--defines ROOMALERT12E-MIB for SNMP agent extension of Room Alert 12E
--Contents:	Global Registration Module
--		Room Alert OIDs - Enterprise 20916
--Version:	1.0.0
--Date:		WEB_RELEASE_DATE_PLACEHOLDER
--Developed By: AVTECH Software, Inc.

--
--Copyright (c) COPYRIGHT_YEAR_PLACEHOLDER AVTECH Software, Inc.
--

ROOMALERT12E-MIB DEFINITIONS ::= BEGIN


IMPORTS
	enterprises, IpAddress, Counter, TimeTicks
		FROM RFC1155-SMI
	OBJECT-TYPE
		FROM RFC-1212
	TRAP-TYPE
		FROM RFC-1215;


avtech			OBJECT IDENTIFIER ::= { enterprises 20916 }
products		OBJECT IDENTIFIER ::= { avtech 1 }
roomalert12E	OBJECT IDENTIFIER ::= { products 9 }
sensors			OBJECT IDENTIFIER ::= { roomalert12E 1 }
lightTower		OBJECT IDENTIFIER ::= { roomalert12E 2 }
internal-sen	OBJECT IDENTIFIER ::= { sensors  1 }
digital-sen1	OBJECT IDENTIFIER ::= { sensors  2 }
digital-sen2	OBJECT IDENTIFIER ::= { sensors  3 }
digital-sen3	OBJECT IDENTIFIER ::= { sensors  4 }
switch1			OBJECT IDENTIFIER ::= { sensors  5 }
switch2			OBJECT IDENTIFIER ::= { sensors  6 }
switch3			OBJECT IDENTIFIER ::= { sensors  7 }
switch4			OBJECT IDENTIFIER ::= { sensors  8 }
analog			OBJECT IDENTIFIER ::= { sensors  9 }
relay			OBJECT IDENTIFIER ::= { sensors 10 }
traps			OBJECT IDENTIFIER ::= { roomalert12E 3 }

-- Room Alert 12E MIB
-- Parameters




internal-sen-1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { internal-sen 1 }

internal-sen-2 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { internal-sen 2 }

internal-sen-3 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { internal-sen 3 }

internal-sen-4 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { internal-sen 4 }

internal-sen-5 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { internal-sen 5 }

internal-sen-6 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"Represents the sensor's label/"
::= { internal-sen 6 }

analog-1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The current status of the Room Alert 12E analog input (0-5VDC)."
::= { analog 1 }

analog-2 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The analog sensor's label."
::= { analog 2 }

relay-1 OBJECT-TYPE
	SYNTAX		INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The current status of the Room Alert 12E relay output."
::= { relay 1 }

relay-2 OBJECT-TYPE
	SYNTAX		OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION "The relay output's label."
::= { relay 2 }

digital-sen1-1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen1 1 }

digital-sen1-2 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen1 2 }

digital-sen1-3 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen1 3 }

digital-sen1-4 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen1 4 }

digital-sen1-5 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen1 5 }

digital-sen1-6 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"Represents the sensor's label/"
::= { digital-sen1 6 }

digital-sen2-1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen2 1 }

digital-sen2-2 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen2 2 }

digital-sen2-3 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen2 3 }

digital-sen2-4 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen2 4 }

digital-sen2-5 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen2 5 }

digital-sen2-6 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"Represents the sensor's label/"
::= { digital-sen2 6 }

digital-sen3-1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Celsius. If this sensor is a Digital Power Sensor, this value represents the Current reading in Amperage."
::= { digital-sen3 1 }

digital-sen3-2 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temperature or Temp/Humidity sensor, this value represents the current temperature in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Power reading in Watts."
::= { digital-sen3 2 }

digital-sen3-3 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current relative humidity in % Relative Humidity. If this sensor is a Digital Power Sensor, this value represents the Voltage reading in Volts."
::= { digital-sen3 3 }

digital-sen3-4 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Fahrenheit. If this sensor is a Digital Power Sensor, this value represents the Reference reading in Volts."
::= { digital-sen3 4 }

digital-sen3-5 OBJECT-TYPE
	SYNTAX  	INTEGER(0..65535)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"If this sensor is a Temp/Humidity sensor, this value represents the current heat index in Celsius."
::= { digital-sen3 5 }

digital-sen3-6 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"Represents the sensor's label/"
::= { digital-sen3 6 }

switch-sen1-1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The reading for switch sensor 1 (0 = OPEN, 1 = CLOSED)."
::= { switch1 1 }

switch-sen1-2 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The label for switch sensor 1."
::= { switch1 2 }

switch-sen2 OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The reading for switch sensor 2 (0 = OPEN, 1 = CLOSED)."
::= { switch2 1 }

switch-sen2-2 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The label for switch sensor 2."
::= { switch2 2 }

switch-sen3 OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The reading for switch sensor 3 (0 = OPEN, 1 = CLOSED)."
::= { switch3 1 }

switch-sen3-2 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The label for switch sensor 3."
::= { switch3 2 }

switch-sen4 OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The reading for switch sensor 4 (0 = OPEN, 1 = CLOSED)."
::= { switch4 1 }

switch-sen4-2 OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"The label for switch sensor 4."
::= { switch4 2 }

alarmmessage OBJECT-TYPE
	SYNTAX  	OCTET STRING
	ACCESS		read-only
	STATUS		mandatory
	DESCRIPTION	"Last Alarm Message"
::= { traps 1 }


-- Light Tower

lightTower-RE OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the red LED on the Light Tower."
::= { lightTower 1 }

lightTower-OR OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the orange LED on the Light Tower."
::= { lightTower 2 }

lightTower-GR OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the green LED on the Light Tower."
::= { lightTower 3 }

lightTower-WH OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the white LED on the Light Tower."
::= { lightTower 4 }

lightTower-BL OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the blue LED on the Light Tower."
::= { lightTower 5 }

lightTower-A1 OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the 1st audio alarm on the Light Tower."
::= { lightTower 6 }

lightTower-A2 OBJECT-TYPE
	SYNTAX  	INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the 2nd audio alarm on the Light Tower."
::= { lightTower 7 }

lightTower-RL OBJECT-TYPE
	SYNTAX		INTEGER(0..1)
	ACCESS		read-write
	STATUS		mandatory
	DESCRIPTION	"The status of the LTA's on-board relay output"
::= { lightTower 8 }


-- ROOMALERT12E TRAPS

tempalarm1-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A tempalarm1 trap signifies that the current
			temperature on external sensor 1 is outside the
			defined high or low threshold."
::= 1

room-alert-12E-snmp-trap TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A room-alert-12E-snmp-trap indicates that an alarm
			condition has occurred on the sensor inidcated
			by the alarmMessage variable."
::= 2

tempalarm2-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A tempalarm2 trap signifies that the current
			temperature on external sensor 2 is outside the
			defined high or low threshold."
::= 3

tempclear2-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A tempclear2 trap signifies that the current
			temperature on external sensor 2 has returned to
			a normal condition and is within the defined
			high or low threshold."
::= 4

tempalarm3-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A tempalarm3 trap signifies that the current
			temperature on external sensor 3 is outside the
			defined high or low threshold."
::= 5

tempclear3-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A tempclear3 trap signifies that the current
			temperature on external sensor 3 has returned to
			a normal condition and is within the defined
			high or low threshold."
::= 6

humidityalarm1-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A humidityalarm1 trap signifies that the current
			humidity on external sensor 1 is outside the
			defined high or low threshold."
::= 7

humidityclear1-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A humidityclear1 trap signifies that the current
			humidity on external sensor 1 has returned to
			a normal condition and is within the defined
			high or low threshold."
::= 8

humidityalarm2-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A humidityalarm2 trap signifies that the current
			humidity on external sensor 2 is outside the
			defined high or low threshold."
::= 9

humidityclear2-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A humidityclear2 trap signifies that the current
			humidity on external sensor 2 has returned to
			a normal condition and is within the defined
			high or low threshold."
::= 10

humidityalarm3-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A humidityalarm3 trap signifies that the current
			humidity on external sensor 3 is outside the
			defined high or low threshold."
::= 11

humidityclear3-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A humidityclear3 trap signifies that the current
			humidity on external sensor 3 has returned to
			a normal condition and is within the defined
			high or low threshold."
::= 12

switchalarm1-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchalarm1 trap signifies that switch sensor 1
			is in an alarm state."
::= 13

switchclear1-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchclear1 trap signifies that the switch sensor 1
			has returned to a normal state."
::= 14

switchalarm2-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchalarm2 trap signifies that switch sensor 2
			is in an alarm state."
::= 15

switchclear2-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchclear2 trap signifies that the switch sensor 2
			has returned to a normal state."
::= 16

switchalarm3-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchalarm3 trap signifies that switch sensor 3
			is in an alarm state."
::= 17

switchclear3-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchclear3 trap signifies that the switch sensor 3
			has returned to a normal state."
::= 18

switchalarm4-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchalarm4 trap signifies that switch sensor 4
			is in an alarm state."
::= 19

switchclear4-12E TRAP-TYPE
	ENTERPRISE	roomalert12E
	VARIABLES	{ alarmmessage }
	DESCRIPTION	"A switchclear4 trap signifies that the switch sensor 4
			has returned to a normal state."
::= 20
END