by
                    a line-to-neutral configuration. (line 2 to neutral).
                line-3-N
                    The load for this receptacle branch is supplied by
                    a line-to-neutral configuration. (line 3 to neutral).
                line-1-line-2
                    The load for this receptacle branch is supplied by
                    a line-to-line configuration (line 1 to line 2).
                line-2-line-3
                    The load for this receptacle branch is supplied by
                    a line-to-line configuration (line 2 to line 3).
                line-3-line-1
                    The load for this receptacle branch is supplied by
                    a line-to-line configuration (line 3 to line 1).
                line-1-line-2-and-line-1-neutral
                    The load for this mixed receptacle branch is supplied by
                    a line-to-line and line-to-neutral configuration
                    (line 1 to line 2 and line 1 to neutral).
                line-2-line-3-and-line-2-neutral
                    The load for this mixed receptacle branch is supplied by
                    a line-to-line and line-to-neutral configuration
                    (line 2 to line 3 and line 2 to neutral).
                line-3-line-1-and-line-3-neutral
                    The load for this mixed receptacle branch is supplied by
                    a line-to-line and line-to-neutral configuration
                    (line 3 to line 1 and line 3 to neutral).
                unknown-line-neutral
                    The load for this branch is supplied by
                    a line-to-neutral configuration. The system is unable to
                    determine which lines are supporting the load.
                unknown-line-line
                    The load for this branch is supplied by
                    a line-to-line configuration. The system is unable to
                    determine which lines are supporting the load.
            "
        ::= { lgpPduRbEntry 55 }

    lgpPduRbEntryRcpCount OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Count"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The number of receptacles on this receptacle branch."
        ::= { lgpPduRbEntry 60 }

    lgpPduRbEntryEpRated OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltRMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Rated Line Voltage for the receptacle branch and its associated
             receptacles (i.e. This is the nominal line voltage that is
             available to the connected load; it is NOT a measured voltage.)"
        ::= { lgpPduRbEntry 70 }

    lgpPduRbEntryEcRated OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the rated input line current for the module
            (it is NOT the measured current)."
        ::= { lgpPduRbEntry 75 }

    lgpPduRbEntryFreqRated OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Hertz"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This is the rated electrical frequency for the receptacle branch
             and its associated receptacles"
        ::= { lgpPduRbEntry 80 }

    lgpPduRbEntryEnergyAccum OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Kilowatt-Hour"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Total accumulated energy, measured at the receptacle branch input,
             since the last energy reset. Writing a value of 0 (zero) to this
             causes the accumulated energy to be reset. Writing a non-zero
             value is invalid and shall result in a write error and the
             total energy value remains unchanged.

             If the energy has not been reset and has not wrapped, then this
             is the total energy since installation.

             This value persists across boot events.

             NOTE: Resetting this value does not reset the values for the
             individual receptacles."
        ::= { lgpPduRbEntry 85 }

    lgpPduRbEntryEpLNTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 VoltRMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Electrical Potential
             measured in Volts RMS (Root Mean Squared)."
        ::= { lgpPduRbEntry 100 }

    lgpPduRbEntryPwr OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Watt"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Real Power (Wattage)"
        ::= { lgpPduRbEntry 115 }

    lgpPduRbEntryAp OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltAmp"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Apparent Power (VA)"
        ::= { lgpPduRbEntry 120 }

    lgpPduRbEntryPf OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.01 Power Factor"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Power Factor of the
             receptacle branches' input."
        ::= { lgpPduRbEntry 125 }

    lgpPduRbEntryEcHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-neutral measurement of the Electrical Current
             measured in Amperes RMS (Root Mean Squared)."
        ::= { lgpPduRbEntry 130 }

    lgpPduRbEntryEcThrshldUndrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an under current alarm is activated.  If
             the measured current (lgpPduRbEntryEc) is equal to or below
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an under current alarm
             is activated"
        ::= { lgpPduRbEntry 135 }

    lgpPduRbEntryEcThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current warning is activated.  If
             the measured current (lgpPduRbEntryEc) is equal to or over
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an over current warning
             is activated"
        ::= { lgpPduRbEntry 140 }

    lgpPduRbEntryEcThrshldOvrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current alarm is activated.  If
             the measured current (lgpPduRbEntryEcLN) is equal to or over
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an over current alarm
             is activated"
        ::= { lgpPduRbEntry 145 }

    lgpPduRbEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduRbEntry 150 }

    lgpPduRbEntryEcUsedBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The percent of current utilization relative to the over current
             alarm threshold."
        ::= { lgpPduRbEntry 160 }

    lgpPduRbEntryEpLLTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 VoltRMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The line-to-line measurement of the Electrical Potential
             measured in Volts RMS (Root Mean Squared)."
        ::= { lgpPduRbEntry 170 }

    lgpPduRbEntrySwOverCurrentProtection OBJECT-TYPE
        SYNTAX      INTEGER
        {
            disable(0),
            enable(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The configuration parameter to enable or disable the Branch
            SW Over Current Protection feature.If the feature is enabled, in case of Over Current Warning or Alarm condition, following action will be taken on the receptacles:
            Locked & On - No Change
            Locked & Off - No Change
            Unlocked & Off - Turn it Off and Lock it
            Unlocked & On - If load present, No Change. If no load, turn it Off and Lock it.
            No action will be taken if the feature is disabled.
            Note: Only applicable to PDU models where receptacle measurement and control is possible. Not applicable to branch monoitoring models

         disabled
              This function is disabled.
         enable
              This function is enabled."

        ::= { lgpPduRbEntry 175 }

-- -----------------------------------------------------------------------------

-- PDU Receptacle Branch - Line/Phase Measurements.

-- -----------------------------------------------------------------------------

lgpPduRbLineTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduRbLineEntry
    MAX-ACCESS  not-accessible
    STATUS      deprecated
    DESCRIPTION
        "This table contains a list of PDU receptacle branch line/phase
         measurements. The table contains zero, one, or many rows, depending
         upon the number of PDUs and the number of receptacle branches
         on each PDU that are being monitored.

         The NMS cannot create or delete rows in the table.
         The rows are created by the agent based upon the capabilities of the
         PDU(s) being monitored.  Each row in the table represents a
         particular phase/line measurement of a PDU Receptacle
         Branch.

         Rows in the table are uniquely identified by three indexes representing
         respectively the PDU (lgpPduEntryIndex), the receptacle
         branch (lgpPduRbEntryIndex) and the line/phase being
         measured (lgpPduRbLineEntryIndex).
         "
    ::= { lgpPduReceptacleBranch 40 }

    lgpPduRbLineEntry OBJECT-TYPE
        SYNTAX      LgpPduRbLineEntry
        MAX-ACCESS  not-accessible
        STATUS      deprecated
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduRbLineTable'.  The table is
             indexed by three indexes.  The 'lgpPduEntryIndex' references
             a PDU in the 'lgpPduTable' to which this receptacle branch
             line/phase measurement belongs.  The 'lgpPduRbEntryIndex' together
             with the 'lgpPduEntryIndex' references the receptacle branch
             in the 'lgpPduRbTable'.  The 'lgpPduRbLineEntryIndex' represents
             the line/phase of the measurements in the row of this table.
             Together these three indexes uniquely identify a phase/line
             measurement on a receptacle branch within a PDU being monitored
             by this agent.
            "
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduRbEntryIndex,
            lgpPduRbLineEntryIndex
        }
        ::= { lgpPduRbLineTable 1 }

    LgpPduRbLineEntry ::= SEQUENCE
    {
        lgpPduRbLineEntryIndex                           Unsigned32,
        lgpPduRbLineEntryId                              Unsigned32,
        lgpPduRbLineEntryLine                            INTEGER,
        lgpPduRbLineEntryEpLNTenths                      Unsigned32,
        lgpPduRbLineEntryEpLN                            Unsigned32,
        lgpPduRbLineEntryEc                              Unsigned32,
        lgpPduRbLineEntryPwr                             Unsigned32,
        lgpPduRbLineEntryAp                              Unsigned32,
        lgpPduRbLineEntryPf                              Integer32,
        lgpPduRbLineEntryEcHundredths                    Unsigned32,
        lgpPduRbLineEntryEcThrshldUndrAlm                Unsigned32,
        lgpPduRbLineEntryEcThrshldOvrWarn                Unsigned32,
        lgpPduRbLineEntryEcThrshldOvrAlm                 Unsigned32,
        lgpPduRbLineEntryEcAvailBeforeAlarmHundredths    Unsigned32,
        lgpPduRbLineEntryEcAvailBeforeAlarm              Unsigned32,
        lgpPduRbLineEntryEcUsedBeforeAlarm               Unsigned32,
        lgpPduRbLineEntryEpLL                            Unsigned32,
        lgpPduRbLineEntryEpLLTenths                      Unsigned32
    }

    lgpPduRbLineEntryIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      deprecated
        DESCRIPTION
            "This is the index that indicates the row of the
             'lgpPduRbLineTable'"
        ::= { lgpPduRbLineEntry 1 }

    lgpPduRbLineEntryId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "Runtime assigned branch identifier."
        ::= { lgpPduRbLineEntry 5 }

    lgpPduRbLineEntryLine OBJECT-TYPE
        SYNTAX      INTEGER
        {
            phase1(1),
            phase2(2),
            phase3(3)
        }
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line number or phase that the measurement for this
             receptacle branch represents for each measurement in this row of
             the table.  The phases are as follows:
              Line#  Description
              -----  ---------------------------------------------------
                 1   Line 1-N (A) for Line-to-Neutral measurements
                 2   Line 2-N (B) for Line-to-Neutral measurements
                 3   Line 3-N (C) for Line-to-Neutral measurements

                 1   Line 1-2 (A-B) for Line-to-Line measurements
                 2   Line 2-3 (B-C) for Line-to-Line measurements
                 3   Line 3-1 (C-A) for Line-to-Line measurements
             "
        ::= { lgpPduRbLineEntry 10 }

    lgpPduRbLineEntryEpLNTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 VoltRMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Electrical Potential
             measured in Volts RMS (Root Mean Squared)."
        ::= { lgpPduRbLineEntry 19 }

    lgpPduRbLineEntryEpLN OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltRMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Electrical Potential
             measured in Volts RMS (Root Mean Squared)."
        ::= { lgpPduRbLineEntry 20 }

    lgpPduRbLineEntryEc OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Electrical Current
             measured in Amperes RMS (Root Mean Squared)."
        ::= { lgpPduRbLineEntry 21 }

    lgpPduRbLineEntryPwr OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Watt"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Real Power (Wattage)"
        ::= { lgpPduRbLineEntry 22 }

    lgpPduRbLineEntryAp OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltAmp"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Apparent Power (VA)"
        ::= { lgpPduRbLineEntry 23 }

    lgpPduRbLineEntryPf OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.01 Power Factor"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Power Factor of the
             receptacle branches' input."
        ::= { lgpPduRbLineEntry 24 }

    lgpPduRbLineEntryEcHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-neutral measurement of the Electrical Current
             measured in Amperes RMS (Root Mean Squared)."
        ::= { lgpPduRbLineEntry 25 }

    lgpPduRbLineEntryEcThrshldUndrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "The threshold at which an under current alarm is activated.  If
             the measured current (lgpPduRbLineEntryEc) is equal to or below
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an under current alarm
             is activated"
        ::= { lgpPduRbLineEntry 35 }

    lgpPduRbLineEntryEcThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "The threshold at which an over current warning is activated.  If
             the measured current (lgpPduRbLineEntryEc) is equal to or over
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an over current warning
             is activated"
        ::= { lgpPduRbLineEntry 36 }

    lgpPduRbLineEntryEcThrshldOvrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "The threshold at which an over current alarm is activated.  If
             the measured current (lgpPduRbLineEntryEcLN) is equal to or over
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an over current alarm
             is activated"
        ::= { lgpPduRbLineEntry 37 }

    lgpPduRbLineEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduRbLineEntry 39 }

    lgpPduRbLineEntryEcAvailBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduRbLineEntry 40 }

    lgpPduRbLineEntryEcUsedBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Percent"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The percent of current utilization relative to the over current
             alarm threshold."
        ::= { lgpPduRbLineEntry 41 }

    lgpPduRbLineEntryEpLL OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "VoltRMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-line measurement of the Electrical Potential
             measured in Volts RMS (Root Mean Squared)."
        ::= { lgpPduRbLineEntry 60 }

    lgpPduRbLineEntryEpLLTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 VoltRMS"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The line-to-line measurement of the Electrical Potential
             measured in Volts RMS (Root Mean Squared)."
        ::= { lgpPduRbLineEntry 61 }

-- -----------------------------------------------------------------------------

-- PDU Receptacle (RCP) - Table

-- -----------------------------------------------------------------------------

lgpPduReceptacle OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains information about PDU receptacles."
    REFERENCE
        "The registrations for the objects in this sub-tree are
         defined below."
    ::= { lgpPdu 50 }

lgpPduRcpTableCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of receptacles in the lgpPduRcpTable."
    ::= { lgpPduReceptacle 19 }

lgpPduRcpTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduRcpEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of PDU receptacle entries.
         The table contains numerous rows representing an individual
         receptacle, depending upon the number and configuration of
         the PDU(s) being monitored by the agent.

         The NMS cannot create or delete rows in the table. The rows are
         created by the agent based upon the capabilities of the managed
         PDU(s).  Each row in the table represents a receptacle in
         the system.
         "
    ::= { lgpPduReceptacle 20 }

    lgpPduRcpEntry OBJECT-TYPE
        SYNTAX      LgpPduRcpEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduRcpTable'.  This table is indexed
             by three indexes. The 'lgpPduEntryIndex' references a PDU in
             the 'lgpPduTable' that a given row in this table represents.
             The 'lgpPduRbEntryIndex' together with the 'lgpPduEntryIndex'
             specifies a row in the 'lgpPduRbTable' that the receptacle
             belongs.  The 'lgpPduRcpEntryIndex' identifies the particular
             receptacle within the branch.
            "

        INDEX
        {
            lgpPduEntryIndex,
            lgpPduRbEntryIndex,
            lgpPduRcpEntryIndex
        }
        ::= { lgpPduRcpTable 1 }

    LgpPduRcpEntry ::= SEQUENCE
    {
            lgpPduRcpEntryIndex                            Unsigned32,
            lgpPduRcpEntryId                               Unsigned32,
            lgpPduRcpEntryUsrLabel                         DisplayString,
            lgpPduRcpEntryUsrTag1                          DisplayString,
            lgpPduRcpEntryUsrTag2                          DisplayString,
            lgpPduRcpEntrySysAssignLabel                   DisplayString,
            lgpPduRcpEntryPosition                         Unsigned32,
            lgpPduRcpEntryType                             INTEGER,
            lgpPduRcpEntryLineSource                       INTEGER,
            lgpPduRcpEntryCapabilities                     INTEGER,
            lgpPduRcpEntryEp                               Unsigned32,
            lgpPduRcpEntryEpTenths                         Unsigned32,
            lgpPduRcpEntryEc                               Unsigned32,
            lgpPduRcpEntryEcHundredths                     Unsigned32,
            lgpPduRcpEntryPwrOut                           Unsigned32,
            lgpPduRcpEntryApOut                            Unsigned32,
            lgpPduRcpEntryPf                               Unsigned32,
            lgpPduRcpEntryFreq                             Unsigned32,
            lgpPduRcpEntryEnergyAccum                      Unsigned32,
            lgpPduRcpEntryPwrOnDelay                       Unsigned32,
            lgpPduRcpEntryPwrState                         INTEGER,
            lgpPduRcpEntryPwrUpState                       INTEGER,
            lgpPduRcpEntryControl                          INTEGER,
            lgpPduRcpEntryControlLock                      INTEGER,
            lgpPduRcpEntryEcThrshldUnderAlarm              Unsigned32,
            lgpPduRcpEntryEcThrshldOverWarn                Unsigned32,
            lgpPduRcpEntryEcThrshldOverAlarm               Unsigned32,
            lgpPduRcpEntryEcAvailBeforeAlarmHundredths     Unsigned32,
            lgpPduRcpEntryEcAvailBeforeAlarm               Unsigned32,
            lgpPduRcpEntryEcUsedBeforeAlarm                Unsigned32,
            lgpPduRcpEntryEcCrestFactor                    Unsigned32,
            lgpPduRcpEntryBlinkLED                         INTEGER,
            lgpPduRcpEntrySwOverTemperatureProtection      INTEGER,
            lgpPduRcpEntryOperationCondition               INTEGER,
            lgpPduRcpEntryCriticality                      INTEGER,
            lgpPduRcpEntryPostOnDelay                      Unsigned32,
            lgpPduRcpEntryPostOffDelay                     Unsigned32,
            lgpPduRcpEntryAddReceptacleToGroup             OBJECT IDENTIFIER,
            lgpPduRcpEntryRemoveReceptacleFromGroup        OBJECT IDENTIFIER
    }

    lgpPduRcpEntryIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is the index that indicates the receptacle position on the
             receptacle branch.  This along with the other two indexes on the
             lgpPduRcpTable uniquely identify the receptacle in this table."
        ::= { lgpPduRcpEntry 1 }

    lgpPduRcpEntryId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "A runtime assigned receptacle identification number."
        ::= { lgpPduRcpEntry 5 }

    lgpPduRcpEntryUsrLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned label for this receptacle."
        ::= { lgpPduRcpEntry 10 }

    lgpPduRcpEntryUsrTag1 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned Tag to assist in identifying or grouping this
             receptacle within the end-users domain."
        ::= { lgpPduRcpEntry 15 }

    lgpPduRcpEntryUsrTag2 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned Tag to assist in identifying or grouping this
             receptacle within the end-users domain."
        ::= { lgpPduRcpEntry 20 }

    lgpPduRcpEntrySysAssignLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "System assigned identifier representing the receptacle. The value
             is independent of any user assigned label or tag. The exact format
             of this label is system dependent and is subject to change,
             therefore, it should not be referenced for programmatic use."
        ::= { lgpPduRcpEntry 25 }

    lgpPduRcpEntryPosition OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "A number representing the position of the receptacle within the
             receptacle branch."
        ::= { lgpPduRcpEntry 30 }

    lgpPduRcpEntryType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            nema-5-20R-20-Amp(1),
            iec-C13-sheet-F-10-Amp(2),
            iec-C19-sheet-J-16-Amp(3),
            cee-7-type-E-schuko(7)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The type or form of receptacle.  The enumerations are specified
             in well-known industry standard terms and abbreviations."
        ::= { lgpPduRcpEntry 40 }

    lgpPduRcpEntryLineSource OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            line-1-N(1),
            line-2-N(2),
            line-3-N(3),
            line-1-line-2(4),
            line-2-line-3(5),
            line-3-line-1(6),
            unknown-line-neutral(7),
            unknown-line-line(8)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This represents the line source that is supplying power to this
             receptacle.
                not-specified
                    The line source supplying power to the load for this
                    receptacle has not been specified/configured.
                line-1-N
                    The load for this receptacle is supplied by
                    a line-to-neutral configuration. (line 1 to neutral).
                line-2-N
                    The load for this receptacle is supplied by
                    a line-to-neutral configuration. (line 2 to neutral).
                line-3-N
                    The load for this receptacle is supplied by
                    a line-to-neutral configuration. (line 3 to neutral).
                line-1-line-2
                    The load for this receptacle is supplied by
                    a line-to-line configuration (line 1 to line 2).
                line-2-line-3
                    The load for this receptacle is supplied by
                    a line-to-line configuration (line 2 to line 3).
                line-3-line-1
                    The load for this receptacle is supplied by
                    a line-to-line configuration (line 3 to line 1).
                unknown-line-neutral
                    The load for this receptacle is supplied by
                    a line-to-neutral configuration. The system is unable to
                    determine which lines are supporting the load.
                unknown-line-line
                    The load for this receptacle is supplied by
                    a line-to-line configuration. The system is unable to
                    determine which lines are supporting the load.
            "
        ::= { lgpPduRcpEntry 45 }

    lgpPduRcpEntryCapabilities OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            no-optional-capabilities(1),
            measurement-only(2),
            measurement-and-control(3),
            control-only(4),
            current-measurement-only(5),
            current-measurement-and-control(6)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Receptacle capabilities describes what an individual receptacle is
             capable of.

             no-optional-capabilities
                 The receptacle is unable to report measurements and lacks
                 control capabilities.
             measurement-only
                 The receptacle is capable of reporting multiple measurements.
             measurement-and-control
                 The receptacle is capable of reporting multiple measurements
                 and controlling the state.
             control-only
                 The receptacle is capable of controlling the state.
             current-measurement-only
                 The receptacle is capable of reporting the current/amperage
                 only.
             current-measurement-and-control
                 The receptacle is capable of reporting the current/amperage and
                 has the ability to control the state."
        ::= { lgpPduRcpEntry 50 }

    lgpPduRcpEntryEp OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Volts-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Voltage being delivered to the load attached to the receptacle.
             Alternating Current RMS Electrical Potential measurement."
        ::= { lgpPduRcpEntry 55 }

    lgpPduRcpEntryEpTenths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Volts-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Voltage being delivered to the load attached to the receptacle.
             Alternating Current RMS Electrical Potential measurement."
        ::= { lgpPduRcpEntry 56 }

    lgpPduRcpEntryEc OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Current (amperage) being delivered to the load attached to
             the receptacle. Electrical Current is measured in
             Amperes RMS (Root Mean Squared)."
        ::= { lgpPduRcpEntry 60 }

    lgpPduRcpEntryEcHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amp-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Current (amperage) being delivered to the load attached to
             the receptacle. Electrical Current is measured in
             Amperes RMS (Root Mean Squared)."
        ::= { lgpPduRcpEntry 61 }

    lgpPduRcpEntryPwrOut OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Watt"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Real Power (watts) being delivered to the load attached to
             the receptacle."
        ::= { lgpPduRcpEntry 65 }

    lgpPduRcpEntryApOut OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Volt-Amp-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Apparent Power (volt-amps) being delivered to the load
             attached to the receptacle."
        ::= { lgpPduRcpEntry 70 }

    lgpPduRcpEntryPf OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       ".01 Power Factor"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Receptacle Power Factor, which is the ratio of real power
             to apparent power (i.e. ratio of watts to volts-amps)."
        ::= { lgpPduRcpEntry 75 }

    lgpPduRcpEntryFreq OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Hertz"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The measured line frequency being delivered to the load
             attached to the receptacle."
        ::= { lgpPduRcpEntry 80 }

    lgpPduRcpEntryEnergyAccum OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Kilowatt-Hour"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Total accumulated energy, measured at the module input, since
             the last energy reset. Writing a value of 0 (zero) to this
             causes the accumulated energy to be reset. Writing a non-zero
             value is invalid and shall result in a write error and the
             total energy value remains unchanged.

             If the energy has not been reset and has not wrapped,
             then this is the total energy since installation.

             This value persists across boot events."
        ::= { lgpPduRcpEntry 85 }

    lgpPduRcpEntryPwrOnDelay OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Seconds"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The amount of time to wait before power is applied to the
            receptacle after a power strip is turned on or rebooted.
            This can be used to stagger the powering of multiple
            receptacles in order to prevent a large initial current
            draw."
        ::= { lgpPduRcpEntry 90 }

    lgpPduRcpEntryPwrState OBJECT-TYPE
        SYNTAX      INTEGER
        {
            unknown(0),
            off(1),
            on(2),
            off-pending-on-delay(3)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "unknown
                The current power state is unknown.
             off
                The current power state of the receptacle is OFF.
             on
                The current power state of the receptacle is ON.
             off-pending-on-delay
                The current power state of the receptacle is OFF.  The power
                will be ON at the expiration of the ON delay of this
                receptacle."
        ::= { lgpPduRcpEntry 95 }

    lgpPduRcpEntryPwrUpState OBJECT-TYPE
        SYNTAX      INTEGER
        {
            on(1),
            off(2),
            last-state(3)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 'Power Up State' defines the state to which the receptacle shall return 
	    after a power cycle of the PDU.
	
	     on
	   	The receptacle shall be switched to the ON state after the power on delay
                timer (lgpPduRcpEntryPwrOnDelay).
	     off
	   	The receptacle shall be in the OFF state upon power cycle. 
             last-state
	   	The receptacle shall be put to the previous state. Again, on state will be 
		effective only after the power on delay (lgpPduRcpEntryPwrOnDelay)."		
        ::= { lgpPduRcpEntry 96 }

    lgpPduRcpEntryControl OBJECT-TYPE
        SYNTAX      INTEGER
        {
            off(0),
            on(1),
            cycle-power(2)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This object represents the current and persistent (configured)
             power state of the receptacle.  The receptacle can also be
             controlled by writing to this object.
             off
                 The current and persisted (configured) power state of the
                 receptacle is 'off'.  When writing 'off' to this object the
                 receptacle, if ON, will be turned OFF and its persistent
                 (configured) power state will be set to 'off'.
             on
                 The current and persisted (configured) power state of the
                 receptacle is 'on'.  When writing 'on' to this object the
                 receptacle, if 'off', will be turned 'on' and its persistent
                 (configured) power state will be set to 'on'.
             cycle-power
                 The receptacle is currently in a power-cycle state. The
                 power to the receptacle is being turned off momentarily and
                 will then revert to being 'on'.
                 When writing 'cycle-power' to this OBJECT if the receptacle is
                 'on' it will be momentarily turned 'off' and then revert to the
                 'on' state.  The receptacle's persistent (configured) power
                 state will be left unchanged ('on').

                 If the receptacle is OFF writing cycle-power has no
                 affect on the receptacle.
            "
        ::= { lgpPduRcpEntry 100 }

    lgpPduRcpEntryControlLock OBJECT-TYPE
        SYNTAX      INTEGER
        {
            unknown(0),
            unlocked(1),
            locked(2)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This object represents the locked state of the receptacle.

             unknown
                 The lock state of the receptacle is not known at this time.
             locked
                 If the receptacle is 'locked' then its current persisted
                 (configured) state can not be changed.
             unlocked
                 If the receptacle is 'unlocked', then a user with proper
                 permissions may change the receptacles state."
        ::= { lgpPduRcpEntry 105 }

    lgpPduRcpEntryEcThrshldUnderAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an under current alarm is activated.  If
             the measured current (lgpPduRbLineEntryEcLL) is equal to or below
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an under current alarm
             is activated"
        ::= { lgpPduRcpEntry 150 }

    lgpPduRcpEntryEcThrshldOverWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current warning is activated.  If
             the measured current (lgpPduRbLineEntryEcLL) is equal to or over
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an over current warning
             is activated"
        ::= { lgpPduRcpEntry 151 }

    lgpPduRcpEntryEcThrshldOverAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Percent"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The threshold at which an over current alarm is activated.  If
             the measured current (lgpPduRbLineEntryEcLL) is equal to or over
             this percentage of the full scale rated value
             (lgpPduRbEntryEcRated), an over current alarm
             is activated"
        ::= { lgpPduRcpEntry 152 }

    lgpPduRcpEntryEcAvailBeforeAlarmHundredths OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduRcpEntry 159 }

    lgpPduRcpEntryEcAvailBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Amps-AC-RMS"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The amount that the current/amperage may increase from its present
             value before an over current alarm occurs."
        ::= { lgpPduRcpEntry 160 }

    lgpPduRcpEntryEcUsedBeforeAlarm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 Percent"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The percent of current utilization relative to the over current
             alarm threshold."
        ::= { lgpPduRcpEntry 161 }

    lgpPduRcpEntryEcCrestFactor OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.01"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Receptacle current crest factor, which is the peak amplitude of the
             current waveform divided by the RMS value of the waveform."
        ::= { lgpPduRcpEntry 162 }

    lgpPduRcpEntryBlinkLED OBJECT-TYPE
        SYNTAX      INTEGER
        {
            noAction(1),
            blinkLED(2)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Blink the receptacle LED. Writing blinkLED(2) will cause the LED
             to blink for a predefined duration of time. Reading this object
             will always return noAction(1)."
        ::= { lgpPduRcpEntry 200 }

    lgpPduRcpEntrySwOverTemperatureProtection OBJECT-TYPE
        SYNTAX      INTEGER
        {
            disable(0),
            enable(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The configuration parameter to enable or disable the Receptacle
            SW Over Temperature Protection feature
            If the feature is enabled, in case of Over Temperature Alarm condition,
            following action will be taken on the receptacles:
            Locked & Off - No Change
            Unlocked & Off - No Change
            Unlocked & On - Turn it Off.
            Locked & On - Turn it Off and keep it Locked.

            No action will be taken if the feature is disabled."
        ::= { lgpPduRcpEntry 205 }

    lgpPduRcpEntryOperationCondition OBJECT-TYPE
        SYNTAX      INTEGER
        {
            normalOperation(1),
            normalWithWarning(2),
            normalWithAlarm(3),
            abnormal(4)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Receptacle Operating Condition - indicates the condition of the receptacle.

             The operating condition has the following:

             Normal
                 Normal operation without any alarm or warning.
             Alarm
                 An Alarm condition due to over/under current.
             Warning
                 A Warning condition due to over/under current
             Abnormal
                 A condition in which the outlet is in 'Power Off State' but still drawing current."
        ::= { lgpPduRcpEntry 210 }

    lgpPduRcpEntryCriticality OBJECT-TYPE
        SYNTAX      INTEGER
        {
            critical(0),
            notCritical(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The configuration parameter can be used by the user to mark a receptacle as
            critical or non-critical."
        ::= { lgpPduRcpEntry 215 }

    lgpPduRcpEntryPostOnDelay OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Seconds"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 'Post On Delay' is the time interval (in seconds) that the PDU waits after
            a command is issued to switch ON a receptacle before applying power to the receptacle

            A value of zero implies that there is no delay (i.e. the receptacle is turned on
            immediately on command issue)."
        ::= { lgpPduRcpEntry 220 }

    lgpPduRcpEntryPostOffDelay OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "Seconds"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The 'Post Off Delay' is the time interval (in seconds) that the PDU waits after
            a command is issued to switch OFF a receptacle before removing power from the receptacle

            A value of zero implies that there is no delay (i.e. the receptacle is turned off
            immediately on command issue)."
        ::= { lgpPduRcpEntry 225 }

    lgpPduRcpEntryAddReceptacleToGroup OBJECT-TYPE
        SYNTAX      OBJECT IDENTIFIER
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This receptacle can be added to a group by writing a corresponding
             OID to this column.  The OID must be a pointer to the 
             lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable.
             For example, to add this receptacle to group 1, the oid 
             .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to 
             this column."
        ::= { lgpPduRcpEntry 230 }

    lgpPduRcpEntryRemoveReceptacleFromGroup OBJECT-TYPE
        SYNTAX      OBJECT IDENTIFIER
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This receptacle can be removed from a group by writing a corresponding
             OID to this column.  The OID must be a pointer to the 
             lgpPduRcpGroupUsrLabel from the lgpPduRcpGroupTable.
             For example, to remove this receptacle from group 1, the oid 
             .1.3.6.1.4.1.476.1.42.3.8.50.30.10.1.1 would be written to 
             this column."
        ::= { lgpPduRcpEntry 235 }

-- -----------------------------------------------------------------------------
-- PDU Receptacle Group Table
-- -----------------------------------------------------------------------------

lgpPduRcpGroup OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains information about receptacle groups.
         Receptacle groups are supported by some PDU's and allow control of 
         multiple receptacles at a time by issuing commands to an associated 
         receptacle group."
    REFERENCE
        "The registrations for the objects in this sub-tree are
         defined below."
    ::= { lgpPduReceptacle 30 }

lgpPduRcpGroupTableCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of receptacle groups (rows) in the lgpPduRcpGroupTable."
    ::= { lgpPduRcpGroup 9 }

lgpPduRcpGroupTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduRcpGroupEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of the possible receptacle groups
         that can be created.  The table contains a fixed number of rows, which
         is the maximum number of receptacle groups that can be used."
    ::= { lgpPduRcpGroup 10 }

    lgpPduRcpGroupEntry OBJECT-TYPE
        SYNTAX      LgpPduRcpGroupEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduRcpGroupTable'.
             This table is indexed by lgpPduRcpGroupIndex.
            "
        INDEX
        {
            lgpPduRcpGroupIndex
        }
        ::= { lgpPduRcpGroupTable 1 }

    LgpPduRcpGroupEntry ::= SEQUENCE
    {
        lgpPduRcpGroupIndex                       Unsigned32,
        lgpPduRcpGroupUsrLabel                    DisplayString,
        lgpPduRcpGroupDeleteGroup                 INTEGER,
        lgpPduRcpGroupControlPower                INTEGER,
        lgpPduRcpGroupControlLock                 INTEGER,
        lgpPduRcpGroupBlinkLED                    INTEGER
    }

    lgpPduRcpGroupIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is an index into the table.  There will always be 64 rows,
             each representing a separate receptacle group.
            "
        ::= { lgpPduRcpGroupEntry 1 }

    lgpPduRcpGroupUsrLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned identifier for this receptacle group."
        ::= { lgpPduRcpGroupEntry 10 }

    lgpPduRcpGroupDeleteGroup OBJECT-TYPE
        SYNTAX      INTEGER
        {
            no-action(0),
            delete-receptacle-group(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This column will delete the receptacles from the group when written to."
        ::= { lgpPduRcpGroupEntry 20 }

    lgpPduRcpGroupControlPower OBJECT-TYPE
        SYNTAX      INTEGER
        {
            no-action(0),
            off(1),
            on(2),
            cycle-power(3)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This column controls the power to the group of receptacles.  The corresponding
             operation will be performed on all receptacles that have been added to the group.            
            "
        ::= { lgpPduRcpGroupEntry 30 }

    lgpPduRcpGroupControlLock OBJECT-TYPE
        SYNTAX      INTEGER
        {
            no-action(0),
            unlock(1),
            lock(2)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This column controls the locking of the group of receptacles.  The corresponding
             operation will be performed on all receptacles that have been added to the group.            
            "
        ::= { lgpPduRcpGroupEntry 40 }

    lgpPduRcpGroupBlinkLED OBJECT-TYPE
        SYNTAX      INTEGER
        {
            no-action(0),
            blinkLED(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "This column will blink the LED's associated with all receptacles that are part of
             the group.            
            "
        ::= { lgpPduRcpGroupEntry 50 }

-- -----------------------------------------------------------------------------
-- PDU Receptacle Group Display Table
-- -----------------------------------------------------------------------------

lgpPduRcpGroupDisplayTableCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of rows currently in the lgpPduRcpGroupDisplayTable."
    ::= { lgpPduRcpGroup 19 }

lgpPduRcpGroupDisplayTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduRcpGroupDisplayEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table is used to display which receptacle groups are currently
         defined and which receptacles are associated with each group.
         The table will have 0 rows when no receptacles have been added to any receptacle
         groups.  If a single receptacle has been added to 2 different groups, 
         there will be 2 rows in the table.
        "
    ::= { lgpPduRcpGroup 20 }

    lgpPduRcpGroupDisplayEntry OBJECT-TYPE
        SYNTAX      LgpPduRcpGroupDisplayEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduRcpGroupDisplayTable'.
             This table is indexed by two indexes. 
             The 'lgpPduRcpGroupIndex' references a receptacle group in
             the 'lgpPduRcpGroupTable' that a given row in this table represents.
             The 'lgpPduEntryIndex' references a PDU in the 'lgpPduTable' 
             that identifies the particular PDU receptacle list 
             within the receptacle group.
            "
        INDEX
        {
            lgpPduRcpGroupIndex,
            lgpPduEntryIndex
        }
        ::= { lgpPduRcpGroupDisplayTable 1 }

    LgpPduRcpGroupDisplayEntry ::= SEQUENCE
    {
        lgpPduRcpGroupDisplayIndex                Unsigned32,
        lgpPduRcpGroupDisplayGroup          DisplayString
    }

    lgpPduRcpGroupDisplayIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is an index into the table.  There can be zero or more rows
             in this table."
        ::= { lgpPduRcpGroupDisplayEntry 10 }

    lgpPduRcpGroupDisplayGroup OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "This column displays the PDU receptacle list of the specified 
             receptacle group.  The value in this column is a comma delimted string that decribes
		  the list of receptacles of a PDU that are members of the receptacle group.
             For example, if receptacles 1 and 3 of branch A and receptacles 2 and 4 
             of branch B are members of the receptacle group, this column 
             would show: A-1,A-3,B-2,B-4"
        ::= { lgpPduRcpGroupDisplayEntry 20 }

-- -----------------------------------------------------------------------------
-- PDU Auxiliary Sensors
-- -----------------------------------------------------------------------------

lgpPduAuxiliarySensors OBJECT-IDENTITY
    STATUS      current
    DESCRIPTION
        "This sub-tree contains information about PDU Auxiliary Sensors."
    REFERENCE
        "The registrations for the objects in this sub-tree are
        defined below."
    ::= { lgpPdu 60 }

lgpPduAuxSensorCount OBJECT-TYPE
    SYNTAX      Unsigned32
    UNITS       "Count"
    MAX-ACCESS  read-only
    STATUS      current
    DESCRIPTION
        "Number of auxiliary sensors in the lgpPduAuxSensorTable."
    ::= { lgpPduAuxiliarySensors 5 }

lgpPduAuxSensorTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduAuxSensorEntry
    MAX-ACCESS  not-accessible
    STATUS      deprecated
    DESCRIPTION
        "This table contains a list of the PDU's Auxiliary Sensors.
         The table contains zero, one, or more rows, depending
         upon the number of PDUs being monitored and the number of
         auxiliary sensors installed for each PDU.
         The NMS cannot create or delete rows in the table. The rows are
         created by the agent based upon the capabilities of the PDUs
         being monitored.  Each row in the table represents an auxiliary
         sensor in a PDU."
    ::= { lgpPduAuxiliarySensors 10 }

    lgpPduAuxSensorEntry OBJECT-TYPE
        SYNTAX      LgpPduAuxSensorEntry
        MAX-ACCESS  not-accessible
        STATUS      deprecated
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduAuxSensorTable'.
             This table is indexed by both the 'lgpPduEntryIndex' which is
             the sole index into the 'lgpPduTable' and the
             'lgpPduAuxSensorIndex'which is a unique identifier for the
             auxiliary sensor attached to the given PDU.  Taken together these
             two indexes uniquely identify an Auxiliary Sensor within this
             agent."
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduAuxSensorIndex
        }
        ::= { lgpPduAuxSensorTable 1 }

    LgpPduAuxSensorEntry ::= SEQUENCE
    {
        lgpPduAuxSensorIndex                   Unsigned32,
        lgpPduAuxSensorMeasType                INTEGER,
        lgpPduAuxSensorId                      Unsigned32,
        lgpPduAuxSensorSysAssignLabel          DisplayString,
        lgpPduAuxSensorPositionRelative        Unsigned32,
        lgpPduAuxSensorUsrLabel                DisplayString,
        lgpPduAuxSensorUsrTag1                 DisplayString,
        lgpPduAuxSensorUsrTag2                 DisplayString,
        lgpPduAuxSensorTempSerialNum           DisplayString,
        lgpPduAuxSensorHumSerialNum            DisplayString,
        lgpPduAuxSensorTempMeasurementDegF     Integer32,
        lgpPduAuxSensorTempThrshldUndrAlmDegF  Integer32,
        lgpPduAuxSensorTempThrshldOvrAlmDegF   Integer32,
        lgpPduAuxSensorTempThrshldUndrWarnDegF Integer32,
        lgpPduAuxSensorTempThrshldOvrWarnDegF  Integer32,
        lgpPduAuxSensorTempMeasurementDegC     Integer32,
        lgpPduAuxSensorTempThrshldUndrAlmDegC  Integer32,
        lgpPduAuxSensorTempThrshldOvrAlmDegC   Integer32,
        lgpPduAuxSensorTempThrshldUndrWarnDegC Integer32,
        lgpPduAuxSensorTempThrshldOvrWarnDegC  Integer32,
        lgpPduAuxSensorHumMeasurement          Unsigned32,
        lgpPduAuxSensorHumThrshldUndrAlm       Unsigned32,
        lgpPduAuxSensorHumThrshldOvrAlm        Unsigned32,
        lgpPduAuxSensorHumThrshldUndrWarn      Unsigned32,
        lgpPduAuxSensorHumThrshldOvrWarn       Unsigned32
    }

    lgpPduAuxSensorIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      deprecated
        DESCRIPTION
            "This is the index indicating the nth element of the table."
        ::= { lgpPduAuxSensorEntry 1 }

    lgpPduAuxSensorMeasType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            temperature(1),
            humidity(2),
            temperature-and-humidity(3)
        }
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "not-specified
                The type of sensor is unknown.
             temperature
                The sensor in this row of the table measures temperature.
             humidity
                The sensor in this row of the table measures relative humidity.
             temperature-and-humidity
                The sensor in this row of the table measures both temperature
                and relative humidity."
        ::= { lgpPduAuxSensorEntry 5 }

    lgpPduAuxSensorId OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "System assigned auxiliary sensor identification number. The value
             assigned is product specific."
        ::= { lgpPduAuxSensorEntry 10 }

    lgpPduAuxSensorSysAssignLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "Label assigned to the auxiliary sensor at runtime by the system.
             The value is independent of any user assigned label or asset tag."
        ::= { lgpPduAuxSensorEntry 15 }

    lgpPduAuxSensorPositionRelative OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "Auxiliary sensor relative position.  This is a one-based value
             that indicates the sensor's position relative to the sensor string
             connector."
        ::= { lgpPduAuxSensorEntry 20 }

    lgpPduAuxSensorUsrLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "User assigned auxiliary sensor label."
        ::= { lgpPduAuxSensorEntry 25 }

    lgpPduAuxSensorUsrTag1 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "User assigned Tag to assist in identifying or grouping this
             auxiliary sensor within the end-users domain."
        ::= { lgpPduAuxSensorEntry 30 }

    lgpPduAuxSensorUsrTag2 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "User assigned Tag to assist in identifying or grouping this
             auxiliary sensor within the end-users domain."
        ::= { lgpPduAuxSensorEntry 35 }

    lgpPduAuxSensorTempSerialNum OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The temperature sensor's globally unique serial number assigned at
             the time of manufacture."
        ::= { lgpPduAuxSensorEntry 40 }

    lgpPduAuxSensorHumSerialNum OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "The humidity sensor's globally unique serial number assigned at
             the time of manufacture."
        ::= { lgpPduAuxSensorEntry 45 }

    lgpPduAuxSensorTempMeasurementDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "Temperature measured at the temperature sensor reported in
             degrees Fahrenheit."
        ::= { lgpPduAuxSensorEntry 50 }

    lgpPduAuxSensorTempThrshldUndrAlmDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Under temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or below this value."
        ::= { lgpPduAuxSensorEntry 55 }

    lgpPduAuxSensorTempThrshldOvrAlmDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Over temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxSensorEntry 60 }

    lgpPduAuxSensorTempThrshldUndrWarnDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Under temperature warning threshold.  A warning is activated if
             the temperature is equal to or below this value."
        ::= { lgpPduAuxSensorEntry 65 }

    lgpPduAuxSensorTempThrshldOvrWarnDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Over temperature warning threshold.  A warning is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxSensorEntry 70 }

    lgpPduAuxSensorTempMeasurementDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "Temperature measured at the temperature sensor reported in
             degrees Celsius."
        ::= { lgpPduAuxSensorEntry 75 }

    lgpPduAuxSensorTempThrshldUndrAlmDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Under temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or below this value."
        ::= { lgpPduAuxSensorEntry 80 }

    lgpPduAuxSensorTempThrshldOvrAlmDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Over temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxSensorEntry 85 }

    lgpPduAuxSensorTempThrshldUndrWarnDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Under temperature warning threshold.  A warning is activated if
             the temperature is equal to or below this value."
        ::= { lgpPduAuxSensorEntry 90 }

    lgpPduAuxSensorTempThrshldOvrWarnDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Over temperature warning threshold.  A warning is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxSensorEntry 95 }

    lgpPduAuxSensorHumMeasurement OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-only
        STATUS      deprecated
        DESCRIPTION
            "Relative Humidity measured at the humidity sensor."
        ::= { lgpPduAuxSensorEntry 100 }

    lgpPduAuxSensorHumThrshldUndrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Under relative humidity alarm threshold.  An alarm is activated
             if the relative humidity is equal to or below this value."
        ::= { lgpPduAuxSensorEntry 105 }

    lgpPduAuxSensorHumThrshldOvrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Over relative humidity alarm threshold.  An alarm is activated
             if the relative humidity is equal to or above this value."
        ::= { lgpPduAuxSensorEntry 110 }

    lgpPduAuxSensorHumThrshldUndrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Under relative humidity warning threshold.  A warning is activated
             if the relative humidity is equal to or below this value."
        ::= { lgpPduAuxSensorEntry 115 }

    lgpPduAuxSensorHumThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      deprecated
        DESCRIPTION
            "Over relative humidity warning threshold.  A warning is activated
             if the relative humidity is equal to or above this value."
        ::= { lgpPduAuxSensorEntry 120 }

lgpPduAuxMeasTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduAuxMeasEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of the PDU's Auxiliary Sensor Measurements.
         The table contains zero, one, or more rows, depending
         upon the number of PDUs being monitored, the number of auxiliary
         sensors installed for each PDU, and the number of measurements within
         each sensor. The NMS cannot create or delete rows in the table. The
         rows are created by the agent based upon the capabilities of the PDUs
         being monitored.  Each row in the table represents an auxiliary
         sensor measurement in a PDU."
    ::= { lgpPduAuxiliarySensors 15 }

    lgpPduAuxMeasEntry OBJECT-TYPE
        SYNTAX      LgpPduAuxMeasEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduAuxMeasTable'.
             This table is indexed by 'lgpPduEntryIndex' which is
             the sole index into the 'lgpPduTable', 'lgpPduAuxSensorIndex' which
             is a unique identifier for the auxiliary sensor attached to the
             given PDU, and 'lgpPduAuxMeasSensorMeasurementIndex' which is the
             measurement's index identified on the sensor. Taken together these
             three indexes uniquely identify an Auxiliary Sensor Measurement
             within this agent."
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduAuxMeasSensorIndex,
            lgpPduAuxMeasSensorMeasurementIndex
        }
        ::= { lgpPduAuxMeasTable 1 }

    LgpPduAuxMeasEntry ::= SEQUENCE
    {
        lgpPduAuxMeasSensorIndex               Unsigned32,
        lgpPduAuxMeasSensorMeasurementIndex    Unsigned32,
        lgpPduAuxMeasType                      INTEGER,
        lgpPduAuxMeasSensorSysAssignLabel      DisplayString,
        lgpPduAuxMeasUsrLabel                  DisplayString,
        lgpPduAuxMeasUsrTag1                   DisplayString,
        lgpPduAuxMeasUsrTag2                   DisplayString,
        lgpPduAuxMeasSensorSerialNum           DisplayString,
        lgpPduAuxMeasTempDegF                  Integer32,
        lgpPduAuxMeasTempThrshldUndrAlmDegF    Integer32,
        lgpPduAuxMeasTempThrshldOvrAlmDegF     Integer32,
        lgpPduAuxMeasTempThrshldUndrWarnDegF   Integer32,
        lgpPduAuxMeasTempThrshldOvrWarnDegF    Integer32,
        lgpPduAuxMeasTempDegC                  Integer32,
        lgpPduAuxMeasTempThrshldUndrAlmDegC    Integer32,
        lgpPduAuxMeasTempThrshldOvrAlmDegC     Integer32,
        lgpPduAuxMeasTempThrshldUndrWarnDegC   Integer32,
        lgpPduAuxMeasTempThrshldOvrWarnDegC    Integer32,
        lgpPduAuxMeasHum                       Unsigned32,
        lgpPduAuxMeasHumThrshldUndrAlm         Unsigned32,
        lgpPduAuxMeasHumThrshldOvrAlm          Unsigned32,
        lgpPduAuxMeasHumThrshldUndrWarn        Unsigned32,
        lgpPduAuxMeasHumThrshldOvrWarn         Unsigned32,
        lgpPduAuxMeasDrClosureState            INTEGER,
        lgpPduAuxMeasDrClosureConfig           INTEGER,
        lgpPduAuxMeasCntctClosureState         INTEGER,
        lgpPduAuxMeasCntctClosureConfig        INTEGER,
        lgpPduAuxMeasDiffPressure              Integer32,
        lgpPduAuxMeasDiffPressureThrshldUndrAlm         Integer32,
        lgpPduAuxMeasDiffPressureThrshldOvrAlm          Integer32,
        lgpPduAuxMeasDiffPressureThrshldUndrWarn        Integer32,
        lgpPduAuxMeasDiffPressureThrshldOvrWarn         Integer32,
        lgpPduAuxMeasLeakDetectState           INTEGER
    }

    lgpPduAuxMeasSensorIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is the index indicating the sensor the measurement is accessed
             from."
        ::= { lgpPduAuxMeasEntry 1 }

    lgpPduAuxMeasSensorMeasurementIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This is the measurement's index identified on the sensor."
        ::= { lgpPduAuxMeasEntry 5 }

    lgpPduAuxMeasType OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            temperature(1),
            humidity(2),
            door-closure(3),
            contact-closure(4),
            differential-pressure(5),
            leak-detection(6)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "not-specified
                The type of measurement is unknown.
             temperature
                The measurement in this row of the table measures temperature.
             humidity
                The measurement in this row of the table measures relative
                humidity.
             door-closure
                The measurement in this row of the table measures the state of a
                door.
             contact-closure
                The measurement in this row of the table measures the state of a
                contact closure.
             differential-pressure
                The measurement in this row of the table measures differential pressure.
             leak-detection
                The measurement in this row of the table measures the state of a
                leak detection sensor."
        ::= { lgpPduAuxMeasEntry 10 }

    lgpPduAuxMeasSensorSysAssignLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Label assigned to the auxiliary sensor at runtime by the system.
             The value is independent of any user assigned label or asset tag."
        ::= { lgpPduAuxMeasEntry 15 }

    lgpPduAuxMeasUsrLabel OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned auxiliary sensor measurement label."
        ::= { lgpPduAuxMeasEntry 20 }

    lgpPduAuxMeasUsrTag1 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned Tag to assist in identifying or grouping this
             auxiliary sensor measurement within the end-users domain."
        ::= { lgpPduAuxMeasEntry 25 }

    lgpPduAuxMeasUsrTag2 OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "User assigned Tag to assist in identifying or grouping this
             auxiliary sensor measurement within the end-users domain."
        ::= { lgpPduAuxMeasEntry 30 }

    lgpPduAuxMeasSensorSerialNum OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The sensor's globally unique serial number assigned at
             the time of manufacture."
        ::= { lgpPduAuxMeasEntry 35 }

    lgpPduAuxMeasTempDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Temperature measured at the temperature sensor reported in
             degrees Fahrenheit."
        ::= { lgpPduAuxMeasEntry 40 }

    lgpPduAuxMeasTempThrshldUndrAlmDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 50 }

    lgpPduAuxMeasTempThrshldOvrAlmDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 55 }

    lgpPduAuxMeasTempThrshldUndrWarnDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under temperature warning threshold.  A warning is activated if
             the temperature is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 60 }

    lgpPduAuxMeasTempThrshldOvrWarnDegF OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Fahrenheit"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over temperature warning threshold.  A warning is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 65 }

    lgpPduAuxMeasTempDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Temperature measured at the temperature sensor reported in
             degrees Celsius."
        ::= { lgpPduAuxMeasEntry 70 }

    lgpPduAuxMeasTempThrshldUndrAlmDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 75 }

    lgpPduAuxMeasTempThrshldOvrAlmDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over temperature alarm threshold.  An alarm is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 80 }

    lgpPduAuxMeasTempThrshldUndrWarnDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under temperature warning threshold.  A warning is activated if
             the temperature is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 85 }

    lgpPduAuxMeasTempThrshldOvrWarnDegC OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 degrees Celsius"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over temperature warning threshold.  A warning is activated if the
             temperature is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 90 }

    lgpPduAuxMeasHum OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Relative Humidity measured at the humidity sensor."
        ::= { lgpPduAuxMeasEntry 95 }

    lgpPduAuxMeasHumThrshldUndrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under relative humidity alarm threshold.  An alarm is activated
             if the relative humidity is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 100 }

    lgpPduAuxMeasHumThrshldOvrAlm OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over relative humidity alarm threshold.  An alarm is activated
             if the relative humidity is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 105 }

    lgpPduAuxMeasHumThrshldUndrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under relative humidity warning threshold.  A warning is activated
             if the relative humidity is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 110 }

    lgpPduAuxMeasHumThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Unsigned32
        UNITS       "0.1 percent Relative Humidity"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over relative humidity warning threshold.  A warning is activated
             if the relative humidity is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 115 }

    lgpPduAuxMeasDrClosureState OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            open(1),
            closed(2)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The state of a door sensor measurement.
                not-specified
                    The door state is unknown.
                open
                    The door is in the open state.
                closed
                    The door is in the closed state."
        ::= { lgpPduAuxMeasEntry 120 }

    lgpPduAuxMeasDrClosureConfig OBJECT-TYPE
        SYNTAX      INTEGER
        {
            disabled(0),
            alarm-when-open(1)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Configure door state alarms. This object provides the ability to
             select when a door closure measurement should cause an alarm.
                disabled
                    The door state will never result in alarm.
                alarm-when-open
                    Activate an alarm when the door state becomes open."
        ::= { lgpPduAuxMeasEntry 125 }

    lgpPduAuxMeasCntctClosureState OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            open(1),
            closed(2)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "The state of a contact closure sensor measurement.
                not-specified
                    The contact closure state is unknown.
                open
                    The contact closure is in the open state.
                closed
                    The contact closure is in the closed state."
        ::= { lgpPduAuxMeasEntry 130 }

    lgpPduAuxMeasCntctClosureConfig OBJECT-TYPE
        SYNTAX      INTEGER
        {
            disabled(0),
            alarm-when-open(1),
            alarm-when-closed(2)
        }
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Configure contact closure state alarms. This object provides the
             ability to select when a contact closure measurement should
             activate an alarm.
                disabled
                    The contact closure state will never result in alarm.
                alarm-when-open
                    Activate an alarm when the contact closure state becomes
                    open.
                alarm-when-closed
                    Activate an alarm when the contact closure state becomes
                    closed."
        ::= { lgpPduAuxMeasEntry 135 }

    lgpPduAuxMeasDiffPressure OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 Pascal"
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "Pressure difference measured at the differential pressure sensor."
        ::= { lgpPduAuxMeasEntry 140 }

    lgpPduAuxMeasDiffPressureThrshldUndrAlm OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 Pascal"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under differential pressure alarm threshold.  An alarm is activated
             if the differential pressure is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 145 }

    lgpPduAuxMeasDiffPressureThrshldOvrAlm OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 Pascal"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over differential pressure alarm threshold.  An alarm is activated
             if the differential pressure is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 150 }

    lgpPduAuxMeasDiffPressureThrshldUndrWarn OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 Pascal"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Under differential pressure warning threshold.  A warning is activated
             if the differential pressure is equal to or below this value."
        ::= { lgpPduAuxMeasEntry 155 }

    lgpPduAuxMeasDiffPressureThrshldOvrWarn OBJECT-TYPE
        SYNTAX      Integer32
        UNITS       "0.1 Pascal"
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "Over differential pressure warning threshold.  A warning is activated
             if the differential pressure is equal to or above this value."
        ::= { lgpPduAuxMeasEntry 160 }

    lgpPduAuxMeasLeakDetectState OBJECT-TYPE
        SYNTAX      INTEGER
        {
            not-specified(0),
            no-leak-detected(1),
            leak-detected(2),
            leak-detection-pending(3),
            cable-fault(4)
        }
        MAX-ACCESS  read-only
        STATUS      current
        DESCRIPTION
            "not-specified
                The leak detection state is unknown.
             no-leak-detected
                No leak has been detected.
             leak-detected
                A leak has been detected.
             leak-detection-pending
                Characterization of possible leak is pending further analysis
                based on new data received from the sensor.
                This state may not occur at all, but if it does, it should occur
                only for a small amount of time before transitioning to 
                no-leak-detected or leak-detected.
             cable-fault
                A fault in the cable has been detected (for example, a
                disconnected cable).  The sensor will not be able to detect
                a leak.
            "
        ::= { lgpPduAuxMeasEntry 165 }

lgpPduAuxMeasOrderTable OBJECT-TYPE
    SYNTAX      SEQUENCE OF LgpPduAuxMeasOrderEntry
    MAX-ACCESS  not-accessible
    STATUS      current
    DESCRIPTION
        "This table contains a list of the PDU's Auxiliary Sensors
         and their respective 'location' in the lgpPduAuxMeasTable table.
         This table contains 1 row, for potential sensor for each PDU.
         The rows in this table are created by the agent based on the maximum
         number of sensor's supported for each PDU.

         Each row in the table represents an auxiliary sensor, identified by its
         factory assigned serial number and its placement in the lgpPduAuxMeasTable.
         If all serial numbers in this table are empty strings then the
         location of the sensors in the lgpPduAuxMeasTable will default to the
         agent's default placement algorithm.  If sensors in the
         lgpPduAuxMeasTable and are not represented by an entry in this table then
         the location of the unrepresented sensor(s) in the lgpPduAuxMeasTable,
         and other display mediums, will be determined by the agent, but in no
         case will an unrepresented sensor occupy a position reserved for a sensor
         present in this table.  Those unrepresented sensor's display location is
         not guaranteed to be consistent across reboots or rediscovery actions
         on the sensor bus.  Only sensors represented in this table are guarantted
         consistent placement as specified by their index entries (position) in
         this table.

         Note that it is possible to have entries in this table representing sensors
         that may not exist on the given PDU at runtime. These allocated by not present
         sensors will reduce the total number of sensors that can be displayed for
         the given PDU."

    ::= { lgpPduAuxiliarySensors 20 }

    lgpPduAuxMeasOrderEntry OBJECT-TYPE
        SYNTAX      LgpPduAuxMeasOrderEntry
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "This entry defines the attributes to be populated in the
             various columns of the 'lgpPduAuxMeasOrderTable'.
             This table is indexed by 'lgpPduEntryIndex' which is
             the sole index into the 'lgpPduTable' and 'lgpPduAuxMeasSensorIndex'
             which is a unique identifier for the auxiliary sensor attached to the
             given PDU. Taken together these two indexes uniquely
             identify a Auxiliary Sensor within this agent."
        INDEX
        {
            lgpPduEntryIndex,
            lgpPduAuxSensorOrderIndex
        }
        ::= { lgpPduAuxMeasOrderTable 1 }

    LgpPduAuxMeasOrderEntry ::= SEQUENCE
    {
        lgpPduEntryIndex                       Unsigned32,
        lgpPduAuxSensorOrderIndex              Unsigned32,
        lgpPduAuxMeasOrderSensorSerialNum      DisplayString
    }

    lgpPduAuxSensorOrderIndex OBJECT-TYPE
        SYNTAX      Unsigned32
        MAX-ACCESS  not-accessible
        STATUS      current
        DESCRIPTION
            "Index representing the position within the sensor string on the given PDU"
        ::= { lgpPduAuxMeasOrderEntry 5 }

   lgpPduAuxMeasOrderSensorSerialNum OBJECT-TYPE
        SYNTAX      DisplayString
        MAX-ACCESS  read-write
        STATUS      current
        DESCRIPTION
            "The sensor's globally unique serial number assigned at
             the time of manufacture.  The sensor represented by this
             serial number will be, if discovered, by the agent placed
             in the lgpPduAuxMeasTable at the location specified by the
             index entries herein.  A empty string in this object indicates
             an open display position that can be occupied by any sensor not
             given a specific display position in this table."
        ::= { lgpPduAuxMeasOrderEntry 15 }

END